OPERATIONAL AND CONNECTION INFORMATION

Rc/Rh Connections

For installations having a separate 24VAC transformer for heating and cooling, the R connection can be separated into two connections, one for each transformer. This allows isolation between the two transformers to be preserved. To separate Rc from Rh, remove the factory supplied jumper between the Rc and Rh terminals. The Rh terminal powers the W output. The Rc terminal powers the Y1, Y/Y2, G and O outputs.

Wiring

For all wiring applications, use 22 AWG or larger wire. Continuous wire lengths over 100 ft. (30.5 m) should use 20 AWG or larger. Wire lengths are not to exceed 250 ft. (76 m) per run.

O/B Terminal - On HP Thermostat Only

This terminal is normally connected to the reversing valve of the heat pump. It is called O when the valve is energized in cooling and B when it is energized in heating. Option 10 of the Configuration Options makes the O/B selection.

Timers

There are several timers which influence the thermostat’s operation:

If any of the timers listed below is preventing the equipment from turning on, the display icons which show the equipment is operating will be flashing to indicate a turn-on delay is present.

Five-Minute Compressor Timeguard

This timer prevents the compressor from starting unless it has been off for 5 minutes. It can be defeated for one cycle by simultaneously pressing the FAN and UP keys.

22

Image 24
Contents Legacy Series Programmable Thermostat Designed and Assembled in the U.S.APage Table of Contents Safety Considerations Introduction Installation Considerations PowerModels Installation Thermostat LocationEnvironmental Hazard Backplate Mounting Secure Wires to Terminal Strip Terminal Designations Set Thermostat Configuration Configuration Options Summary Configuration Options Selection To Enter the Configuration ModeOption 01 Equipment type Option 03 Fahrenheit/Centigrade Option 04 Fan G on with W outputOption 07 Zoning Option 10 Reversing valveOption 12 Smart Recovery programmable model only Option 11 Minimum Deadband Between Heating And CoolingOption 13 Room Air Temperature Offset Option 15 Auto Changeover AvailabilityOption 16 Maximum Cycles Per Hour Option 17 Minimum Time Between Equipment StagesOption 18 Backlight Configuration Option 21 Keypad LockoutOption 99 Reset to Factory Defaults Option 26 Minimum Cooling SetpointOption 27 Maximum Heating Setpoint Check Thermostat Operation Checklist Features and Accessories BatteriesDisplay Lighting Door Switch Mounting OptionsWiring TimersOperational and Connection Information Rc/Rh ConnectionsError Codes Minimum On TimerCycle Timer Auto Changeover TimerOutputs Cool Heat EM HeatWiring Diagrams Single Speed A/C Thermostat Typical InstallationWiring Diagrams Single-stage Furnace with Air Conditioner and Split Power Thermostat Heat Stage 3 furnace Heat/Cool Stage Fan 24VAC Hot Heating FV/FK Fan Coil w/2-Stage Air Conditioner FV/FK Fan Coil w/2-Stage Heat Pump Thermostat Configuration Record Mode SettingsConfiguration Options Page Page Page Page IIT2---PAC---05

T2-PAC specifications

The Bryant T2-PAC is a standout unit in the realm of high-efficiency heating, ventilation, and air conditioning (HVAC) systems. Designed with modern comfort in mind, this system embodies advanced technologies and features that provide optimal performance and energy savings, making it a preferred choice for numerous homeowners and commercial spaces.

One of the key highlights of the Bryant T2-PAC is its innovative two-stage cooling and heating capabilities. This feature ensures that the system can modulate its output to meet varying comfort demands efficiently. By operating at a lower stage most of the time, the T2-PAC minimizes energy consumption while still delivering reliable heating or cooling when required, ensuring maximum comfort throughout the day and night.

Incorporating advanced inverter technology, the Bryant T2-PAC stands out with exceptional energy efficiency ratings. This technology allows the system to adjust its compressor speed based on real-time indoor temperature demands, addressing fluctuations in a home or building's environment swiftly. As a result, users may enjoy lower utility bills while remaining comfortable regardless of the season.

The system also features a robust build quality with stainless steel components that enhance durability and extend the unit's lifespan. Its smart design emphasizes quieter operation, ensuring that the system runs discreetly without disrupting daily life or activities.

In addition to its performance, the Bryant T2-PAC offers convenient smart home integration through user-friendly controls. Homeowners can easily adjust settings via mobile applications or voice-controlled devices, enhancing user experience and accessibility.

The T2-PAC is designed with eco-conscious consumers in mind. Its eco-friendly refrigerant reduces the system’s environmental impact while maintaining performance. Moreover, the Bryant brand is known for its commitment to reliability and comfort, evidenced by its extensive warranty offerings and the robust customer support network.

In summary, the Bryant T2-PAC incorporates innovative technologies and features that ensure efficient and effective climate control. With its two-stage operation, advanced inverter technology, durable build, quiet operation, smart home compatibility, and eco-friendly design, the T2-PAC is truly a versatile heating and cooling solution suitable for diverse environments. Investing in this unit means investing in enduring comfort and significant energy savings for the long term.