Bryant T2-PAC Error Codes, Minimum On Timer, Cycle Timer, Auto Changeover Timer

Page 25

Minimum On Timer

Once the equipment has been turned on, it must remain on for 3 minutes. A change in mode or setpoint will cancel this timer.

Cycle Timer

Based on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or 10 minutes. This much time must elapse from the start of one cycle before another cycle can start. It serves to impose the cycles per hour limits. It can be defeated for one cycle by simultaneously pressing the FAN and UP keys.

Auto Changeover Timer

To prevent unnecessary cycling between heating and cooling modes, this timer prevents a changeover to the opposite mode until a demand exists in the opposite mode for 20 minutes. It is defeated when setpoints are changed so that the opposite mode is immediately available if desired.

Error Codes

Two error messages indicate problems with the thermostat’s operation. If the room temperature sensor fails, the temperature display will show ---, two dashes. If there is an internal memory failure, the temperature display will show E4. The remedy for each of these is to replace the thermostat.

Table 1 shows the thermostat outputs for each available stage of heating or cooling. It may be useful in checkout or troubleshooting.

23

Image 25
Contents Designed and Assembled in the U.S.A Legacy Series Programmable ThermostatPage Table of Contents Safety Considerations Introduction Power Installation ConsiderationsModels Thermostat Location InstallationEnvironmental Hazard Backplate Mounting Secure Wires to Terminal Strip Terminal Designations Set Thermostat Configuration Configuration Options Summary To Enter the Configuration Mode Configuration Options SelectionOption 01 Equipment type Option 04 Fan G on with W output Option 03 Fahrenheit/CentigradeOption 07 Zoning Option 10 Reversing valveOption 11 Minimum Deadband Between Heating And Cooling Option 12 Smart Recovery programmable model onlyOption 15 Auto Changeover Availability Option 13 Room Air Temperature OffsetOption 16 Maximum Cycles Per Hour Option 17 Minimum Time Between Equipment StagesOption 21 Keypad Lockout Option 18 Backlight ConfigurationOption 26 Minimum Cooling Setpoint Option 99 Reset to Factory DefaultsOption 27 Maximum Heating Setpoint Check Thermostat Operation Checklist Batteries Features and Accessories Display Lighting Mounting Options Door SwitchTimers WiringOperational and Connection Information Rc/Rh ConnectionsMinimum On Timer Error CodesCycle Timer Auto Changeover TimerCool Heat EM Heat OutputsSingle Speed A/C Thermostat Typical Installation Wiring DiagramsWiring Diagrams Single-stage Furnace with Air Conditioner and Split Power Thermostat Heat Stage 3 furnace Heat/Cool Stage Fan 24VAC Hot Heating FV/FK Fan Coil w/2-Stage Air Conditioner FV/FK Fan Coil w/2-Stage Heat Pump Mode Settings Thermostat Configuration RecordConfiguration Options Page Page Page Page IIT2---PAC---05