LG Electronics LP091HEM-Y8 manual Complaint Cause Remedy

Page 41

COMPLAINT

CAUSE

REMEDY

 

 

 

Fan motor will not run.

No power

Check voltage at outlet. Correct if none.

 

 

 

 

Power supply cord

Check voltage to rotary switch. If none, check

 

 

power supply cord. Replace cord if circuit is open.

 

 

 

 

Rotary switch

Check switch continuity. Refer to wiring diagram

 

 

for terminal identification. Replace switch if

 

 

defective.

 

 

 

 

Wire disconnected or

Connect wire. Refer to wiring diagram for terminal

 

connection loose

identification. Repair or replace loose terminal.

 

 

 

 

Capacitor (Discharge

Test capacitor.

 

capacitor before testing.)

Replace if not within ±10% of manufacturer's

 

 

rating. Replace if shorted, open, or damaged.

 

 

 

 

Will not rotate

Fan blade hitting shroud or cross flow fan hitting

 

 

scroll. Realign assembly.

 

 

Units using slinger ring condenser fans must

 

 

have 1/4 to 5/16 inch clearance to the base. If it is

 

 

hitting the base, shim up the bottom of the fan

 

 

motor with mounting screw(s).

 

 

Check fan motor bearings; if motor shaft will not

 

 

rotate, replace the motor.

 

 

 

Fan motor runs

Revolves on overload.

Check voltage. See limits on this page. If not within

intermittently

 

limits, call an electrician.

 

 

Test capacitor.

 

 

Check bearings. Does the fan blade rotate freely?

 

 

If not, replace fan motor.

 

 

Pay attention to any change from high speed to

 

 

low speed. If the speed does not change, replace

 

 

the motor.

 

 

 

Fan motor noise.

Grommets

Check grommets; if worn or missing, replace them.

 

 

 

 

Fan

If cracked, out of balance, or partially missing,

 

 

replace it.

 

 

 

 

Turbo fan

If cracked, out of balance, or partially missing,

 

 

replace it.

 

 

 

 

Loose set screw

Tighten it.

 

 

 

 

Worn bearings

If knocking sounds continue when running or

 

 

loose, replace the motor. If the motor hums or

 

 

noise appears to be internal while running,

 

 

replace motor.

 

 

 

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 41 -

Only for training and service purposes

LGE Internal Use Only

 

Image 41
Contents SVC Manual LGE Internal Use Only SpecificationSleeve and the Rear Grille Features and BenefitsOutdoor Air Temperature Switchover Door Switch/Occupancy SensorTemperature limits Quick Heater RecoveryVentilation Control LocationsOperation Electric Heating Model Additional Controls Temperature LimitingRemoving the Front Grille Additional ControlsREMOTE/LOCAL Control Molex Housing SpecEnergy Saver Front Desk ControlFront Grille Disassembly InstructionsMechanical Parts Control BOX Electric Heater Electric Heater Model only AIR Handling PartsAxial FAN Cross Flow FANShroud Electrical PartsOutdoor Motor Compressor6 P.C.B Power CordCondenser Refrigeration CycleEvaporator Capillary TubeLGE Internal Use Only Pulling Vacuum HOW to Install the Unit InstallationDimension of air conditioner Dimension of sleeve assembly optionalGeneral Wall Sleeve InstallationWall Case Installation Data As shipped, the LG wall sleeve is ready for installation Installation of Wall Case in Wall OpeningPreparation of the Front Grille Preparation of the Wall Case for All Types of ConstructionLGE Internal Use Only Sub-Base Connected Unit Installation Electrical Requirements Electrical SafetyElectrical Data for 230/208V Model 208, 230, and 208/230 Volt UnitsInstallation Field Installed AccessoriesControl Panel Key Lock DescriptionHazardous Voltage Condensate Disposal Pump Kit InstallationPart No AYSB2101 Place the top cover assembly back into the unit Spraying Architectural Grille Architecture Grille Aluminum Single PackPart No AYDR101 Drain InstallationCondensate Drain kit Outdoor Drain Kit Installation Outdoor Drain Kit InstallationChecklist Indoor Drain Kit InstallationLeveling Legs Part No AYLL101Leveling Leg Assembly Installation on Wall Sleeve Leveling Leg AssemblyJunction Box Kit Installation and Wiring Procedure Hard Wire KitPart No AYAGALA01 Use Copper Conductors OnlyVolt Units 208/230 Volt UnitsPart No AYRE110 Remote Escutcheon KitPart No AYSB1101 230/208V 20A AYSB2101 230/208V 30A SubbaseTo each installation instruction for that accessory After wiring is complete, mount covers a and F toSkirting Hole Location Right Cover Assembly Subbase with provided screws. Figure Outside Dimensions Troubleshooting Guide Piping System 066mm 406mm 505mmTroubleshooting Guide Fails to Start Complaint Cause Remedy 208/230V 187V 253V Room AIR Conditioner Voltage LimitsComplaint Cause Remedy Th2 Thermistor for Evaporator pipe temperature Piping DiagramsTh3 Thermistor for outdoor Air temperature Th4 Thermistor for Condenser pipe Air temperatureCN-NN Schematic Diagram435300B Exploded ViewJanuary