Installation of Unit

Vacuum Drying of the Connecting Pipes and the Indoor Unit

The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor.

1.Confirm that both the liquid side valve and the gas side valve are set to the closed position.

2.After connecting the piping, check the joints for gas leakage with gas leak detector.

3.Remove the service port nut, and connect the gauge manifold and the vacuum pump to the service port by the charge hose.

4.Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below - 76cmHg.

5.Remove the valve stem nuts, and fully open the stems of the 2-way and 3-way valves with a hexagon wrench.

6.Tighten the valve stem nuts of the 2-way valve and 3-way valve.

7.Disconnect the charge hose and fit the nut to the service port. (Tightening torque: 1.8kg.m)

Indoor unit

Liquid side

 

 

 

Closed

Outdoor unit

 

 

2-way valve/

 

 

 

3-way valve

 

 

 

Gas side

 

 

 

3-way

 

 

 

valve

Closed

 

 

 

 

Vaccum pump

 

 

 

OPEN

CLOSE

 

 

 

 

Installation Manual

17

Image 17
Contents LG Floor Standing Type Air Conditioner Table of Contents Use the correctly rated breaker or fuse Always ground the productOperation Be sure the installation area does not deteriorate with ageUse two or more people to lift and transport the product Keep level even when installing the productSelection of the best location Installation of UnitPiping length and the elevation Refrigerant amount Indoor Unit InstallationOutdoor unit Installation Selecting the locationOutdoor Unit Installation guide at the seasideInstallation works Descriptions Installation MethodInstallation Parts, Tools Use Preparation of installation parts and toolsCut the pipes and the cable Preparation of PipingMove the indoor tubing and drain hose to the hole Precautions in bendingConnection of piping Connecting the Cable to Indoor Unit Connecting the cables to the outdoor unit Connecting pipings to the outdoor unitPower supply Power Supply and WiringVacuum Drying of the Connecting Pipes and the Indoor Unit Form the Piping Final Check and Test Run Memo Floor Standing type Air Conditioner