Installation of Unit
TheIndoor UnitInstallation
| 200mm |
|
70mm | 90mm | 70mm |
| ||
|
|
Wall
Core Drill
1. The mounting floor should be strong and solid |
enough to prevent it from vibration. |
INSIDEOUTSIDE
2. Drill the piping hole with 70mm diameter hole- |
core drill at either the right or the left of indoor |
unit. The hole should be sightly slant to the |
outdoor side. |
Plastic tube (Bushing)
Wall
3. | Insert the plastic tube through the hole. |
4. | Cut the extruded outside part of the plastic |
| tube, if necessary. |
Tilt
Cut if necessary
More than 15mm
OutdoorunitInstallation
1.Install the outdoor unit on the concrete or any solid base securely and horizontally by securing it with bolts (Ø12mm) and nuts.
2.If there is any vibration transmitted to the building, mount the rubber underneath the outdoor unit.
Refrigerant amount
Before shipment, this air conditioner is filled with the rated amount of refrigerant including additional amount required for
MODEL | REFRIGERANT CHARGE | |
|
| |
20k/28k/30k/40k | 30g/m (1.06oz/m) | |
(BTU/h) | ||
| ||
|
| |
44k/48k/50k/55k/60k | 40g/m (1.41oz/m) | |
(BTU/h) | ||
| ||
|
| |
80k | 80g/m (2.82oz/m) | |
(BTU/h) | ||
| ||
|
|
Example) 28k/30k
In case of 10m long
8Floor Standing type Air Conditioner