LG Electronics MP03-VDLPM 10 1/2 Min 267 mm, Vent / 45 Degree Starter Elbow Connection

Page 12

10 1/2” Min.

(267 mm)

10 1/2” Min.

(267 mm)

Figure 14

D. Attach vent components to 45 degree starter elbow - Secure Vent SV4.5 direct vent system components are unitized concentric pipe components featuring positive twist lock connections (see Figure 15 ).

All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent compo- nents fit over the appliance collar to create the positive twist lock connection.

First Vent

Component

Align the dimple (four places) with the opening of the locking incline channel on appliance collar. Twist vent component clockwise to engage and seal.

Dimple

Locking

Incline Channel

45 degree starter elbow

Vent / 45 Degree Starter

Elbow Connection

Figure 15

To attach a vent component to the 45 degree starter elbow, align the dimpled end over the elbow, adjusting the radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar (refer to Figure 15 ).

Push the vent component against the starter elbow until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels.

The unitized design of the Secure Vent com- ponents will engage and seal both the inner and outer pipe without the need for sealant or screws. If desired a #6 x 1/2" screw may be used at the joint, but it is not required as the pipe will securely lock when twisted.

Note: Always use the starter elbow directly at the appliance 45° collar unless rigid straight pipe of flex pipe is used, as shown in Figure 17.

E. Attach vent components to each other - Other vent sections may be added to the previously installed section in accordance with the require- ments of the vertical vent figures and tables. To add another vent component to a length of vent run, align the dimpled end over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.

This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 16.

F. Install firestop/spacer at ceiling - When

using Secure Vent, use SV4.5VF firestop/spacer at ceiling joists; when using Secure Flex, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer must be installed on the top side of the joist.

Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner. Remember to maintain 1" (25 mm) clearance to combustibles, framing mem- bers, and attic or ceiling insulation when running vertical chimney sections. Attic insu- lation shield (96K94) may be used to obtain the required clearances indicated here. See installation accessories table on page 25.

G. Support the vertical vent run sections - Note - Proper venting support is very impor- tant. The weight of the vent must not be supported by the fireplace in any degree.

Support the vertical portion of the venting system every 8 feet (2.4m) above the fireplace vent outlet. One method of support is by utiliz- ing field provided support straps (conven- tional plumber's tape). Secure the plumber's tape to the framing members with nails or screws.

Arrow

Align the dimple (four places) of the

 

upper vent section with the opening of

 

the locking incline channel on the

 

lower vent section. Twist vent

 

component clockwise to engage and

 

seal until arrow and dimple align.

 

Dimple

 

 

Locking

 

 

Incline Channel

 

 

Connected

 

 

Vent Sections

Arrow

Arrow

Vent / Vent Section

 

 

Connection

 

Figure 16

Rigid Or Flex

Venting

Components May

Be Connected

Directly To The 45

Degree Collar.

Detail

Figure 17

Blocking

Support Straps (Plumber’s tape)

8 feet (2.4 m)

Maximum

1 inch

(25.4 mm) minimum clearance to combustibles

12

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Image 12
Contents OTL Report No -F-47-5 MPLDV-35NM-2Table of Contents Millivolt And Electronic Models All ModelsModel Orifice size Nat PropTypical Locations LocationModel No Shelf Height inches mm Top Vent ApplicationVertical Vent Termination Clearances Appliance and Vent ClearancesVent Termination Clearances Horizontal Vent Termination ClearancesTypical Installation Sequence Detailed Installation StepsRouting GAS Line Horizontal Vent Termination ClearancesCanadian Installation US Installation Meter/regulator assembly= Clearance to service regulator vent outlet Feet 91cm Inches 30cmModel No 1030 1162 419 109245 1/4 67 1/4 47 1/2 19 3/8 33 5/8 Corner Framing with Square Termination SV4.5HT-2Model No Install the Vent System These fireplaces must be vented directly to the outsideVertical Termination Systems Roof Vent Section Length Chart 10 1/2 Min 267 mm Vent / 45 Degree Starter Elbow ConnectionConnection Framing Dimensions for Roof Pitch 12/12If the vent system extends more than 5 Swivel JointVertical Vent FIGURES/TABLES SupportBracket Ceiling Firestop/Spacer SV4.5VF Detail ViewHorizontal Outside Wall Termination System Plan the vent runTypical Horizontal Vent Installation Install firestop/spacer at ceilingFrame exterior wall opening Four incline channels on the collar refer to onInstall Firestop/Spacer at exterior wall Install the desired terminationMm as shown in Figure Slide the collars of the termination ontoHorizontal Vent FIGURES/TABLES Exterior Wall ThicknessConnection not Directly AT Appliance Connection Directly AT ApplianceWall Wall Firestop/SpacerWall Ceiling Firestop/Spacer SV4.5VFInstall the Outer Flex Pipe Pull and extend the inner flexible vent pipePull and extend the outer flexible vent pipe Route Flex VentField Wiring Millivolt Wiring See FigureElectronic Wiring See Figure After the wiring is complete, replace the cover plateConnecting GAS Line Installing the Glass Door and Optional Hood Installing the Glass DoorING Embers and Volcanic Stones Burner Adjustments Burner AdjustmentFinishing Requirements Wall DetailsInstallation Accessories Cold Climate InsulationMantel Clearances Cat Cat. No. Model No. Description.2 Installation Code GAS Conversion KitsMillivolt Appliances Pilot Orifice Electronic Appliances Dexen Electronic Valves Model No Orifice size NaturalPage Page 850,043M REV. E 06/2008 West Taft Avenue Orange, CA