LG Electronics MP03-VDLPM Frame exterior wall opening, Typical Horizontal Vent Installation

Page 16

D. Frame exterior wall opening -

Locate the center of the vent outlet on the exterior wall according to the dimensions shown in Figure 9 on page 8.

Cut and/or frame an opening, 10-1/2" x 12-1/8" (267 mm x 308mm) inside dimensions, about this center.

E. Frame ceiling opening - If the vertical route is to penetrate a ceiling, use plumb line to locate the center above the appliance. Cut and/ or frame an opening, 10-1/2" x 10-1/2" (267

mmx 267 mm) inside dimensions, about this center (refer to Figure 14 on page 11 ).

F. Attach vent components to starter elbow -

To attach a vent component to the the starter elbow, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlets of

TYPICAL HORIZONTAL VENT INSTALLATION

Building

Support

Horizontal / Inclined Run

Brackets

SV4.5 HT-2

Support

 

Termination

Framing

 

 

 

SV4.5E90

 

 

Elbow

 

 

 

 

SV4.5L6/12/24/36/48

Exterior

Ceiling

 

Vent Sections

Wall

Vertical

Firestop/Spacer

Support Bracket Spacing

 

Rise

 

SV4.5 HT-2

 

 

Every 5 ft (1.52 m)

 

 

 

Termination

 

See Figure 17 on page 12 for

 

 

vertical vent section support.

 

 

 

Fireplace

Exterior

 

 

Wall

 

 

 

Figure 26

the four incline channels on the collar (refer to Figure 15 on page 12).

Push the vent component against the elbow until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe elements with the same procedure. Sealant and securing screws are not required.

Note: A 90 or 45 degree elbow may not be directly attached to the appliance elbow collar.

G.Attach vent components to each other - Other vent sections may be added to the pre- viously installed section in accordance with the requirements of the vent tables.

To add another vent component to a length of vent run, align the dimpled end of the compo- nent over the inclined channel end of the previously installed section, adjusting the ra- dial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section.

Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 16 on page 12.

H. Install firestop/spacer at ceiling -

When using Secure Vent, use SV4.5VF firestop/ spacer at ceiling joists; when using Secure Flex, use SF4.5VF firestop/spacer.

If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.

Remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.

I. Support the vertical run sections -

On the vertical run, support the venting sys- tem every 8 feet (2.4m) above the fireplace vent outlet with field provided support straps (Plumber's tape).

Attach the straps to the vent pipe and secure to the framing members with nails or screws. See Figure 17 on page 12.

J. Change vent direction - At transition from or to a horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected vent sec- tions. See Figure 18 on page 13.

K. Continue installation of horizontal/inclined sections - Continue with the installation of the straight vent sections in horizontal/inclined run as described in Step F.

Install support straps every 5 ft. (1.52 m) along horizontal/inclined vent runs using con- ventional plumber’s tape. See Figure 26, it is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.

It is important to maintain the required clear- ances to combustibles at the top and bottom for all horizontal/inclined runs.

Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical vent elements.

Clearances for horizontal vent elements are 1" (25 mm) at the sides and 1" (25 mm) on the bottom. Clearances above horizontal vent elements are 3" (76 mm) for all models and all applications. Exception: Clearance is 5" (127 mm) for MPLDV35, MPLDV40 & MPLDV45, when the center line of the hori- zontal run is less than 48" (1219 mm) above the fireplace top wrapper surface.

L. Assemble vent run to exterior wall - If not previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step D. Assemble the vent system to point where the terminus of the last section is within 7 in. (178 mm) to 11-1/4 in. (286 mm) inboard of the exterior surface to which the SV4.5 HT-2 termination is to be attached, see Figure 28.

16

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Image 16
Contents OTL Report No -F-47-5 MPLDV-35NM-2Table of Contents Millivolt And Electronic Models All ModelsModel Orifice size Nat PropTypical Locations LocationModel No Shelf Height inches mm Top Vent ApplicationVertical Vent Termination Clearances Appliance and Vent ClearancesVent Termination Clearances Horizontal Vent Termination ClearancesTypical Installation Sequence Detailed Installation StepsRouting GAS Line Horizontal Vent Termination ClearancesCanadian Installation US Installation Meter/regulator assembly= Clearance to service regulator vent outlet Feet 91cm Inches 30cmModel No 1030 1162 419 109245 1/4 67 1/4 47 1/2 19 3/8 33 5/8 Corner Framing with Square Termination SV4.5HT-2Model No These fireplaces must be vented directly to the outside Install the Vent SystemVertical Termination Systems Roof Vent Section Length Chart Vent / 45 Degree Starter Elbow Connection 10 1/2 Min 267 mmConnection Framing Dimensions for Roof Pitch 12/12If the vent system extends more than 5 Swivel JointVertical Vent FIGURES/TABLES SupportBracket Ceiling Firestop/Spacer SV4.5VF Detail ViewHorizontal Outside Wall Termination System Plan the vent runTypical Horizontal Vent Installation Install firestop/spacer at ceilingFrame exterior wall opening Four incline channels on the collar refer to onInstall Firestop/Spacer at exterior wall Install the desired terminationMm as shown in Figure Slide the collars of the termination ontoHorizontal Vent FIGURES/TABLES Exterior Wall ThicknessConnection not Directly AT Appliance Connection Directly AT ApplianceWall Wall Firestop/SpacerWall Ceiling Firestop/Spacer SV4.5VFInstall the Outer Flex Pipe Pull and extend the inner flexible vent pipePull and extend the outer flexible vent pipe Route Flex VentField Wiring Millivolt Wiring See FigureElectronic Wiring See Figure After the wiring is complete, replace the cover plateConnecting GAS Line Installing the Glass Door Installing the Glass Door and Optional HoodING Embers and Volcanic Stones Burner Adjustments Burner AdjustmentFinishing Requirements Wall DetailsCold Climate Insulation Installation AccessoriesMantel Clearances Cat Cat. No. Model No. DescriptionGAS Conversion Kits .2 Installation CodeMillivolt Appliances Pilot Orifice Electronic Appliances Dexen Electronic Valves Model No Orifice size NaturalPage Page 850,043M REV. E 06/2008 West Taft Avenue Orange, CA