State Industries GP 6 50YPC T 100 Draining and Flushing, Routine Preventive Maintenance

Page 24

Powered Anode Operation

To protect the glass-lined water tank from corrosion through electrolysis, this water heater is equipped with a non sacrificial powered anode rod. The powered anode rod is non sacrificial and should not need to be replaced unless damaged.

If the powered anode rod has been damaged then the powered anode rod should be removed and replaced from the water heater tank. IMPORTANT: If the damaged powered anode rod has not been replaced but has been remove permanently, this will void any warranties.

 

Powered Anode System

 

To ensure a long, trouble-free

Powered

operating life, this water

heater is equipped with a

Anode

powered anode system.

Rod

 

 

The powered anode rod is of

 

a permanent design and does

 

not need replacing unless

 

damaged.

FIGURE 22.

NOTE: Whether re-installing or replacing the powered anode rod, check for any leaks and immediately correct if found.

In replacing the powered anode:

1.Turn off electrical supply and gas supply to the water heater.

2.Shut off the water supply and open a nearby hot water faucet to depressurize the water tank.

3.Drain approximately 5 gallons of water from tank (Refer to the “Draining and Flushing” section for proper procedures). Close drain valve.

4.Remove the wiring connection on the top of the powered anode rod and remove the old powered anode rod (Figure 22).

5.Use Teflon® tape or approved pipe sealant on threads and install new anode rod.

6.Turn on water supply and open nearby hot water faucet to purge air from water system. Check for any leaks and immediately correct any if found.

7.Turn on electrical and gas supplies. Restart the water heater as directed under the “Operating Your Water Heater.” See the “Repair Parts Illustration” section for anode rod location.

TEFLON® is a registered trademark of E.I. Du Pont De Nemours and Company

Draining and Flushing

It is recommended that the tank be drained and flushed every 6 months to remove sediment which may build up during operation. The water heater should be drained if being shut down during freezing temperatures. To drain the tank, perform the following steps:

1.Turn off the gas to the water heater at the manual gas shut-off valve and turn off the electrical power to the gas control/thermostat valve.

2.Open a nearby hot water faucet until the water is not longer hot.

3.Close the cold water inlet valve.

4.Connect a hose to the drain valve and terminate it to an adequate drain or external to the building.

5.Open the water heater drain valve and allow all the water to drain from the tank. Flush the tank with water as needed to remove sediment.

6.Close the drain valve, refill the tank, and restart the heater as directed in this manual.

If the water heater is going to be shut down for an extended period, the drain valve should be left open.

IMPORTANT: Condensation may occur when refilling the tank and should not be confused with a tank leak.

Routine Preventive Maintenance

At least annually, a visual inspection should be made of the venting and air supply system, piping systems, and main burner. Check the water heater for the following:

Obstructions, damage, or deterioration in the venting system. Make sure the ventilation and combustion air supplies are not obstructed.

Clean any dust or debris from the louvers of the air intake chamber.

Soot and/or carbon on the main burner. Contact a qualified technician.

Leaking or damaged water and gas piping.

Presence of flammable or corrosive materials in the installation area.

Presence of combustible materials near the water heater.

After servicing this water heater, check to make sure it is working properly. (See “Operating Your Water Heater” section of this manual.)

IMPORTANT: If you lack the necessary skills required to properly perform this visual inspection, you should not proceed, but get help from a qualified technician.

24

Image 24
Contents Residential GAS Water Heaters Table of Contents Safe INSTALLATION, USE and Service Safety PrecautionsFire or Explosion Hazard Typical Installation GET to Know Your Water Heater GAS ModelsInstalling Your GAS Water Heater Unpacking the Water Heater Excessive Weight HazardImportant Information About This Water Heater Consumer InformationLocation Requirements Site LocationCarbon Monoxide Poisoning Hazard Clearances and Accessibility State of CaliforniaGas Pressure Testing GAS SupplyGas Requirements Gas PipingGas Pipe Capacity Table Combustion AIR & Ventilation Unconfined SpaceConfined Space Minimum Btuh InputAll Air from Inside the Building All Air from OutdoorsLouvers and Grilles Draft Hood Installation Vent Pipe SystemVent Connectors Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingTemperature and Pressure Relief Valve Closed System/Thermal ExpansionTemperature & Pressure Relief Valve Relief Valve and Pipe InsulationCombination Space Heating/Potable Water System Discharge LineSolar Installation Wiring DiagramElectrical Connections Installation Checklist Important Information about this Water HeaterOperating Your Water Heater Operating InstructionsWater Heater Operation Checking the DraftBurn Hazard Water Temperature Regulation Burner FlamesEmergency Shut Down Safety Shut-off Operational ConditionsCondensation Water Heater SoundsRoutine Preventive Maintenance Powered Anode OperationDraining and Flushing Maintenance of Your Water Heater Replacement PartsRemoving the Manifold/Burner Assembly Removing the Burner from the Manifold/ Burner AssemblyReplacing the Flame Sense/Hot Surface igniter Assembly Cleaning the Combustion Chamber and Air Diverter AssemblyReplacing the Manifold/Burner Assembly Removing and Replacing the Gas Control Valve/Thermostat Removing the Gas Control Valve/ThermostatReplacing the Gas Valve Pressurized Combustion Chamber System Operational Checklist Troubleshooting ChartCont Control Display Troubleshooting Control Display Status Problem SolutionControl Display Status Problem Solution FV-SENSE and Open Flashing Troubleshooting Flowchart YESRepair Parts List Repair Parts IllustrationListed Parts Kits and Illustrations Page Page Page Limited Residential GAS Warranty YearImportant Information

317998-002, GP 6 50YPC T 100, GP 6 40YPC T 100 specifications

State Industries has long been at the forefront of technological advancements and innovative design in the industrial market. The company has developed a range of high-efficiency products designed for various applications, including the GP 6 40YPC T 100 and GP 6 50YPC T 100 models, as well as the 317998-002 component. Each product in this lineup is characterized by specific features and cutting-edge technologies tailored to meet diverse operational needs.

The GP 6 40YPC T 100 model boasts a robust construction aimed at durability and resilience in demanding environments. Its design incorporates advanced materials that resist wear and corrosion, ensuring a prolonged lifespan and reduced maintenance requirements. The model operates efficiently even in high-pressure scenarios, making it suitable for various industrial applications, including manufacturing and processing.

In contrast, the GP 6 50YPC T 100 model is designed with a focus on maximizing performance and energy efficiency. It features an optimized airflow system that enhances heat dissipation, preventing overheating and maintaining operational integrity. This model is ideal for applications that require continuous operation, as it minimizes downtime and maximizes productivity. Additionally, the GP 6 50YPC T 100 is equipped with smart technology that monitors performance metrics, providing real-time feedback on operational efficiency.

The 317998-002 component serves as a critical element in both models, acting as a versatile interface that integrates seamlessly with existing systems. It is designed to enhance connectivity and facilitate communication between various industrial components, promoting improved efficiency and ease of integration.

Both the GP 6 models and the 317998-002 feature user-friendly interfaces, allowing operators to easily manage and adjust settings. This focus on user experience helps to reduce training time and improve overall operational efficiency. Furthermore, both models adhere to strict industry standards, ensuring reliability and safety in all conditions.

In summary, State Industries' GP 6 40YPC T 100 and GP 6 50YPC T 100 models, along with the 317998-002 component, represent the pinnacle of innovation and reliability in industrial solutions. Their advanced features, technologies, and characteristics make them suitable choices for organizations looking to enhance productivity and operational efficiency in a variety of applications. With a commitment to quality and performance, State Industries continues to set the standard for excellence in the industry.