State Industries 317998-002, GP 6 50YPC T 100, GP 6 40YPC T 100 FV-SENSE and Open Flashing

Page 32

cont.

 

 

CONTROL DISPLAY STATUS

PROBLEM

SOLUTION

 

 

 

 

 

11.

“FV-SENSE” and “OPEN” Flashing

 

1. Check all wiring to the flammable vapor

Flammable Vapor Sensor is open

sensor.

 

 

 

 

2. Remove the connectors from the

 

 

 

 

flammable vapor sensor and measure

 

 

 

 

the resistance of the sensor with an

 

 

 

 

ohmmeter.

 

 

 

 

A. If the reading taken is more than

 

 

 

 

1.7 million ohms, replace the

 

 

 

 

flammable vapor sensor.

 

 

 

 

B. If the reading taken is less than 1.7

 

 

 

 

million ohms, and the wiring from

 

 

 

 

the control to the sensor is good,

 

 

 

 

replace the lower control.

12.

“FV-SENSE” and “SHORT” Flashing

 

1. Check all wiring to the flammable vapor

Flammable Vapor Sensor is

sensor.

 

 

 

shorted

2. Remove the connectors from the

 

 

 

 

 

 

 

 

flammable vapor sensor and measure

 

 

 

 

the resistance of the sensor with an

 

 

 

 

ohmmeter.

 

 

 

 

A. If the reading taken is less than

 

 

 

 

2000 ohms, replace the flammable

 

 

 

 

vapor sensor.

 

 

 

 

B. If the reading taken is more than

 

 

 

 

2000 ohms, and the wiring from the

 

 

 

 

control to the sensor is good,

 

 

 

 

replace the lower control.

13.

“THMSTR” and “OPEN” Flashing

 

1. Turn power off for 10 to 20 seconds then

The self-diagnostic test has

on again to clear this error code.

 

 

 

detected the temperature sensor

2. This part of the control cannot be

 

 

 

(thermistor) inside the immersion

 

 

 

replaced or serviced. If the error code

 

 

 

probe is open.

 

 

 

cannot be cleared, the lower control must

 

 

 

 

 

 

 

 

be replaced.

14.

“THMSTR” and “SHORT” Flashing

 

1. Turn power off for 10 to 20 seconds then

The self-diagnostic test has

on again to clear this error code.

 

 

 

detected the temperature sensor

2. This part of the control cannot be

 

 

 

(thermistor) inside the immersion

 

 

 

replaced or serviced. If the error code

 

 

 

probe is shorted.

 

 

 

cannot be cleared, the lower control must

 

 

 

 

 

 

 

 

be replaced.

15.

All Segments Flashing

 

1. Press and release each of the

The self-diagnostic check has

temperature adjustment buttons. If the

 

 

 

detected one or both of the

above action does not clear the error, the

 

 

 

temperature adjustment buttons

control will continue to regulate the water

 

 

 

are stuck.

temperature at the last setting. However,

 

 

 

 

settings will no longer be adjustable – the

 

 

 

 

upper control should be replaced.

16.

“P-ANODE” and “OPEN” Flashing

 

1. Check the wire that runs from the power

No current to Power Anode.

anode to the upper control. Check the

 

 

 

 

wire for damage, and to ensure that the

 

 

 

 

connectors are fully seated into the

 

 

 

 

mating connectors on both ends.

 

 

 

 

2. Check that the tank is full of water. Never

 

 

 

 

use this water heater unless it is

 

 

 

 

completely full of water. To prevent

 

 

 

 

damage to the tank, the tank must be

 

 

 

 

filled with water. Water must flow from

 

 

 

 

the hot water faucet before turning “ON”

 

 

 

 

gas to the water heater.

 

17.

“P-ANODE” Flashing

 

1. Turn the power off for 10 to 20 seconds

 

Power Anode circuit failure.

then on again to clear the error code.

 

 

 

 

2. If the error code persists or cannot be

 

 

 

 

cleared, replace the upper control.

 

 

 

 

 

32

Image 32
Contents Residential GAS Water Heaters Table of Contents Safe INSTALLATION, USE and Service Safety PrecautionsFire or Explosion Hazard Typical Installation GET to Know Your Water Heater GAS ModelsInstalling Your GAS Water Heater Unpacking the Water Heater Excessive Weight HazardImportant Information About This Water Heater Consumer InformationCarbon Monoxide Poisoning Hazard Location RequirementsSite Location Clearances and Accessibility State of CaliforniaGas Pressure Testing GAS SupplyGas Requirements Gas PipingGas Pipe Capacity Table Combustion AIR & Ventilation Unconfined SpaceConfined Space Minimum Btuh InputLouvers and Grilles All Air from Inside the BuildingAll Air from Outdoors Draft Hood Installation Vent Pipe SystemVent Connectors Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingTemperature and Pressure Relief Valve Closed System/Thermal ExpansionTemperature & Pressure Relief Valve Relief Valve and Pipe InsulationCombination Space Heating/Potable Water System Discharge LineElectrical Connections Solar InstallationWiring Diagram Installation Checklist Important Information about this Water HeaterOperating Your Water Heater Operating InstructionsBurn Hazard Water Heater OperationChecking the Draft Emergency Shut Down Water Temperature RegulationBurner Flames Safety Shut-off Operational ConditionsCondensation Water Heater SoundsDraining and Flushing Routine Preventive MaintenancePowered Anode Operation Maintenance of Your Water Heater Replacement PartsRemoving the Manifold/Burner Assembly Removing the Burner from the Manifold/ Burner AssemblyReplacing the Manifold/Burner Assembly Replacing the Flame Sense/Hot Surface igniter AssemblyCleaning the Combustion Chamber and Air Diverter Assembly Replacing the Gas Valve Removing and Replacing the Gas Control Valve/ThermostatRemoving the Gas Control Valve/Thermostat Pressurized Combustion Chamber System Operational Checklist Troubleshooting Chart Cont Control Display Troubleshooting Control Display Status Problem SolutionControl Display Status Problem Solution FV-SENSE and Open Flashing Troubleshooting Flowchart YESRepair Parts List Repair Parts IllustrationListed Parts Kits and Illustrations Page Page Page Limited Residential GAS Warranty YearImportant Information