State Industries 186589-001 Water Potable Heating and Space Heating, Closed Water System

Page 12

distance below the structural floor. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 ft. (9.14m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve, see Figures 5 or 10.

No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 in. (152mm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circum- stances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

4.When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed, see Figure 7 for suggested piping arrangement.

The Discharge Pipe:

Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe.

Shall terminate at an adequate drain.

Shall not have any valve between the relief valve and tank.

The temperature-pressure relief valve must be manually oper- ated at least once a year. Caution should be taken to ensure that

(1)no one is in front of or around the outlet of the temperature- pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot.

If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and re- place the temperature-pressure relief valve with a new one.

WATER (POTABLE) HEATING AND SPACE HEATING

1.All piping components connected to this unit for space heating applications shall be suitable for use with potable water.

2.Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.

3.This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance.

FIGURE 7

CLOSED WATER SYSTEM

A closed system will exist if a back-flow preventer (check valve), pressure reducing valve, or other similar device is installed in the cold water line between the water heater and the street main (or well). Excessive pressure may develop due to the thermal expansion of heated water causing premature tank failure or intermittent relief valve operation. This type of failure is not covered by the limited warranty. An expansion tank may be necessary in the cold water supply to alleviate this situation, see Figure 1. Contact the local plumbing authority.

If the temperature and pressure relief valve on the appliance discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. DO NOT PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE.

GAS PIPING

Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed 14 inch water column (3.5 kPa) for natural and propane gas (L.P.). The

12

Image 12
Contents Residential GAS Water Heaters Safe INSTALLATION, USE and Service Important DefinitionsGeneral Safety Table of Contents IntroductionKeep Clear of ALL Obstructions Typical Installation GET to Know Your Water Heater Replacement PartsMixing Valve Usage Hotter Water can ScaldLocating the NEW Water Heater Facts to Consider about the LocationInsulation Blankets Ventilation for Appliances Located in Confined SpacesVent Termination Installing the NEW Water Heater Required AbilityInspect Shipment GeneralTEMPERATURE-PRESSURE Relief Valve Valve and Pipe Insulation if SuppliedWater Potable Heating and Space Heating Closed Water SystemGAS Piping GAS Piping with Flexible Connector High Altitude Installations Sediment Traps Filling the Water HeaterVenting Combustion AIR and Ventilation Vent Terminal ClearancesDV Termination Safety Cover Vent ConnectionsLocating Clearance Hole for Vent High Rise Vent ArrangementVent Assembly Securing Vent Termination Assembly to the Exterior WallStandard Vent Arrangement Uncompressing the Corrugated TubingOffset Vent Arrangement TOP Knob Figure DTemperature Regulation Temperature RegulationFor Your Information External DamageStart UP Conditions Operational ConditionsAIR in HOT Water Faucets Maintenance Venting System InspectionPilot and Main Burner Temperature & Pressure Relief Valve Anode ROD MaintenanceDraining Cathodic Protection AnodeDrain Valve Washer Replacement Service Leakage CheckpointsTroubleshooting Guidelines Problem Possible Causes CorrectionSlow HOT Water Recov ERYDrip from Relief Valve Thermostat Fails toPage Series Tank Parts Conditions and ExceptionsService and Labor Responsibility Claim ProcedureInstallation Information Limitation on Implied WarrantiesTennessee Waltz Parkway Ashland CITY, TN

186589-001 specifications

State Industries 186589-001 is a highly efficient water heater designed to meet both residential and commercial hot water demands. Known for its durability and exceptional performance, this unit is a popular choice among homeowners and business owners alike.

One of the standout features of the State Industries 186589-001 is its robust construction. The tank is made from high-quality materials that offer superior insulation, reducing heat loss and improving overall energy efficiency. This ensures a longer lifespan for the unit while minimizing operating costs. The model also features a glass-lined tank, which prevents corrosion and extends the longevity of the water heater.

The 186589-001 employs innovative heating technologies, including an advanced control system that provides precise temperature regulation. This allows users to set their desired water temperature easily, ensuring optimal comfort and safety. With a powerful heating element, the water heater can quickly heat water to desired levels, providing a reliable supply for various applications, from daily bathing to commercial needs.

Furthermore, the State Industries water heater is equipped with multiple safety features. An automatic shut-off function is integrated to protect against overheating, ensuring user safety during operation. Additionally, the model comes with a pressure relief valve, preventing potential hazards from excessive pressure build-up.

In terms of energy efficiency, the 186589-001 meets and often exceeds current industry standards. Its design minimizes energy consumption, which not only lowers utility bills for users but also aligns with environmentally sustainable practices.

The unit is designed for easy installation, making it convenient for both professionals and DIY enthusiasts. Clear instructions are provided, and the compact size allows it to fit in tight spaces, an advantage for those with limited installation options.

Overall, the State Industries 186589-001 stands as a reliable choice for those seeking a quality water heater with excellent features, advanced technology, and safety characteristics. Its commitment to durability and efficiency makes it a valuable investment for anyone in need of consistent hot water supply.