State Industries 186589-001 instruction manual GAS Piping with Flexible Connector

Page 13

minimum inlet gas pressure shown on the rating plate is that which will permit firing at rated input.

All gas piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223.1/NFPA 54 which- ever applies. Copper and brass tubing and fittings (except tin lined copper tubing) shall not be used.

If the gas control valve is subjected to pressures exceeding 1/2 psi (3.5 kPa), the damage to the gas control valve could result in a fire or explosion from leaking gas.

If the main gas line Shut-off serving all gas appliances is used, also turn “off” the gas at each appliance. Leave all gas appli- ances shut “off” until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater. Consult the current edition of National Fuel Gas Code ANSI Z223.1/NFPA 54 and your gas supplier concerning pipe size.

There must be:

A readily accessible manual shut off valve in the gas supply line serving the water heater, and

A drip leg (sediment trap) ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve.

A flexible gas connector or a ground joint union between the shut off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a match or open flame. Rinse off soapy solution and wipe dry.

Use pipe joint compound or teflon tape marked as being resis- tant to the action of petroleum [Propane (L.P.)] gases.

The appliance and its gas connection must be leak tested before placing the appliance in operation.

TheapplianceanditsindividualShut-offvalveshallbedisconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 pound per square inch (3.5 kPa). It shall be isolated from the gas supply piping system by closing its individual manual Shut-off valve during any pres- sure testing of the gas supply piping system at test pressures equal to or less than 1/2 pound per square inch (3.5 kPa).

Connecting the gas piping to the gas control valve of the water heater can be accomplished by either of the two methods shown in Figures 8 and 9.

When installed at elevations above 7,700 feet (2,347 meters), input rating should be reduced at the rate of 4 percent for each 1,000 feet (305 meters) above sea level which requires replacement of the burner orifice in accordance with National Fuel Gas Code ANSI Z223.1/NFPA 54. Contact your local gas supplier for further information.

Failure to replace the standard orifice with a high altitude orifice when installed could result in improper and inefficient operation of the appliance, producing carbon monoxide gas in excess of safe limits, which could result in serious injury or death. Contact your gas supplier for any specific changes which may be re- quired in your area.

FIGURE 8 GAS PIPING WITH

FLEXIBLE CONNECTOR.

FIGURE 9 GAS PIPING WITH ALL

BLACK IRON PIPE TO GAS CONTROL.

13

Image 13
Contents Residential GAS Water Heaters Important Definitions Safe INSTALLATION, USE and ServiceGeneral Safety Introduction Table of ContentsKeep Clear of ALL Obstructions GET to Know Your Water Heater Replacement Parts Typical InstallationHotter Water can Scald Mixing Valve UsageFacts to Consider about the Location Locating the NEW Water HeaterVentilation for Appliances Located in Confined Spaces Insulation BlanketsVent Termination Required Ability Installing the NEW Water HeaterInspect Shipment GeneralValve and Pipe Insulation if Supplied TEMPERATURE-PRESSURE Relief ValveClosed Water System Water Potable Heating and Space HeatingGAS Piping GAS Piping with Flexible Connector Sediment Traps Filling the Water Heater High Altitude InstallationsVenting Vent Terminal Clearances Combustion AIR and VentilationVent Connections DV Termination Safety CoverLocating Clearance Hole for Vent High Rise Vent ArrangementSecuring Vent Termination Assembly to the Exterior Wall Vent AssemblyStandard Vent Arrangement Uncompressing the Corrugated TubingOffset Vent Arrangement Figure D TOP KnobTemperature Regulation Temperature RegulationExternal Damage For Your InformationStart UP Conditions Operational ConditionsAIR in HOT Water Faucets Venting System Inspection MaintenancePilot and Main Burner Anode ROD Maintenance Temperature & Pressure Relief ValveDraining Cathodic Protection AnodeDrain Valve Washer Replacement Leakage Checkpoints ServiceProblem Possible Causes Correction Troubleshooting GuidelinesERY Slow HOT Water RecovDrip from Relief Valve Thermostat Fails toPage Conditions and Exceptions Series Tank PartsClaim Procedure Service and Labor ResponsibilityInstallation Information Limitation on Implied WarrantiesTennessee Waltz Parkway Ashland CITY, TN

186589-001 specifications

State Industries 186589-001 is a highly efficient water heater designed to meet both residential and commercial hot water demands. Known for its durability and exceptional performance, this unit is a popular choice among homeowners and business owners alike.

One of the standout features of the State Industries 186589-001 is its robust construction. The tank is made from high-quality materials that offer superior insulation, reducing heat loss and improving overall energy efficiency. This ensures a longer lifespan for the unit while minimizing operating costs. The model also features a glass-lined tank, which prevents corrosion and extends the longevity of the water heater.

The 186589-001 employs innovative heating technologies, including an advanced control system that provides precise temperature regulation. This allows users to set their desired water temperature easily, ensuring optimal comfort and safety. With a powerful heating element, the water heater can quickly heat water to desired levels, providing a reliable supply for various applications, from daily bathing to commercial needs.

Furthermore, the State Industries water heater is equipped with multiple safety features. An automatic shut-off function is integrated to protect against overheating, ensuring user safety during operation. Additionally, the model comes with a pressure relief valve, preventing potential hazards from excessive pressure build-up.

In terms of energy efficiency, the 186589-001 meets and often exceeds current industry standards. Its design minimizes energy consumption, which not only lowers utility bills for users but also aligns with environmentally sustainable practices.

The unit is designed for easy installation, making it convenient for both professionals and DIY enthusiasts. Clear instructions are provided, and the compact size allows it to fit in tight spaces, an advantage for those with limited installation options.

Overall, the State Industries 186589-001 stands as a reliable choice for those seeking a quality water heater with excellent features, advanced technology, and safety characteristics. Its commitment to durability and efficiency makes it a valuable investment for anyone in need of consistent hot water supply.