RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER
SERVICE HANDBOOK
To replace a pilot assembly:
1.Turn off the gas supply
2.Disconnect the piezo cable from the piezo button (connection near gas control valve).
3.Disconnect the pilot tubing, thermocouple and main burner tube from the bottom of the gas control valve.
4.Remove (2) 3/8 inch nuts securing the inner door.
5.Remove the entire burner assembly.
6.Remove screw securing pilot burner assembly to pilot mounting bracket.
7.Remove pilot assembly - with orange gasket – from the back side of the inner door.
8.Reinsert new pilot assembly into back side of inner door. Wetting the orange gasket may help in securing the gasket into place.
9.Reattach the new pilot assembly to the pilot mounting bracket.
10.Inspect/replace the white, inner door gasket before making the connections to the bottom of the gas control valve.
11.Reattach the piezo cable to the piezo button.
12.Remount the inner door.
13.Follow the pilot lighting instructions including gas and gasket leak checks.
14.Install the outer door.
SEALED COMBUSTION CHAMBER
The combustion chamber is factory sealed around the flame arrestor and the upper and lower perimeter of the chamber. Access for service is provided through an inner door as with current product. However, this inner door is now sealed with; a door gasket, a pilot assembly grommet type seal, and a main burner tube boot/sleeve type seal.