ITT IM213 manual Input Power Connections

Page 15
Hazardous voltage

Starting the System

Section 7 (continued)

Consult motor manual to determine the wire size for the application. Ensure the ground connection to the motor is continuous. Connect wires to the output terminal block labeled T1/U, T2/V, T3/W, and GND/ . Connect the ground wire to the terminal labeled GND/. Connect the other phase leads to T1/U, T2/V and T3/W.

For CentriPro Motors, connecting T1/U to Red, T2/V to Black and T3/W to Yellow will give the correct rotation.

Danger

DANGER

Hazardous voltage

The controller has high leakage current to ground. The output terminals marked “GND” or “ ” must be directly connected to the motor ground. Failure to properly ground the controller or motor will create an electrical shock hazard.

Input Power Connections

DANGER Make sure disconnect switches or circuit breakers are securely in the OFF position before making this connection. Run the input power wires from the fused disconnect through metal conduit to the bottom of the controller. Use metal conduit and metal conduit connectors. Size the conduits according to the

NEC, CEC or local codes. Use the wire sizing chart in the appendix to determine the size of the input power wires. Connect the conduit and insert the wires into the far left opening on the controller. Connect wires to the “INPUT” terminal block. Connect the ground wire to the terminal labeled GND. For three phase input, connect the input phase wires to L1, L2 and L3. For single phase input, connect the input wires to L1 and L3. If single phase input is used the motor overload switches must be set to 50% or lower.

Caution

The wire used for input power connections on models SPD20300 and SPD20300F must have a temperature rating of 90ºC minimum.

Danger

DANGER

Hazardous voltage

The controller has a high leakage current to ground. The input terminals marked “GND” must be directly connected to the service entrance ground. Failure to properly ground the controller or motor will create an electrical shock hazard.

Note

If single phase input power is used the Motor Overload switches must be set to 50% or lower or nuisance input phase loss errors can result.

Note

Do not use GFCI protection with this controller. Nuisance tripping will result.

Danger

DANGER

Hazardous voltage

Status Code Indicator Light is not a voltage indicator! Always turn off disconnect switch and circuit breaker and wait 5 minutes before servicing.

Danger

DANGER

Hazardous voltage

The controller will remain electrically charged for 5 minutes after power is turned off. Wait 5 minutes after disconnecting power before opening controller access cover as there is a severe shock hazard.

15

Image 15
Contents IM213 Commercial Water ITTIndex Death Safety InstructionsVolt = System ComponentsController Product Code Information HP =Fusible Disconnect System DesignSection Diagram #2 shows a set-up for municipal water connectionPressure Tank, Pressure Relief Valve and Discharge Piping Installing the Pressure SensorPiping GeneralMounting the Controller Power Supply and Wiring Power SupplyDelta/Wye with grounded Wye neutral Ungrounded secondary Delta/Delta with grounded legResistance grounding and ground fault protection Open Delta consult factoryFor Frame Size 1 Controllers Single Phase Connection 208/230460 20ºC 30ºC 40ºC 50ºC Conduit, Wire and Fuse SizingInput Power and Line Transformer Requirements Output Power ConnectionsStarting the System Input Power Connections Chart below shows the motor overload setting for each model Setting the Motor Overload SwitchesSetting the Carrier Frequency Switch Setting the Acceleration/Deceleration SwitchesSetting the No Water Restart Time Switches Setting the Minimum Frequency SwitchSetting the Pressure Motor Rotation DirectionSystem Status Input and Output Functions Standby TroubleshootingUse the following table to help troubleshoot problems SwitchIncorrect setting of Motor Overload Setting switches Constant Controller ErrorPower. If the error persists, replace controller This fault can be caused bySet the meter to read DC current mA Connect the black lead from the meter to terminalSensor cable To 50% or lower Blinks Temperature This fault can be caused byTemperature reaches 104 ºF 40ºC Megger readings10Hz for 5 minutes Greater than 275V for 230V units and 560V for 460V unitsController Dimensions Input Appendix Input Wire Sizing ChartsPage IM213 Revision Number November

IM213 specifications

ITT IM213 is a prominent electronic device designed for data acquisition and monitoring in various industrial applications. Known for its robust construction and versatile functionality, the IM213 series has gained significant traction in sectors such as manufacturing, environmental monitoring, and energy management.

One of the key features of the ITT IM213 is its advanced data logging capability. The device can record a wide range of signals, including temperature, pressure, and humidity, making it an essential tool for real-time monitoring. The intuitive user interface allows users to configure the device easily, adjusting parameters to suit specific monitoring needs.

The IM213 utilizes cutting-edge technologies to ensure accuracy and reliability. Its high-resolution analog-to-digital converters (ADCs) offer precise measurements with minimal noise interference, enhancing the overall performance of the device. Additionally, the device supports multiple communication protocols, including Modbus, RS-232, and RS-485, enabling seamless integration into existing systems.

Another noteworthy characteristic of the ITT IM213 is its robust build quality. Designed for use in harsh environments, it features an IP67-rated enclosure that protects it from dust, moisture, and other potential contaminants. This makes it particularly suitable for outdoor applications or locations with challenging conditions.

Furthermore, the IM213 is equipped with a range of connectivity options. Users can connect the device to cloud platforms for remote monitoring and data analytics, leveraging IoT technologies to enhance operational efficiency. This capability allows organizations to make data-driven decisions, improving their overall productivity.

The device also supports customizable alert systems, notifying users of any deviations from preset thresholds in real-time. This feature is crucial for preventing costly downtime and ensuring that processes remain within optimal operational parameters.

In terms of power consumption, the ITT IM213 is designed to be energy-efficient, ensuring long operational life and reduced running costs. Its low-power modes further contribute to sustainability, making it a responsible choice for environmentally conscious organizations.

In summary, the ITT IM213 is a versatile and durable data acquisition device that serves a wide range of industrial applications. Its advanced logging capabilities, high accuracy, robust construction, and connectivity options position it as a leading choice for professionals looking to improve their monitoring and data collection efforts. With these features, the IM213 is poised to play a vital role in enhancing productivity and operational efficiency in various sectors.