ITT IM213 manual Megger readings, To 50% or lower, Blinks Temperature This fault can be caused by

Page 23

Troubleshooting

Red Light Codes (continued)

Flashes

Controller Status

Description

4 Blinks

Pump or Motor Bound

This fault can be caused by:

 

 

• Mechanical binding from debris in pump.

 

 

• Electrical failure of the motor.

 

 

• Incorrect setting of Motor Overload Setting switches.

 

 

• Incorrect rotation.

 

 

• Motor phase loss.

 

 

This fault will be displayed if the output current exceeds 125% of the

 

 

controller rating. The controller will attempt to restart 5 times. If the

 

 

condition persists the controller will lock out and will need to be reset.

 

 

Verify the error by turning power to controller off for 5 minutes and

 

 

then on. Pump/Motor/Wiring must be checked if fault persists.

5 Blinks

Short Circuit

This fault can be caused by:

 

 

• Electrical failure of the motor

 

 

• Electrical failure of wiring between controller and motor.

 

 

This fault will be displayed if the output current exceeds 150% of the

 

 

controller rating. Verify the error by turning power to controller off for

 

 

1 minute and then on. If error persists, motor and wiring between

 

 

controller and motor must be checked. Turn power off for 5 minutes.

 

 

Remove the three motor wires from the terminal block. Check output

 

 

wiring and motor for shorting phase to phase and phase to ground.

 

 

Refer to motor's manual for information on resistance readings and

 

 

megger readings.

6 Blinks

Input Phase Loss

This fault can be caused by:

 

 

• Disconnected input power phase.

 

 

• Incorrect Motor Overload Setting switches. When using single

 

 

phase input power the Motor Overload Setting switches must be set

 

 

to 50% or lower.

 

 

For three phase input operation; this fault will be displayed if the

 

 

phase to phase input voltage is more than 25% lower than the

 

 

nominal. The controller will attempt to restart 5 times. If the

 

 

condition persists the controller will lock out and will need to be reset.

7 Blinks

Temperature

This fault can be caused by:

 

 

• High ambient temperature. The maximum ambient temperature

 

 

rating is 122 ºF (50ºC).

 

 

• Low ambient temperature. The minimum ambient temperature

 

 

rating is -22ºF (-30ºC).

 

 

This fault will be displayed if the ambient temperature is greater than

 

 

122ºF (50ºC) or less than -22ºF (-30ºC). Do not install the controller

 

 

where it will be exposed to direct sunlight. Check for a fan failure. The

 

 

fans on the back of the controller will turn on only when needed. The

 

 

fans will turn on when the motor is running and the heatsink

 

 

temperature reaches 104 ºF (40ºC).

 

 

 

23

Image 23
Contents IM213 Commercial Water ITTIndex Death Safety InstructionsVolt = System ComponentsController Product Code Information HP =Fusible Disconnect System DesignSection Diagram #2 shows a set-up for municipal water connectionPressure Tank, Pressure Relief Valve and Discharge Piping Installing the Pressure SensorPiping GeneralMounting the Controller Delta/Wye with grounded Wye neutral Power Supply and WiringPower Supply Ungrounded secondary Delta/Delta with grounded legFor Frame Size 1 Controllers Resistance grounding and ground fault protectionOpen Delta consult factory 460 Single Phase Connection208/230 20ºC 30ºC 40ºC 50ºC Conduit, Wire and Fuse SizingStarting the System Input Power and Line Transformer RequirementsOutput Power Connections Input Power Connections Chart below shows the motor overload setting for each model Setting the Motor Overload SwitchesSetting the Carrier Frequency Switch Setting the Acceleration/Deceleration SwitchesSetting the No Water Restart Time Switches Setting the Minimum Frequency SwitchSystem Status Setting the PressureMotor Rotation Direction Input and Output Functions Standby TroubleshootingUse the following table to help troubleshoot problems SwitchIncorrect setting of Motor Overload Setting switches Constant Controller ErrorPower. If the error persists, replace controller This fault can be caused bySensor cable Set the meter to read DC current mAConnect the black lead from the meter to terminal To 50% or lower Blinks Temperature This fault can be caused byTemperature reaches 104 ºF 40ºC Megger readings10Hz for 5 minutes Greater than 275V for 230V units and 560V for 460V unitsController Dimensions Input Appendix Input Wire Sizing ChartsPage IM213 Revision Number November

IM213 specifications

ITT IM213 is a prominent electronic device designed for data acquisition and monitoring in various industrial applications. Known for its robust construction and versatile functionality, the IM213 series has gained significant traction in sectors such as manufacturing, environmental monitoring, and energy management.

One of the key features of the ITT IM213 is its advanced data logging capability. The device can record a wide range of signals, including temperature, pressure, and humidity, making it an essential tool for real-time monitoring. The intuitive user interface allows users to configure the device easily, adjusting parameters to suit specific monitoring needs.

The IM213 utilizes cutting-edge technologies to ensure accuracy and reliability. Its high-resolution analog-to-digital converters (ADCs) offer precise measurements with minimal noise interference, enhancing the overall performance of the device. Additionally, the device supports multiple communication protocols, including Modbus, RS-232, and RS-485, enabling seamless integration into existing systems.

Another noteworthy characteristic of the ITT IM213 is its robust build quality. Designed for use in harsh environments, it features an IP67-rated enclosure that protects it from dust, moisture, and other potential contaminants. This makes it particularly suitable for outdoor applications or locations with challenging conditions.

Furthermore, the IM213 is equipped with a range of connectivity options. Users can connect the device to cloud platforms for remote monitoring and data analytics, leveraging IoT technologies to enhance operational efficiency. This capability allows organizations to make data-driven decisions, improving their overall productivity.

The device also supports customizable alert systems, notifying users of any deviations from preset thresholds in real-time. This feature is crucial for preventing costly downtime and ensuring that processes remain within optimal operational parameters.

In terms of power consumption, the ITT IM213 is designed to be energy-efficient, ensuring long operational life and reduced running costs. Its low-power modes further contribute to sustainability, making it a responsible choice for environmentally conscious organizations.

In summary, the ITT IM213 is a versatile and durable data acquisition device that serves a wide range of industrial applications. Its advanced logging capabilities, high accuracy, robust construction, and connectivity options position it as a leading choice for professionals looking to improve their monitoring and data collection efforts. With these features, the IM213 is poised to play a vital role in enhancing productivity and operational efficiency in various sectors.