Troubleshooting

Section 9

General

The S-Drive and Aquavar SPD drive are self-diagnosing controllers. If a problem occurs, observe the Status Code Indicator Light on the front of the unit. No Status Code Indicator Light means either no or low input voltage (less than 140Vac).

Danger

DANGER

Hazardous voltage

Status Code Indicator Light is not a voltage indicator! Always turn off disconnect switch and circuit breaker and wait 5 minutes before servicing. High voltage may still remain on controller.

Refer to the status code label on the side of the controller access cover to diagnose system errors. See the following diagram.

Red Flashes

Fault Code

Restart Action

 

 

 

Constant

Replace Controller

Controller will not restart. Power must

 

 

be reset to clear the fault.

2 Blinks

No Water/Loss of Prime

Controller will restart automatically

 

 

according to the No Water Restart Time

 

 

switches (switches 3&4 of bank 2).

3 Blinks

Sensor Fault

Controller will restart automatically when

 

 

the sensor signal is within the valid

 

 

operating range.

4 Blinks

Pump or Motor Bound

Controller will restart automatically 5

 

 

times. After 5 faults the power must be

 

 

reset to clear the fault.

5 Blinks

Short Circuit/Ground Fault

Controller will not restart. Power must be

 

 

reset to clear the fault.

6 Blinks

Input Phase Loss

Controller will restart automatically 5 times.

 

 

After 5 faults the power must be reset to

 

 

clear the fault.

7 Blinks

Temperature

Controller will restart automatically when

 

 

temperature is within the operating range

 

 

of the controller.

8 BLINKS

Over Voltage

Controller will restart automatically when

 

 

the input voltage is within the operating

 

 

range of the controller.

9 Blinks

Motor Overload

Controller will restart automatically.

 

 

 

Use the following table to help troubleshoot problems.

 

 

 

No Light

 

Controller Status

Description

 

Low/No Input Voltage

Check the input voltage to the controller. Measure the input voltage

 

 

 

between phases using an AC Voltmeter. This voltage should be

 

 

 

greater than 140Vac for the status indicator light to turn on.

 

 

 

 

 

 

 

Green Light Codes

Flashes

 

Controller Status

Description

Constant

 

Standby

Constant Green Light indicates the pump is off. The system is in

 

 

 

Standby mode when there is no flow in the system and the pressure

 

 

 

setting has been reached or the RUN/STOP input is set to STOP (open

 

 

 

switch).

Blinking

 

Pump Running

Flashing Green Light indicates the pump is running.

 

 

 

 

20

Image 20
Contents ITT IM213 Commercial WaterIndex Safety Instructions DeathSystem Components Controller Product Code InformationHP = Volt =System Design Fusible DisconnectDiagram #2 shows a set-up for municipal water connection SectionInstalling the Pressure Sensor PipingGeneral Pressure Tank, Pressure Relief Valve and Discharge PipingMounting the Controller Delta/Wye with grounded Wye neutral Power Supply and WiringPower Supply Delta/Delta with grounded leg Ungrounded secondaryFor Frame Size 1 Controllers Resistance grounding and ground fault protectionOpen Delta consult factory 460 Single Phase Connection208/230 Conduit, Wire and Fuse Sizing 20ºC 30ºC 40ºC 50ºCStarting the System Input Power and Line Transformer RequirementsOutput Power Connections Input Power Connections Setting the Motor Overload Switches Chart below shows the motor overload setting for each modelSetting the Acceleration/Deceleration Switches Setting the No Water Restart Time SwitchesSetting the Minimum Frequency Switch Setting the Carrier Frequency SwitchSystem Status Setting the PressureMotor Rotation Direction Input and Output Functions Troubleshooting Use the following table to help troubleshoot problemsSwitch StandbyConstant Controller Error Power. If the error persists, replace controllerThis fault can be caused by Incorrect setting of Motor Overload Setting switchesSensor cable Set the meter to read DC current mAConnect the black lead from the meter to terminal Blinks Temperature This fault can be caused by Temperature reaches 104 ºF 40ºCMegger readings To 50% or lowerGreater than 275V for 230V units and 560V for 460V units 10Hz for 5 minutesController Dimensions Appendix Input Wire Sizing Charts InputPage IM213 Revision Number November

IM213 specifications

ITT IM213 is a prominent electronic device designed for data acquisition and monitoring in various industrial applications. Known for its robust construction and versatile functionality, the IM213 series has gained significant traction in sectors such as manufacturing, environmental monitoring, and energy management.

One of the key features of the ITT IM213 is its advanced data logging capability. The device can record a wide range of signals, including temperature, pressure, and humidity, making it an essential tool for real-time monitoring. The intuitive user interface allows users to configure the device easily, adjusting parameters to suit specific monitoring needs.

The IM213 utilizes cutting-edge technologies to ensure accuracy and reliability. Its high-resolution analog-to-digital converters (ADCs) offer precise measurements with minimal noise interference, enhancing the overall performance of the device. Additionally, the device supports multiple communication protocols, including Modbus, RS-232, and RS-485, enabling seamless integration into existing systems.

Another noteworthy characteristic of the ITT IM213 is its robust build quality. Designed for use in harsh environments, it features an IP67-rated enclosure that protects it from dust, moisture, and other potential contaminants. This makes it particularly suitable for outdoor applications or locations with challenging conditions.

Furthermore, the IM213 is equipped with a range of connectivity options. Users can connect the device to cloud platforms for remote monitoring and data analytics, leveraging IoT technologies to enhance operational efficiency. This capability allows organizations to make data-driven decisions, improving their overall productivity.

The device also supports customizable alert systems, notifying users of any deviations from preset thresholds in real-time. This feature is crucial for preventing costly downtime and ensuring that processes remain within optimal operational parameters.

In terms of power consumption, the ITT IM213 is designed to be energy-efficient, ensuring long operational life and reduced running costs. Its low-power modes further contribute to sustainability, making it a responsible choice for environmentally conscious organizations.

In summary, the ITT IM213 is a versatile and durable data acquisition device that serves a wide range of industrial applications. Its advanced logging capabilities, high accuracy, robust construction, and connectivity options position it as a leading choice for professionals looking to improve their monitoring and data collection efforts. With these features, the IM213 is poised to play a vital role in enhancing productivity and operational efficiency in various sectors.