Enviro C-10450 owner manual GAS Line Connection, To Test Valve Pressures

Page 22
Figure 30: Fully Labeled Gas Valve.

Initial Installation

GAS LINE CONNECTION AND TESTING:

WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.

GAS LINE CONNECTION

This stove is equipped with a certified flexible pipe located on the right side of the unit terminating in a 3⁄8” male NPT fitting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in Canada, or in the USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI Z223.1.

The efficiency rating of this appliance is a product thermal efficiency rating determined under continuous operating conditions and was determined independently of any installed system.

The appliance and its shutoff valves must be disconnected from the gas supply piping system during any pressure testing where the pressure exceeds 1⁄2 PSIG (3.45 KPa) or damage will occur to the valve.

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1⁄2 psig (3.45 KPa).

Always check for gas leaks with a soap and water solution after completing the required pressure test.

TO TEST VALVE PRESSURES

 

 

��������

 

�����

 

 

 

�������� ���

 

 

�������� ���

 

 

 

 

 

TP TH

 

OUT

IN

 

 

 

 

 

TP

H

O

 

 

I

L

OF

 

 

 

 

 

 

 

F

 

 

 

 

P

TH

 

 

I

 

 

L

 

 

T

O

 

 

 

 

 

 

NO

 

T

P

 

 

 

I

 

 

 

OL

 

 

 

 

����� ����������

������

 

��� �������

�����

����

 

����

The pressure taps are located on the left side of the valve

Turn set screw 1 turn counter clockwise to loosen,

Place 5/16” (8 mm) I.D. hose over pressure tap system.

Check pressures using a manometer.

When finished, release pressure, remove hose & tighten set screw.

Table 6: Pressure and BTU Information.

 

Natural Gas

Propane

 

 

 

Main Orifice

#43 DMS

#53 DMS

Manifold Pressure

3.8” W.C. (0.95 KPa)

11.0” W.C. (2.74 KPa)

Min. Manifold Pressure

1.1” W.C. (0.27 KPa)

2.7” W.C. (0.67 KPa)

 

 

 

Max Supply Pressure

7.0” W.C. (1.74 KPa)

12.0” W.C. (2.98 KPa)

 

 

 

Min. Supply Pressure

5.0” W.C. (1.25 KPa)

11.5” W.C. (2.86 KPa)

 

 

 

Max BTU/hr Input

26,500 BTU/hr (7.87 KW)

26,500 BTU/hr (7.87 KW)

 

 

 

Min. BTU/hr Input

13,500 BTU/hr (3.9 KW)

13,500 BTU/hr (3.9 KW)

 

 

 

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

22

Image 22
Contents EG28 DV S H E R W O O D I N D U S T R I E S L T DFor Your Safety Safety PrecautionsGeneral Table of Contents Vented GAS Fireplace Heater EG28 DV NG/LPG Codes And ApprovalsThis Enviro EG28 DV Fireplace Specifications EG28 Exterior DimensionsInitial Installation Qualified Installers onlyVent restrictor ring Venting Terminals Cannot be Recessed Into a Wall or Siding Vent Pipe Types with Part NumbersCommon Vertical Installation High temperature Silicone Male Edge Outer pipe. Push Installing Horizontal Vent Termination Do not interfere with the structural integrity of the walls Roof Pitch Minimum Height Feet MetersMulti-Story Vent Pipe Installation KIT Components Installation Instructions Wall thimble Assembly of Venting into a Class ‘A’ Chimney EG28 DV Wiring Diagram Then examine the flames, compare the flames to Figure 50% turn down HI-LOW Regulator GAS Line Connection To Test Valve PressuresSecondary Installation Log PlacementLog Placement with Embers Operating Instructions Water Never USE AN Open Flame for Leak TESTING. IfWhat to do if YOU Smell GAS Cleaning Plated Surfaces Routine Maintenance and ServiceCleaning the Inside of the Firebox Opening the DoorTrouble Shooting Problem Possible Cause SolutionParts List Reference Number Part Description Part NumberParts List Parts Diagram Chassis EG 28 Gas Tray and Door Assemblies Warranty To the DistributorInstallation Data Sheet