Enviro C-10608 owner manual Slider Damper Located Behind Left Side panel. To open, Special Notes

Page 26

Installation

SLIDER/DAMPER SET-UP:

This is used to regulate the airflow through the pellet stove. The slider Damper has been factory set for German test pellet fuel.

 

The

slider

damper

is

 

located

behind

the

left

 

side panel. To open the

Air Intake Box

left side panel, undo the

one screw located in the

Exhaust Channel

upper front corner of the

Slider Damper

cabinet

side

between

Exhaust Blower

the louvers. Also loosen

three screws down the

 

back of the side panel.

Figure 29: Slider/Damper Plate in Unit.

The combustion exhaust blower is a variable speed blower controlled by the heat output button. This blower will decrease the vacuum pressure inside the stove and as the heat output button is turned down. The vacuum pressure inside the firebox will increase as the combustion exhaust blower increases in speed (higher heat output setting).

If the fire should happen to go out and the heat output indicator has been set on the lowest setting, the Slider Damper should be pushed in slightly, decreasing the air in the firebox.

If, after long periods of burning, the fire builds up and overflows the burn pot or there is a build up of clinkers, this would be a sign that the pellet quality is poor, this requires more primary air, the slider damper must be pulled out to compensate. Pulling the slider damper out gives the fire more air.

The easiest way to make sure that an efficient flame is achieved is to understand the characteristics of the fire.

A tall, lazy flame with dark orange tips requires more air – Open slider (pull out) slightly.

A short, brisk flame, like a blowtorch, has too much air – Close slider (push in) slightly.

If the flame is in the middle of these two characteristics with a bright yellow/orange, active flame with no black tips then the air is set for proper operation.

SPECIAL NOTES:

Pellet quality is a major factor in how the Pellet stove will operate. If the pellets have a high moisture content or ash content the fire will be less efficient and has a higher possibility of the fire building up and creating clinkers (hard ash build-up).

Taking a reading of vacuum pressure inside the firebox with a magnehelic gauge can be used to set the slider for best combustion. The best settings are a reading of approximately 0.10 inches of water column on the high fire setting. Some fuels may require higher or lower settings. The reading can be taken from the 1⁄8” (3 mm) hole located on the front of the unit below the door and behind the magnetic ash lip.

26

Image 26 Contents
Evolution Table of Contents Store pellets at least 36 1 m away from the pellet stove IntroductionI. Pellet Standards USE of Cordwood is Prohibited by LAW Keep ASH PAN Free of RAW Fuel Reasons WHY the Unit Overheated Operating InstructionsThermostat / Switch Mode Initial START-UP See aboveBurner POT and Liner 2-3 days Routine Cleaning and MaintenanceTools Required to Clean Unit Heat Exchanger Tubes 2-3 daysFresh AIR Intake biannually Door Glass Cleaning 2-3 daysASH PAN weekly Exhaust Passages biannuallyDoor Glass Replacement Post Season CLEAN-UPCleaning Plated Surfaces Brick PanelInstallation Screws to take out to remove stove from palletDimensions of EF5 Minimum Alcove depth Inches Installing Hearth Pad Pedestal onto EF5 Crawlspace, narrow Walkway Closely Exhaust Fresh Air Intake Page Venting horizontally with rise Inside Vertical Installation Outside Vertical Installation Through vent hole Exterior Blower KitThrough Wall Installation with Exterior Blower Kit EF5 If you wish to adjust the slider damper externally not REQUIRED, please follow the instructions belowSlider Damper Located Behind Left Side panel. To open Special NotesDo not TroubleshootingStove will not operate when hot What to do ifLight # 2 on Heat output bar flashing 200 F 93 C high limit temperature sensor has trippedExhaust motor will not function normally Ignitor- the pellets will not light Control settings Heat Level has no effect on the fireConvection blower will not function normally Stove keeps going outWiring Diagram 5V DCParts List Reference Number Description Part Number50-1085 Parts Diagram Components SteelDiagramParts To the Distributor WarrantyTo the Dealer Installation Data Sheet Name of Owner Address