EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
NV name
nvoFcuStatus
nvoFcuStatus
nvoFcuStatus
nvoFcuStatus
nvoFcuStatus
nvoFcuStatus (continued)
field name
sched_occ
eff_sen_occ
net_man_occ
hw_sen_occ
r_o_led
mode
Table C4. Output Variables for Excel 10 FCU Controllers.
engineering units: | digital |
|
| |
state | default | comments | ||
English (metric) or states plus | ||||
or | ||||
range |
|
| ||
value |
|
| ||
|
|
| ||
SNVT_occupancy |
|
| This output variable reports the current scheduled occupancy | |
OC_OCCUPIED | 0 |
| received via the network. | |
OC_UNOCCUPIED | 1 |
|
| |
OC_BYPASS | 2 |
|
| |
OC_STANDBY | 3 |
|
| |
OC_NUL (No Override) | 255 |
|
| |
SNVT_occupancy |
|
| This output variable reports the effective state of occupancy | |
OC_OCCUPIED | 0 |
| sensor(s) connected either to the input terminals or to other nodes | |
OC_UNOCCUPIED | 1 |
| on the network that are bound to this controller. | |
OC_NUL (No Override) | 255 |
|
| |
SNVT_occupancy |
|
| This output variable reports the manual occupancy from the | |
OC_OCCUPIED | 0 |
| network. | |
OC_UNOCCUPIED | 1 |
|
| |
OC_BYPASS | 2 |
|
| |
OC_STANDBY | 3 |
|
| |
OC_NUL | 255 |
|
| |
|
|
|
| |
SNVT_occupancy |
|
| This output variable reports the state of the occupancy sensor | |
OC_OCCUPIED | 0 |
| wired to the node. | |
OC_UNOCCUPIED | 1 |
|
| |
OC_NUL | 255 |
|
| |
SNVT_occupancy |
|
| This output variable reports the current state of the remote override | |
OC_OCCUPIED | 0 |
| LED which indicates the effective schedule override resulting from | |
OC_UNOCCIPIED | 1 |
| the bypass | |
OC_BYPASS | 2 |
| OC_OCCUPIED: 2 flashes per second | |
OC_STANDBY | 3 |
| OC_UNOCCUPIED: 1 flash per second | |
OC_NUL | 255 |
| OC_BYPASS: on | |
|
|
| OC_STANDBY: 2 flashes per second | |
|
|
| OC_NUL: off | |
|
|
|
| |
BYTE |
|
| This output variable is the current operating mode of the node | |
CTL_COOL | 0 |
| determined by many inputs and arbitrated by control logic. | |
CTL_HEAT | 1 |
| CTL_PRESSURIZE disables the heat/cool outputs, fan runs at | |
CTL_PRESSURIZE | 2 |
| highest speed. | |
CTL_DE_PRESSURIZE | 3 |
| CTL_DE_PRESSURIZE disables the heat/cool outputs, fan is | |
CTL_MODE_MANUAL | 4 |
| turned OFF. | |
CTL_MODE_FACTORY_TEST | 5 |
| CTL_MODE_MANUAL allows turning outputs ON/OFF manually | |
CTL_FLOATING_OUT_SYNCH | 6 |
| through nviTest. | |
CTL_FAN_SWITCH_OFF | 7 |
| CTL_MODE_FACTORY_TEST is intended only for the factory. | |
CTL_START_UP_WAIT | 8 |
| CTL_FLOATING_OUT_SYNCH allows enough time (150% valve | |
CTL_DISABLED | 255 |
| ||
|
|
| algorithms are active). The controller then goes into one of the | |
|
| 57 |