EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
NV name
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoTerminalLoad
nvoUnitStatus
field name
object_id
invalid_id
invalid_request
disabled
comm_failure
in_alarm
report_mask
mode
Table C4. Output Variables for Excel 10 FCU Controllers.
engineering units: | digital |
|
| |
state | default | comments | ||
English (metric) or states plus | ||||
or | ||||
range |
|
| ||
value |
|
| ||
|
|
| ||
|
|
| nviSpaceTemp is bound to another node, nvoSpaceTemp is not | |
|
|
| reported on the network. | |
UWORD |
|
| This output variable belongs to the Node Object and reports the | |
NODE_OBJECT | 0 |
| status for any object on a node. This is the answer to the | |
FCU_OBJECT | 1 |
| nviRequest. | |
|
|
|
| |
Bit |
|
| This output variable indicates whether nviRequest uses a fault | |
VALID_ID | 0 |
| object ID. | |
INVALID_ID | 1 |
|
| |
|
|
|
| |
Bit |
|
| This output variable indicates whether nviRequest uses a fault | |
VALID_REQUEST | 0 |
| request. | |
INVALID_REQUEST | 1 |
|
| |
|
|
|
| |
Bit |
|
| This output variable indicates whether the device is enabled or | |
ENABLED | 0 |
| disabled (nviManualMode = DISABLE). | |
DISABLED | 1 |
|
| |
|
|
|
| |
Bit |
|
| This output variable indicates whether an update nviRcvHrtBt is | |
COMMUNICATION_OK | 0 |
| missing. | |
COMMUNICATION_FAILURE | 1 |
|
| |
|
|
|
| |
Bit |
|
| This output variable indicates whether an alarm occured. See | |
NO_ALARM | 0 |
| nvoAlarm. | |
IN_ALARM | 1 |
|
| |
Bit |
|
| This output variable shows the answer to nviRequest > | |
NO_REPORT_MASK | 0 |
| REPORT_MASK | |
REPORT_MASK | 1 |
|
| |
|
|
|
| |
SNVT_lev_percent |
|
| This output variable shows the terminal load, which is a percentage | |
|
| between | ||
163.835% = INVALID |
|
| Negative values indicate heating load and positive values indicate | |
|
|
| cooling load. 100% is the full terminal capacity. An absolute | |
|
|
| terminal load value of more than 100% indicate that the terminal is | |
|
|
| not able to supply the required heating or cooling energy which at | |
|
|
| the zone controller should cause a demand for more supply | |
|
|
| energy. nvoHeatOutput will be transmitted immediately when its | |
|
|
| value has changed significantly (>= 1%). | |
SNVT_hvac_mode |
|
| This output variable reports the last operating mode of the control | |
HVAC_HEAT | 1 |
| algorithm. It is not set to HVAC_OFF if the Heating and Cooling | |
HVAC_COOL | 3 |
| Output shows 0%. HVAC_OFF is set when the Device is disabled | |
HVAC_OFF | 6 |
| from nviRequest, nviManualMode or nviApplicMode. |
62 |