![](/images/new-backgrounds/1104415/10441535x1.webp)
Table
Parameter |
|
| Agilent Model Number |
| ||
| 6641A |
| 6642A | 6643A | 6644A | 6645A |
Maximum AC Line Current Ratings |
|
|
|
|
|
|
100 Vac nominal: |
|
|
| 4.4 A rms |
|
|
120 Vac nominal: |
|
|
| 3.8 A rms |
|
|
220 Vac nominal: |
|
|
| 2.2 A rms |
|
|
230 Vac nominal: |
|
|
| 2.1 A rms |
|
|
240 Vac nominal: |
|
|
| 2.0 A rms |
|
|
Maximum Reverse Bias Current: | With AC input power applied and the dc output reverse | |||||
| biased by an external dc source, the supply will continuously | |||||
| withstand without damage a current equal to its output | |||||
| current rating (see Table 1- 1a). |
|
| |||
Remote Sensing Capability |
|
|
|
|
|
|
Voltage Drop Per Lead: | Up to 1/2 of rated output voltage. |
|
| |||
Load Regulation: | Add 3 mV to spec (see Table | |||||
| the + output lead due to load current changes. |
| ||||
Load Voltage: | Subtract voltage drop in load leads from specified output | |||||
| voltage rating. |
|
|
|
|
Command Processing Time (Average time for output voltage to change after receipt of digital data when the supply is connected directly to the GPIB Bus):
|
|
|
|
|
| 20 ms |
|
|
| |
Downprogrammer Current Capability (± 15%): |
| 5.8 A |
| 2.5 A |
| 1.5 A |
| 0.9 A |
| 0.75 A |
|
|
|
|
|
| |||||
Output Voltage Programming Response Time |
|
|
|
|
|
|
|
|
|
|
Rise/Fall Time (time for output to change from 90 % to 10% or from 10% to 90% of its total excursion): |
|
| ||||||||
Settling Time (time for output change to settle within |
| <15 ms |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 1 LSB (0.025% x rated voltage) of its final value): |
|
| |||||||
|
| <60 ms |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Monotonicity: |
| Output is monotonic over entire rated voltage, current, and | ||||||||
|
| temperature range. |
|
|
|
|
|
| ||
|
|
|
| Up to 3 identical models |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
Analog Programming (IP & VP) |
|
|
|
|
|
|
|
|
|
|
Input Signal:* |
|
|
|
|
| 0 to |
|
|
| |
Input Impedance: |
|
|
|
| 10 kΩ, nominal |
|
|
| ||
*Signal source must be isolated. |
|
|
|
|
|
|
|
|
|
|
Current Monitor Output (+IM): |
| 0 to |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
Savable States |
|
|
|
|
|
|
|
|
|
|
Nonvolatile Memory Locations: |
|
|
|
| 5 ( 0 through 4) |
|
|
| ||
Nonvolatile Memory Write Cycles: |
|
|
|
| 40,000, typical |
|
|
| ||
Prestored State (factory default): |
|
|
|
|
| Location 0 |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
Notes: lFor Performance Specifications, see Table