Cleaning
To prevent electric shock, unplug the unit before cleaning.
Use a dry cloth or one slightly dampened with water to clean the external case parts. Do not attempt to clean internally.
Location and Temperature
Bench Operation
The “Supplemental Characteristics” in Chapter 1 give the dimensions of your power supply. The cabinet has plastic feet that are shaped to ensure
Rack Mounting
Series 668xA and 669xA supplies weigh 51.3 kg (113 lb). Obtain adequate help when mounting the supply in the rack.
The power supply can be mounted in a standard
Series 667xA, 668xA, &669xA
Series 667xA, 668xA, 669xA supplies require instrument support rails for
Temperature Performance
A
Series 664xA & 665xA Operates without loss of performance within the temperature range of 0 °C to 40 °C and with derated output from 40 °C to 55 °C.
Series 667xA, 668xA, &669xA Operates without loss of performance within the temperature range of 0 °C to 55 °C.
It a Series 664xA or 665xA power supply is operated at full output current for several hours, the sheet metal immediately under the transformer (near the right front) can get very hot. Do not touch this area of the cabinet. The line cord also can become quite warm. Both of these conditions are normal.