Agilent Technologies 668xA, 665xA, 664xA, 667xA User Connections, Rear Panel Connections All Models

Models: 668xA 669xA 667xA 664xA 665xA

1 142
Download 142 pages 24.05 Kb
Page 59
Image 59

4

User Connections

Rear Panel Connections (All Models)

Make application load connections to the output terminals or bus bars, analog connector, and digital connector as shown on the rear-panel drawing for your model power supply. These connections are organized by series as follows:

Series 664xA and 665xA

Series 667xA

Series 668xA and 669xA

Make controller connections (GPIB and serial link) as shown in Figure 4-6 at the end of this chapter.

Load Wire Selection (All Models)

Fire Hazard To satisfy safety requirements, load wires must be large enough not to overheat when carrying the maximum short-circuit current of the power supply. If there is more than one load, then any pair of load wires must be capable of safely carrying the full-rated current of the supply. With the larger-capacity supplies (such as Series 668xA), use of two or more load wires in parallel may be required.

Table 4-1 lists the characteristics of AWG (American Wire Gauge) copper wire.

Table 4-1. Stranded Copper Wire Capacity and Resistance

AWG

Ampacityl

Resistance2

AWG

Ampacity1

Resistance2

No.

 

(/m)

No.

 

(/m)

14

25

0.0103

2

140

0.00064

12

30

0.0065

1/0

195

0.00040

10

40

0.0041

2/0

225

0.00032

8

60

0.0025

3/0

260

0.00025

6

80

0.0016

4/0

300

0.00020

4

105

0.0010

 

 

 

 

 

 

NOTES:

 

 

1.

Ampacity is based on 30 °C ambient temperature with conductor rated at 60 °C. For ambient temperature other

 

than 30 °C, multiply the above ampacities by the following constants:

 

 

Temp (°C)

Constant

Temp (°C)

Constant

 

21-25

1.08

 

41-45

0.71

 

26-30

1.00

 

46-50

0.58

 

31-35

0.91

 

51-55

0.41

2.

36-40

0.82

 

 

 

Resistance is nominal at 75 °C wire temperature.

 

 

 

 

 

 

 

 

User Connections 59

Page 59
Image 59
Agilent Technologies 668xA, 665xA manual User Connections, Rear Panel Connections All Models, Load Wire Selection All Models