Honeywell W7752D specifications Type of Heating and Cooling Equipment

Page 15

EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

Fig. 9. Three-speed fan switching and hysteresis, cooling mode (defaults for switching levels shown)

Type of Heating and Cooling Equipment

Excel 10 FCU Controllers can operate with either two-pipe or four-pipe systems. A two-pipe system requires a changeover input to the controller (hardware or network input).

Excel 10 FCU Controllers can operate with a variety of actuators for heating and cooling equipment. Floating actuators can be used; this requires that the valve run time be specified during configuration of the controller.

The actuator runtimes can be configured in the range 20 sec to 600 sec in steps of 1 second.

Valves will be synchronized by driving the valve fully closed

(150% of the valve run time) under the following conditions:

whenever the control level reaches 0% or less;

at power-on;

whenever the occupancy status changes to a lower mode, e.g., from occupied to standby or unoccupied;

when synchronization has not taken place within the last 24 hours.

Once synchronization has been completed, the output control will be returned to the normal control loop.

Valve action can be configured as either direct or reverse. When in a two-pipe system with a changeover input, a floating actuator can be used which has the middle position (50%) as the zero energy position. The cool range is then 0 to 50% and the heat range 50 to 100%. The output must be configured as floating-mid.

Multi-stage systems can be controlled with up to three different stages of heating/cooling control. Switching levels are specified in % of control level (see Fig. 10) as is a hysteresis setting which applies to all switching levels. Heating and cooling switching levels and hysteresis are specified separately. Min. OFF times can be configured, and for one-, two- and three-stage systems, a min. ON time can also be configured.

PWM electronic valves and thermal actuators can also be connected and can be configured as either direct or reverse action. The cycle time must be specified during configuration. In the case of PWM valves, the zero and full positions must also be configured.

Additionally, the W7754K1001 features an extra socket (located to the left of the terminal blocks) containing a digital output suitable for connection to a solid-state relay employed for low-voltage PWM control in high-current electric reheat applications.

13

EN2B-0285GE51 R0909

Image 15
Contents Excel Appendix a Using An LNS tool to Commission a Fan Coil Unit Appendix B Configuring for Master/Slave OperationAppendix C LON Interface Revision History Typical system overview Description of DevicesProduct Names Products CoveredOrganization of Manual Applicable LiteratureControl Provided Control ApplicationSetpoint from Network SetpointsSetpoint Knob Setpoint LimitsZEB Bypass Energy-Saving FeaturesOccupancy Status Operating Modes Safety FeaturesElectrical Shock Hazard ConstructionExcel 10 W7752 FCU Controllers Excel 10 W7754 FCU Controllers 180 Controller Performance Specifications Configurations GeneralFan Type Type of Heating and Cooling Equipment Digital Input Reheat OutputExcel 10 Wall Module Options Common Temperature Control Master/Slave ControllersAbbreviations and Definitions Step No Description OverviewPlan the System Determine Other Bus Devices RequiredLonworks Layout Lay Out Communications and Power WiringPrepare Wiring Diagrams Power WiringGeneral Considerations Plenum WiringPower Vendor wire typeLOW 230 XAL-Term ONW Orks TerminationEchelon-Based Components and Parts Order EquipmentExcel 10 Wall Modules Excel 10 SensorsUsing Plug-Ins Configure ControllersOutput Input Fan Equipment ControlSwitching Levels Zone OptionsMiscellaneous Commissioning TroubleshootingTroubleshooting Excel 10 FCU Controllers and Wall Modules AlarmsReturntonormal FCU AlarmsManual Mode Broadcasting the Service MessageProcedure Temperature Sensor CalibrationNetwork Variable Binding Output Configuration OptionsInput Configuration Options Zone Control OptionsAppendix C LON Interface Page NV name Continuous Automode To 100% For the reheat output EN2B-0285GE51 R0909 Byte Fiveposition NoswitchByte Ntcnonlinearize NtcnonlinearizedDiairflow Byte DinotusedDiwindowclosed DioccupiedsensorThreestage Byte FloatingOnestage TwostageByte Reheat FreeuseRelnotused Twopipe FourpipeUword Nobutton OffsetAbsolutemiddle BypassunoccupieTable C3. Input Variables for Excel 10 FCU Controllers Ocnul Modeenable UnsuppressalarmsModedisable SuppressalarmsRqnormal Rqupdatestatus Rqupdatealarm Rqreportmask OFF NULInvalid OFF1ON2 Byte NormalhcmodeOFF1OFF2 ON1OFF2Ledoff Ledon Byte NormalfanmodeNowindow ClosedOpen Table C4. Output Variables for Excel 10 FCU Controllers Rtncomfailschedocc RtncomfailtempresetAlarmnotifydisabled RtncomfailsetptoffsAlmcomfailmanheat Almcomfailmancool Almhwswmismatch OFF NotassignedOcbypass Ocstandby Fieldschedocc OFF Nofanspeedsw UbyteFieldeffectocc FieldhwoverrideOcunoccupied Ocbypass Ocstandby Ocnul CtlfanswitchoffCtldisabled Ocunoccupied Ocbypass OcstandbyExternalnotactice Not Actice ActiveFanoffafteroncmd FanrunsStoff StonInvalid Uword Contactopen Contactclosed Uword OFF NoreheatNotpressed PressedInvalid Byte Initial Stlow Stmed SthighInalarm EnabledDisabled NoalarmOpen Nowindow Alarm Suppressalarms AlarmnotifydisabledBugver Nodetype Word Table C5. Unused Variables for Excel 10 FCU ControllersAutomation and Control Solutions