Step 3. Lay Out Communications and Power Wiring

LONWORKS Layout

The communications bus, LONWORKS, is a 78-kilobit serial link that uses transformer isolation and differential Manchester encoding. Wire the LONWORKS using wires with specifications set forth in Table 10. An FTT LONWORKS can be wired in daisy chain, star, loop or any combination thereof as long as the max. wire length requirements given in Step 2 are met.

NOTE: Due to the transformer isolation, the bus wiring does not have a polarity; that is, it is not important which of the two LONWORKS terminals are connected to each wire of the twisted pair.

LONWORKS networks can be configured in a variety of ways, but the rules listed in Table 9 always apply. Fig. 13 and Fig. 14 depict two typical daisy chain LONWORKS network layouts; one as a single bus segment that has 60 nodes or less, and one showing two segments. Fig. 15 shows examples of free topology bus layouts. The bus configuration is set up using the Network Manager tool.

Excel 5000

Excel 10 W7754

FCU Controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Honeywell

D-71101 Schönaich

Made in Germany

12

Excel 10 W7752

FCU Controller

 

Honeywell

9

10 11 12

termination module

Fig. 13. LONWORKS wiring layout for one daisy-chain network segment

Excel 5000

Excel 10 W7754

Excel 10 W7752

FCU Controller

FCU Controller

 

 

 

Honeywell

 

Honeywell

 

 

 

 

 

 

D-71101 Schönaich

 

 

 

 

Made in Germany

 

 

 

12

 

9

10 11 12

 

max. 60 nodes

 

 

 

 

 

Excel 10 W7754

Excel 10 W7752

 

FCU Controller

FCU Controller

 

 

 

Honeywell

LonWorks

 

Made in Germany

 

 

router

 

Honeywell

 

 

 

termination module

D-71101 Schönaich

 

 

 

12

9

10 11 12

 

 

 

 

 

 

 

 

max. 60 nodes

 

 

Fig. 14. LONWORKS wiring layout for two daisy-chain network segments

termination module

termination module

EN2B-0285GE51 R0909

18

Image 20
Contents Excel Appendix C LON Interface Revision History Appendix a Using An LNS tool to Commission a Fan Coil UnitAppendix B Configuring for Master/Slave Operation Description of Devices Typical system overviewProducts Covered Organization of ManualApplicable Literature Product NamesControl Application Control ProvidedSetpoints Setpoint KnobSetpoint Limits Setpoint from NetworkZEB Energy-Saving Features BypassOccupancy Status Safety Features Operating ModesConstruction Excel 10 W7752 FCU ControllersExcel 10 W7754 FCU Controllers Electrical Shock Hazard180 Controller Performance Specifications Fan Type ConfigurationsGeneral Type of Heating and Cooling Equipment Reheat Output Digital Input Common Temperature Control Master/Slave Controllers Excel 10 Wall Module OptionsAbbreviations and Definitions Overview Plan the SystemDetermine Other Bus Devices Required Step No DescriptionLay Out Communications and Power Wiring Lonworks LayoutGeneral Considerations Prepare Wiring DiagramsPower Wiring Wiring PowerVendor wire type PlenumLOW 230 ONW Orks Termination XAL-TermOrder Equipment Excel 10 Wall ModulesExcel 10 Sensors Echelon-Based Components and PartsConfigure Controllers Using Plug-InsOutput Input Equipment Control FanMiscellaneous Switching LevelsZone Options Troubleshooting Troubleshooting Excel 10 FCU Controllers and Wall ModulesAlarms CommissioningFCU Alarms ReturntonormalBroadcasting the Service Message Manual ModeTemperature Sensor Calibration ProcedureOutput Configuration Options Input Configuration OptionsZone Control Options Network Variable BindingAppendix C LON Interface Page NV name Continuous Automode To 100% For the reheat output EN2B-0285GE51 R0909 Noswitch Byte NtcnonlinearizeNtcnonlinearized Byte FivepositionByte Dinotused DiwindowclosedDioccupiedsensor DiairflowByte Floating OnestageTwostage ThreestageRelnotused Byte ReheatFreeuse Fourpipe TwopipeUword Offset AbsolutemiddleBypassunoccupie NobuttonTable C3. Input Variables for Excel 10 FCU Controllers Modeenable Unsuppressalarms ModedisableSuppressalarms OcnulInvalid Rqnormal Rqupdatestatus Rqupdatealarm RqreportmaskOFF NUL Byte Normalhcmode OFF1OFF2ON1OFF2 OFF1ON2Byte Normalfanmode Ledoff LedonOpen NowindowClosed Table C4. Output Variables for Excel 10 FCU Controllers Rtncomfailtempreset AlarmnotifydisabledRtncomfailsetptoffs RtncomfailschedoccOcbypass Ocstandby Almcomfailmanheat Almcomfailmancool AlmhwswmismatchOFF Notassigned OFF Nofanspeedsw Ubyte FieldeffectoccFieldhwoverride FieldschedoccCtlfanswitchoff CtldisabledOcunoccupied Ocbypass Ocstandby Ocunoccupied Ocbypass Ocstandby OcnulNot Actice Active FanoffafteroncmdFanruns ExternalnotacticeInvalid Uword StoffSton OFF Noreheat NotpressedPressed Contactopen Contactclosed UwordStlow Stmed Sthigh Invalid Byte InitialEnabled DisabledNoalarm InalarmAlarm Suppressalarms Alarmnotifydisabled Open NowindowBugver Nodetype Table C5. Unused Variables for Excel 10 FCU Controllers WordAutomation and Control Solutions