EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
Step 3. Lay Out Communications and Power Wiring
LONWORKS Layout
The communications bus, LONWORKS, is a
NOTE: Due to the transformer isolation, the bus wiring does not have a polarity; that is, it is not important which of the two LONWORKS terminals are connected to each wire of the twisted pair.
LONWORKS networks can be configured in a variety of ways, but the rules listed in Table 9 always apply. Fig. 13 and Fig. 14 depict two typical daisy chain LONWORKS network layouts; one as a single bus segment that has 60 nodes or less, and one showing two segments. Fig. 15 shows examples of free topology bus layouts. The bus configuration is set up using the Network Manager tool.
Excel 5000 | Excel 10 W7754 | |||||||||
FCU Controller | ||||||||||
| ||||||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
Honeywell
Made in Germany
12 |
Excel 10 W7752
FCU Controller
| Honeywell |
9 | 10 11 12 |
termination module |
Fig. 13. LONWORKS wiring layout for one daisy-chain network segment
Excel 5000 | Excel 10 W7754 | Excel 10 W7752 | |
FCU Controller | FCU Controller | ||
|
|
| Honeywell |
| Honeywell |
|
|
|
| |
|
|
|
| |
|
| Made in Germany |
|
|
| 12 |
| 9 | 10 11 12 |
| max. 60 nodes |
| ||
|
|
| ||
| Excel 10 W7754 | Excel 10 W7752 | ||
| FCU Controller | FCU Controller | ||
|
|
| Honeywell | LonWorks |
| Made in Germany |
|
| router |
| Honeywell |
|
|
|
termination module |
|
|
| |
12 | 9 | 10 11 12 |
| |
|
| |||
|
|
|
| |
| max. 60 nodes |
|
|
Fig. 14. LONWORKS wiring layout for two daisy-chain network segments
termination module |
termination module |
18 |