EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
NV name
nciFcuConfig
nciFcuConfig
nciFcuConfig
nciFcuConfig
field name
DI1_config
fan_config
output_mode[0]
output_mode[1]
Table C2. Configuration Variables for Excel 10 FCU Controllers
engineering units: | digital |
|
| |
state | default | comments | ||
English (metric) or states | ||||
or | ||||
plus range |
|
| ||
value |
|
| ||
|
|
| ||
BYTE |
| DI_NOT_USED | This configuration variable specifies the digital input function and type | |
DI_WINDOW_CLOSED | 0 |
| of switch. The option to be selected is the one which is the condition for | |
DI_OCCUPIED_SENSOR | 1 |
| a closed switch contact (e.g., | |
DI_AIR_FLOW | 2 |
| DI_WINDOW_CLOSED, | |
DI_CHANGEOVER_COOL | 3 |
| DI_WINDOW_OPEN). | |
DI_WINDOW_OPEN | 4 |
| DI_MOVEMENT and DI_NO_MOVEMENT are supported starting with | |
DI_UNOCCUPIED_SENS | 5 |
| ||
DI_NO_AIR_FLOW | 6 |
| FCU2 version 1.0.3. These configuration settings cause the controller | |
DI_CHANGEOVER_HEAT | 7 |
| to retain the occupied state for 15 minutes after the last movement is | |
DI_MOVEMENT | 8 |
| detected. | |
DI_NO_MOVEMENT | 9 |
|
| |
DI_NOT_USED | 255 |
|
| |
|
|
|
| |
BYTE |
| THREE_SPEED | This configuration variable specifies the type of fan connected to the | |
NO_FAN | 0 |
| controller. | |
ONE_SPEED | 1 |
|
| |
TWO_SPEED | 2 |
|
| |
THREE_SPEED | 3 |
|
| |
|
|
|
| |
BYTE |
| OUTP_HEATING | This configuration variable specifies the operating mode of the output | |
OUTP_COOLING | 0 |
| 1. | |
OUTP_HEATING | 1 |
|
| |
OUTP_CHANGEOVER | 2 |
|
| |
OUTP_NOT_USED | 255 |
|
| |
|
|
|
| |
BYTE |
| OUTP_COOLING | This configuration variable specifies the operating mode of the output | |
OUTP_COOLING | 0 |
| 2. This setting is ignored for nciNumValve = TWO_PIPE. | |
OUTP_HEATING | 1 |
|
| |
OUTP_CHANGEOVER | 2 |
|
| |
OUTP_NOT_USED | 255 |
|
| |
|
|
|
|