Honeywell W7752D specifications To 100% For the reheat output EN2B-0285GE51 R0909

Page 41

EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

NV name

nciCntrlSettings

nciCntrlSettings

nciCntrlSettings

nciCntrlSettings

nciCntrlSettings

nciCntrlSettings

nciCntrlSettings

nciCntrlSettings

nciCntrlSettings

nciCntrlSettings

nciCntrlSettings

field name

fan_run_up_time

fan_overrun_time

switch_level_cool[0]

switch_level_cool[1]

switch_level_cool[2]

switch_level_heat[0]

switch_level_heat[1]

switch_level_heat[2]

staging_hysteresis[0]

staging_hysteresis[1]

reheat_switch_level

Table C2. Configuration Variables for Excel 10 FCU Controllers

engineering units:

digital

 

 

state

default

comments

English (metric) or states

or

plus range

 

 

value

 

 

 

 

 

SNVT_time_sec

0

0

This configuration variable specifies the time the fan runs before the

0 to 600 seconds

 

 

outputs are switched ON. It is typically used for electric heat outputs

 

 

 

with fan interlock (see nciFcuConfig.fan_interlock_0 and _1). The

 

 

 

interlock must be set.

 

 

 

 

SNVT_time_sec

0

0

This configuration variable specifies the time the fan still runs after the

0 to 600 seconds

 

 

control algorithm has turned OFF the cooling/heating outputs. It is

 

 

 

typically used for electric heat with fan interlock (see

 

 

 

nciFcuConfig.fan_interlock_0 and _1). The interlock must be set. In

 

 

 

case of smoke purge the overrun-time will be ignored.

 

 

 

 

SNVT_lev_percent

 

5%

This is the switching level to turn ON stage 1 of the cooling equipment

0 to 100%, 0 = Disable

 

 

(if configured as multistage).

 

 

 

 

SNVT_lev_percent

 

50%

This is the switching level to turn ON stage 2 of the cooling equipment

0 to 100%, 0 = Disable

 

 

(if configured as multistage).

 

 

 

 

SNVT_lev_percent

 

75%

This is the switching level to turn ON stage 3 of the cooling equipment

0 to 100%, 0 = Disable

 

 

(if configured as multistage).

 

 

 

 

SNVT_lev_percent

 

5%

This is the switching level to turn ON stage 1 of the heating equipment

0 to 100%, 0 = Disable

 

 

(if configured as multistage).

 

 

 

 

SNVT_lev_percent

 

50%

This is the switching level to turn ON stage 2 of the heating equipment

0 to 100%, 0 = Disable

 

 

(if configured as multistage).

 

 

 

 

SNVT_lev_percent

 

75%

This is the switching level to turn ON stage 3 of the heating equipment

0 to 100%, 0 = Disable

 

 

(if configured as multistage).

 

 

 

 

SNVT_lev_percent

 

10%

This configuration variable applies only to cool outputs configured as

0 to 100%

 

 

multistage outputs and specifies the hysteresis between switching the

 

 

 

cool stages ON and OFF.

 

 

 

 

SNVT_lev_percent

 

10%

This configuration variable applies only to heat outputs configured as

0 to 100%

 

 

multistage outputs and specifies the hysteresis between switching the

 

 

 

heat stages ON and OFF.

SNVT_lev_percent

 

100%

This configuration variable specifies the switch-over control output level

0 to 100%

 

 

for the reheat output.

 

 

 

 

39

EN2B-0285GE51 R0909

Image 41
Contents Excel Appendix C LON Interface Revision History Appendix a Using An LNS tool to Commission a Fan Coil UnitAppendix B Configuring for Master/Slave Operation Typical system overview Description of DevicesOrganization of Manual Products CoveredApplicable Literature Product NamesControl Provided Control ApplicationSetpoint Knob SetpointsSetpoint Limits Setpoint from NetworkZEB Bypass Energy-Saving FeaturesOccupancy Status Operating Modes Safety FeaturesExcel 10 W7752 FCU Controllers ConstructionExcel 10 W7754 FCU Controllers Electrical Shock Hazard180 Controller Performance Specifications Fan Type ConfigurationsGeneral Type of Heating and Cooling Equipment Digital Input Reheat OutputExcel 10 Wall Module Options Common Temperature Control Master/Slave ControllersAbbreviations and Definitions Plan the System OverviewDetermine Other Bus Devices Required Step No DescriptionLonworks Layout Lay Out Communications and Power WiringGeneral Considerations Prepare Wiring DiagramsPower Wiring Power WiringVendor wire type PlenumLOW 230 XAL-Term ONW Orks TerminationExcel 10 Wall Modules Order EquipmentExcel 10 Sensors Echelon-Based Components and PartsUsing Plug-Ins Configure ControllersOutput Input Fan Equipment ControlMiscellaneous Switching LevelsZone Options Troubleshooting Excel 10 FCU Controllers and Wall Modules TroubleshootingAlarms CommissioningReturntonormal FCU AlarmsManual Mode Broadcasting the Service MessageProcedure Temperature Sensor CalibrationInput Configuration Options Output Configuration OptionsZone Control Options Network Variable BindingAppendix C LON Interface Page NV name Continuous Automode To 100% For the reheat output EN2B-0285GE51 R0909 Byte Ntcnonlinearize NoswitchNtcnonlinearized Byte FivepositionDiwindowclosed Byte DinotusedDioccupiedsensor DiairflowOnestage Byte FloatingTwostage ThreestageRelnotused Byte ReheatFreeuse Twopipe FourpipeUword Absolutemiddle OffsetBypassunoccupie NobuttonTable C3. Input Variables for Excel 10 FCU Controllers Modedisable Modeenable UnsuppressalarmsSuppressalarms OcnulInvalid Rqnormal Rqupdatestatus Rqupdatealarm RqreportmaskOFF NUL OFF1OFF2 Byte NormalhcmodeON1OFF2 OFF1ON2Ledoff Ledon Byte NormalfanmodeOpen NowindowClosed Table C4. Output Variables for Excel 10 FCU Controllers Alarmnotifydisabled RtncomfailtempresetRtncomfailsetptoffs RtncomfailschedoccOcbypass Ocstandby Almcomfailmanheat Almcomfailmancool AlmhwswmismatchOFF Notassigned Fieldeffectocc OFF Nofanspeedsw UbyteFieldhwoverride FieldschedoccCtldisabled CtlfanswitchoffOcunoccupied Ocbypass Ocstandby Ocunoccupied Ocbypass Ocstandby OcnulFanoffafteroncmd Not Actice ActiveFanruns ExternalnotacticeInvalid Uword StoffSton Notpressed OFF NoreheatPressed Contactopen Contactclosed UwordInvalid Byte Initial Stlow Stmed SthighDisabled EnabledNoalarm InalarmOpen Nowindow Alarm Suppressalarms AlarmnotifydisabledBugver Nodetype Word Table C5. Unused Variables for Excel 10 FCU ControllersAutomation and Control Solutions