EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
NV name
nciCntrlSettings
nciCntrlSettings
nciCntrlSettings
nciCntrlSettings
nciCntrlSettings
nciCntrlSettings
nciCntrlSettings
nciCntrlSettings
nciCntrlSettings
nciCntrlSettings
nciCntrlSettings
field name
fan_run_up_time
fan_overrun_time
switch_level_cool[0]
switch_level_cool[1]
switch_level_cool[2]
switch_level_heat[0]
switch_level_heat[1]
switch_level_heat[2]
staging_hysteresis[0]
staging_hysteresis[1]
reheat_switch_level
Table C2. Configuration Variables for Excel 10 FCU Controllers
engineering units: | digital |
|
| |
state | default | comments | ||
English (metric) or states | ||||
or | ||||
plus range |
|
| ||
value |
|
| ||
|
|
| ||
SNVT_time_sec | 0 | 0 | This configuration variable specifies the time the fan runs before the | |
0 to 600 seconds |
|
| outputs are switched ON. It is typically used for electric heat outputs | |
|
|
| with fan interlock (see nciFcuConfig.fan_interlock_0 and _1). The | |
|
|
| interlock must be set. | |
|
|
|
| |
SNVT_time_sec | 0 | 0 | This configuration variable specifies the time the fan still runs after the | |
0 to 600 seconds |
|
| control algorithm has turned OFF the cooling/heating outputs. It is | |
|
|
| typically used for electric heat with fan interlock (see | |
|
|
| nciFcuConfig.fan_interlock_0 and _1). The interlock must be set. In | |
|
|
| case of smoke purge the | |
|
|
|
| |
SNVT_lev_percent |
| 5% | This is the switching level to turn ON stage 1 of the cooling equipment | |
0 to 100%, 0 = Disable |
|
| (if configured as multistage). | |
|
|
|
| |
SNVT_lev_percent |
| 50% | This is the switching level to turn ON stage 2 of the cooling equipment | |
0 to 100%, 0 = Disable |
|
| (if configured as multistage). | |
|
|
|
| |
SNVT_lev_percent |
| 75% | This is the switching level to turn ON stage 3 of the cooling equipment | |
0 to 100%, 0 = Disable |
|
| (if configured as multistage). | |
|
|
|
| |
SNVT_lev_percent |
| 5% | This is the switching level to turn ON stage 1 of the heating equipment | |
0 to 100%, 0 = Disable |
|
| (if configured as multistage). | |
|
|
|
| |
SNVT_lev_percent |
| 50% | This is the switching level to turn ON stage 2 of the heating equipment | |
0 to 100%, 0 = Disable |
|
| (if configured as multistage). | |
|
|
|
| |
SNVT_lev_percent |
| 75% | This is the switching level to turn ON stage 3 of the heating equipment | |
0 to 100%, 0 = Disable |
|
| (if configured as multistage). | |
|
|
|
| |
SNVT_lev_percent |
| 10% | This configuration variable applies only to cool outputs configured as | |
0 to 100% |
|
| multistage outputs and specifies the hysteresis between switching the | |
|
|
| cool stages ON and OFF. | |
|
|
|
| |
SNVT_lev_percent |
| 10% | This configuration variable applies only to heat outputs configured as | |
0 to 100% |
|
| multistage outputs and specifies the hysteresis between switching the | |
|
|
| heat stages ON and OFF. | |
SNVT_lev_percent |
| 100% | This configuration variable specifies the | |
0 to 100% |
|
| for the reheat output. | |
|
|
|
|
39 |
|