APC ACF102BLK manual Connect the power supply

Page 14

Operation

Connect the power supply

1.Set the fan speed selector to OFF.

2.Using one of the supplied power cords, connect the female end to the "A" input socket on the inside of the unit. Plug the male end into a power-protected socket. Ensure that there is adequate power for the fans to run at 100% (230V 4 A). The UPS in the rack must be sized properly to power this unit.

Use the Rack Air Removal Unit only with a 3000 watt UPS or higher. The UPS should not be loaded above 80% when using the Rack Air Removal Unit.

Warning

3.To provide redundant power to the unit, use the "B" input socket to connect to a second source of protected power.

4.Attach the cord retainer to lock the cords in place.

Cords may be bundled and tie-wrapped to provide clearance for other components.

Note

10

NetworkAIR Rack Air Removal Unit Installation

Image 14
Contents NetworkAIR Rack Air Removal Unit Page Contents Life-Support Policy Introduction FeaturesGeneral Information Safety Information Before You Begin InventoryTools required Receiving inspectionInstallation Remove the rear doorsInstall the fan frame Install the fan assembly Optional Items Operation Start-upConnect the power supply How to set the fans based on wattage Temperature overrideTemp Override Temperature Override How to set the temperature overrideHow to set the fans based on temperature Alarm Settings LED legendHow to Communicate Using the A-Link How to connect to the A-LinkHow to Communicate Using the A-Link Chart Warranty limitations Warranty and ServiceLimited warranty Obtaining serviceExamples of life-support devices Life-Support PolicyGeneral policy Specifications ACF102BLK 230VAC 50HzPage Page APC Worldwide Customer Support