Alarm Settings

The Rack Air Removal Unit has three LEDs on the front of the door that indicate whether the system is in an alarm state.

LED legend

LED

System

Fan

Thermal Control

 

Status

Status

Status

Description

Indicates the status of the

Indicates status of the three

Indicates the status of the

 

controller boards

fans

temperature in the

 

 

 

enclosure

 

 

 

 

Green

System OK

Fans OK

Temperature within range

 

 

 

 

Green

N/A

N/A

Exhaust temperature has

Flashing

 

 

exceeded the temperature

 

 

 

override setpoint

 

 

 

(kW mode only)

 

 

 

 

Red

Control failure, the fans

Fan failure,

High temperature, the unit

 

will default to high speed

remaining fans operate at

has lost thermal control

 

when there is a board

full speed

 

 

failure to keep air moving

 

 

 

through the enclosure

 

 

 

 

 

 

Red/Green

N/A

Smoke Alarm (optional)

Smoke Alarm (optional)

Flashing

 

 

 

NetworkAIR Rack Air Removal Unit Installation

15

Image 19
Contents NetworkAIR Rack Air Removal Unit Page Contents Life-Support Policy General Information FeaturesIntroduction Safety Information Inventory Before You BeginReceiving inspection Tools requiredRemove the rear doors InstallationInstall the fan frame Install the fan assembly Optional Items Start-up OperationConnect the power supply Temperature override How to set the fans based on wattage Temp Override How to set the temperature override Temperature OverrideHow to set the fans based on temperature LED legend Alarm SettingsHow to connect to the A-Link How to Communicate Using the A-LinkHow to Communicate Using the A-Link Chart Obtaining service Warranty and ServiceLimited warranty Warranty limitationsGeneral policy Life-Support PolicyExamples of life-support devices 230VAC 50Hz Specifications ACF102BLKPage Page APC Worldwide Customer Support