APC ACF102BLK manual Temp Override

Page 16

Operation

Temperature Override in each Fan Speed Mode

 

kW mode

Exhaust temperature

Remote mode

 

 

mode

 

 

 

 

 

Temp Override

Fan speed will increase

No Effect

Depends on the fan speed

Enabled

when rack equipment

 

selection of the remote

 

exhaust temperature

 

device. Same as kW or

 

reaches 40.5° C (105° F)

 

exhaust temperature mode.

 

 

 

In kW mode the

 

 

 

temperature override

 

 

 

setpoint can be set to

 

 

 

32.2–51.6° C (90–125°

 

 

 

F)

 

 

 

 

Temp Override

No Effect

No Effect

No Effect

Disabled

 

 

 

Note

If a Computer Room Air Conditioner fails, the subsequent rise in ambient temperature can cause the temperature override to activate. Increasing the fan speed can have an impact on the airflow in the room.

12

NetworkAIR Rack Air Removal Unit Installation

Image 16
Contents NetworkAIR Rack Air Removal Unit Page Contents Life-Support Policy General Information FeaturesIntroduction Safety Information Before You Begin InventoryTools required Receiving inspectionInstallation Remove the rear doorsInstall the fan frame Install the fan assembly Optional Items Operation Start-upConnect the power supply How to set the fans based on wattage Temperature overrideTemp Override Temperature Override How to set the temperature overrideHow to set the fans based on temperature Alarm Settings LED legendHow to Communicate Using the A-Link How to connect to the A-LinkHow to Communicate Using the A-Link Chart Warranty and Service Limited warrantyWarranty limitations Obtaining serviceGeneral policy Life-Support PolicyExamples of life-support devices Specifications ACF102BLK 230VAC 50HzPage Page APC Worldwide Customer Support