Enerco HST45 owner manual Venting/Ducting, Roof Pitch, Horizontal Through the Sidewall

Page 14

MINIMUM HEIGHT FROM ROOF

 

TO LOWEST DISCHARGE OPENING

 

Roof Pitch

H (Min)

Flat to 6/12

1.0 Feet

Over 6/12 to 8/12

1.5 Feet

Over 8/12 to 10/12

2.5 Feet

Over 10/12 to 12/12

4.0 Feet

Over 12/12 to 16/12

6.0 Feet

Over 16/12 to 20/12

7.5 Feet

2.All other gas vents shall terminate not less than 2 feet (0.6m) above the highest point where they pass through the roof and at least 2 feet (0.6m) higher than any portion of a building

located within 10 feet (3.1m) as shown in the following illustration.

10ft. or less

Vent Cap Type B

Vent Pipe

2ft. min.

 

Type B

 

(Double Wall)

 

Storm Collar

Boot Flashing

2" Clearance

NOTE : To minimize problems associated with condensation in long runs, vent pipe can be insulated.

3.The horizontal venting system approved with this heater consists of the Side Wall Vent Kit (02840) shown are page 3.

4.Limit the quantity of 90° elbows to two. When vent pipe is in a horizontal run, it must be pitched downward ¼ inch per foot towards the vent terminal. The heater must be installed level.

5.The horizontal venting system shall not terminate:

a)Less than 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (30cm) above any door, window or gravity air inlet into any building. The bottom of the vent terminal shall be located at least 7 feet (2.1m) above grade or above snow accumulation levels as determined by local codes.

b)Less than 3 feet (0.9m) from a combustion air inlet.

c)Less than 3 feet (0.9m) from any other building opening or any gas service regulator.

d)Directly over areas where condensate or vapor could create a nuisance or hazard or be harmful to the operation of gas utility meters, regulators, relief valves, or other equipment. Building materials should be protected from flue gases and condensate.

6.In regions of the country where prevailing winds are consistently higher than 40 mph, it may be necessary to terminate the vent system above the roof level.

Vent Cap

Type “B” Vent

Vent Pipe (Single Wall)

Seal joint & annular space.

c) Horizontal Through the Sidewall

This heater, when horizontally vented, must be installed with the approved venting system.

When venting the heater horizontally through a combustible outside wall, the same requirements listed previously for Venting Through the Roof apply except as follows:

1.When venting the heater to the outside of the building through a sidewall, use 3 inch O.D. single-wall metal pipe. This is to be

constructed of galvanized sheet metal or other approved noncombustible, corrosion-resistant material as indicated by state and/or local codes.

2.For horizontal venting, the vent lengths may be as follows:

Minimum Equivalent Length = 5 feet of Pipe Maximum Equivalent Length = 25 feet of Pipe

Use the following correction factors to obtain the equivalent length:

a)Subtract 15 feet if the run is horizontal

b)Subtract 10 feet for an approved vent cap.

c)Subtract 10 feet for each elbow beyond 15 feet from the heater.

d)Subtract 15 feet for each elbow within 15 feet of the heater.

EXAMPLE for an approved vent cap you have ---------

10 ft.

for a horizontal run you have -----------------

15 ft.

Your Maximum Equivalent Length is ----------------

25 ft.

 

 

Single-Wall

18"

 

Vent Pipe

 

 

 

Wall

Wall Thimble

 

 

Venting/Ducting

For Commercial and Industrial Installations Only General Requirements

Use aluminum or teflon tape suitable for 550°F (3M Company tapes #433 or #363) or RTV silicone sealant.

Heater must be vented in accordance with specification ANSI Z223.1 - latest revision . Partial information relating to this specification is provided in this section with regard to size and configurations for venting arrangements. For complete information consult ANSI Z223.1 - latest revision and applicable local codes. Use the following guidelines to help insure an adequate, safe ventin arrangement.

Enerco Group, Inc., Gas-Fired Low-Intensity Infrared Heater

14

Operating Instructions and Owner’s Manual

Image 14
Contents MR. Heater Contents Unpacking the Heater Available AccessoriesBefore YOU Begin IntroductionAbout The Heater Rear ViewVenting Specifications Technical SpecificationsHeater Specifications Side View End ViewInstaller’s responsibility Where can the heater be installed?Where can’t the heater be installed? Gas Service Requirements System RequirementsGrounding Electrical Service Requirements System RequirementsNon-residential Installations Venting RequirementsInstallation Tools InstallationSafety Equipment Installation MaterialsGeneral Guidelines Residential Horizontal InstallationsTilted Installations Minimum Required Safe Distances from CombustiblesHang the Heater Horizontal InstallationTilted Installation Heater Orientation MHT / HST Heater Assembly Instructions Venting Typical InstallationCanadian Installations1 US Installations2 10 ft Basic Flue Venting Residential OnlyVertical Through the Roof Horizontal Through the Sidewall Venting/DuctingRoof Pitch Single wall vent run Single wall terminal end Vertical VentingSingle Wall Double WallOutside Combustion Air Supply Electrical Service InstallationAir For Combustion Residential Direct Outside Air For Combustion Residential120V-60Hz Supply Circuit Gas Service InstallationInstall Gas Supply Lines Heater OperationUse LP-resistant joint compound on all threads Proper Operating Flame Maintenance Pre-Season MaintenanceOperation of the Heater Blower does not Come on TroubleshootingReplace fuse or reset circuit breaker Replace blower motor Igniter does not SparkBurner does not Light Burner does not Stay LITMHT-45 HST-45 Illustrated PartsIllustrated Parts MHT /HST45 Tube Heater Operating Instructions