Desa installation manual Pointing Down, Natural

Page 14

INSTALLATION

Continued

Installation Items Needed

Before installing heater, make sure you have the items listed below.

external regulator (supplied by installer)

piping (check local codes)

sealant (resistant to propane/LP gas)

equipment shutoff valve *

test gauge connection *

sediment trap

tee joint

pipe wrench

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 31.

For propane/LP gas, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pres- sure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 13. Pointing the vent down protects it from freezing rain or sleet.

Installation must include a equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 14).

IMPORTANT: Install equipment shutoff valve in an accessible location. The main gas valve is for turn- ing on or shutting off the gas to the appliance.

Check your building codes for any special re- quirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install sediment trap in supply line as shown in Figure 14. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

CAUTION:Useonlynew,black ironorsteelpipe.Internally-tinned copper tubing may be used in certain areas. Check your local codes.Usepipeof1/2"diameteror greatertoallowpropergasvolume toheater.Ifpipeistoosmall,undue loss of volume will occur.

Propane/LP

Supply Tank

External

Regulator

Vent

Pointing

Down

Figure 13 - External Regulator With Vent

Pointing Down

CAUTION: Avoid damage to regulator.Holdgasregulatorwith wrenchwhenconnectingittogas piping and/or fittings.

Natural

 

CSA Design-Certified

 

Equipment Shutoff Valve

From Gas Meter

With 1/8" NPT Tap*

(5" W.C.** to

 

 

10.5" W.C.

 

 

Gas

Pressure)

 

 

 

 

Regulator

 

 

 

Propane/LP

 

 

 

From External

 

 

Regulator

 

3" Min.

Approved

(11" W.C.**

 

 

 

 

Flexible

to 14" W.C.

 

 

Tee

Cap Pipe

Gas Hose (if

Pressure

allowed by

Joint

Nipple

 

 

Sediment Trap

local codes)

 

 

Figure 14 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 31.

** Min. inlet pressure for purpose of input adjustment.

14

www.desatech.com

113101-01C

Image 14 Contents
24 Variable MANUALLY-CONTROLLED Models Patent PendingTable of Contents Safety Information Product Identification Unpacking Product FeaturesLocal Codes AIR for Combustion VentilationUnusually Tight Construction Providing Adequate VentilationDetermining FRESH-AIR Flow for Fireplace Location Determining if You Have a Confined or Unconfined SpaceVentilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Check GAS TypeFront Rear Log Size Side Wall CeilingMinimum Firebox Size Minimum Noncombustible Material ClearancesMantel Clearances Log SetFloor Clearances Log SetAssembly Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Connecting to GAS Supply Installation Items NeededPointing Down NaturalTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Checking GAS ConnectionsTest Pressures In Excess Of 1/2 Psig 3.5 kPa Pressure Testing Heater Gas Connections Installing Back LogInstallation Operating Heater What to do if YOU Smell GASLighting Instructions Slightly depress and turn control knob counTo Turn OFF GAS To Appliance Manual Lighting ProcedureVariable Control Operation STOP! Read the safety information, page 20, column Pilot Flame Pattern Inspecting BurnersThermostat Control Operation Burner Primary AIR HolesBurner Injector Holder and Pilot AIR Inlet Hole Cleaning MaintenanceODS/PILOT and Burner Replacement Parts Technical ServiceService Hints Troubleshooting Observed Problem Possible Cause RemedyODS/pilot lights but flame goes See Cleaning and Mainte Gas leak. See Warning Statement aboveOptional Positioning Thermostat Sensing Bulb For Masonry and FACTORY- Built Metal FireplaceSpecifications Equipment Shutoff Valve GA5010 AccessoriesParts Central Fireplace HoodIllustrated Parts Breakdown Parts List Variable MANUALLY-CONTROLLED Winchester OAK ModelsIllustrated Parts Breakdown THERMOSTATICALLY-CONTROLLED Royal English OAK Models Limited Warranty VENT-FREE GAS Fireplace Warranty InformationKeep this Warranty