CHECKING GAS CONNECTIONS

WARNING:Testallgaspiping and connections , internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a commercial leak de- tection solution to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: For propane/LP units, make sure external regula- tor has been installed between propane/LP supply and heater. SeeguidelinesunderConnecting to Gas Supply, page 13.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping. Pressures in ex- cess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

4.Check all joints of gas supply piping system. Apply a commercial leak detection solution to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 15).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

3.Check all joints from gas meter (natural gas) or propane/LP supply to equipment shutoff valve (see Figure 16 or 17). Apply a commercial leak detection solution to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Equipment

Open

Shutoff Valve

 

 

Closed

Figure 15 - Equipment Shutoff Valve

Propane/LP

Equipment Shutoff Valve

Supply Tank

 

Control Valve

Location

Figure 16 - Checking Gas Joints (Propane/LP Gas Only)

Equipment Shutoff Valve

Gas

Meter

Control Valve Location

Figure 17 - Checking Gas Joints

(Natural Gas Only)

113101-01C

www.desatech.com

15

Image 15 Contents
Patent Pending 24 Variable MANUALLY-CONTROLLED ModelsTable of Contents Safety Information Product Identification AIR for Combustion Ventilation Product FeaturesLocal Codes UnpackingDetermining if You Have a Confined or Unconfined Space Providing Adequate VentilationDetermining FRESH-AIR Flow for Fireplace Location Unusually Tight ConstructionVentilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Check GAS Type InstallationMinimum Noncombustible Material Clearances Log Size Side Wall CeilingMinimum Firebox Size Front RearLog Set Mantel ClearancesLog Set Floor ClearancesInstalling Damper Clamp Accessory for Vented Operation Installing Heater BaseAssembly Installation Items Needed Connecting to GAS SupplyNatural Pointing DownChecking GAS Connections Test Pressures In Excess Of 1/2 Psig 3.5 kPaTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Installing Back Log Pressure Testing Heater Gas ConnectionsInstallation What to do if YOU Smell GAS Operating HeaterSlightly depress and turn control knob coun Lighting InstructionsManual Lighting Procedure Variable Control OperationTo Turn OFF GAS To Appliance STOP! Read the safety information, page 20, column Burner Primary AIR Holes Inspecting BurnersThermostat Control Operation Pilot Flame PatternCleaning Maintenance ODS/PILOT and BurnerBurner Injector Holder and Pilot AIR Inlet Hole Technical Service Service HintsReplacement Parts Observed Problem Possible Cause Remedy TroubleshootingODS/pilot lights but flame goes See Cleaning and Mainte Statement above Gas leak. See WarningFor Masonry and FACTORY- Built Metal Fireplace Optional Positioning Thermostat Sensing BulbSpecifications Fireplace Hood AccessoriesParts Central Equipment Shutoff Valve GA5010Illustrated Parts Breakdown Variable MANUALLY-CONTROLLED Winchester OAK Models Parts ListIllustrated Parts Breakdown THERMOSTATICALLY-CONTROLLED Royal English OAK Models Warranty Information Keep this WarrantyLimited Warranty VENT-FREE GAS Fireplace