Desa Ventilation AIR, Ventilation Air From Inside Building, Ventilation Air From Outdoors

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

Example:

Gas water heater

40,000

 

__________ Btu/Hr

Vent-free fireplace

31,500

 

+__________ Btu/Hr

Total

= 71,500

Btu/Hr

nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________Btu/Hr (maximum the space can support)

_________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

71,500 Btu/Hr (actual amount of Btu/Hr used)

The space in the example is a confined space because the actual Btu/Hr used is more than the maximum

Ventilation

 

Grills

 

Into Adjoining

Or

Room,

Remove

Option 1

Door into

 

 

Adjoining

 

Room,

 

Option

 

3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

Btu/Hr the space can support. You must provide ad- ditional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors, page 7.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma-

12"

Figure 2 - Ventilation Air from Inside

Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

113101-01C

www.desatech.com

7

Image 7
Contents Patent Pending 24 Variable MANUALLY-CONTROLLED ModelsTable of Contents Safety Information Product Identification AIR for Combustion Ventilation Product FeaturesLocal Codes UnpackingDetermining if You Have a Confined or Unconfined Space Providing Adequate VentilationDetermining FRESH-AIR Flow for Fireplace Location Unusually Tight ConstructionVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallationMinimum Noncombustible Material Clearances Log Size Side Wall CeilingMinimum Firebox Size Front RearLog Set Mantel ClearancesLog Set Floor ClearancesInstalling Heater Base Installing Damper Clamp Accessory for Vented OperationAssembly Installation Items Needed Connecting to GAS SupplyNatural Pointing DownTest Pressures In Excess Of 1/2 Psig 3.5 kPa Checking GAS ConnectionsTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Installing Back Log Pressure Testing Heater Gas ConnectionsInstallation What to do if YOU Smell GAS Operating HeaterSlightly depress and turn control knob coun Lighting InstructionsVariable Control Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance STOP! Read the safety information, page 20, column Burner Primary AIR Holes Inspecting BurnersThermostat Control Operation Pilot Flame PatternODS/PILOT and Burner Cleaning MaintenanceBurner Injector Holder and Pilot AIR Inlet Hole Service Hints Technical ServiceReplacement Parts Observed Problem Possible Cause Remedy TroubleshootingODS/pilot lights but flame goes See Cleaning and Mainte Statement above Gas leak. See WarningFor Masonry and FACTORY- Built Metal Fireplace Optional Positioning Thermostat Sensing BulbSpecifications Fireplace Hood AccessoriesParts Central Equipment Shutoff Valve GA5010Illustrated Parts Breakdown Variable MANUALLY-CONTROLLED Winchester OAK Models Parts ListIllustrated Parts Breakdown THERMOSTATICALLY-CONTROLLED Royal English OAK Models Keep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS Fireplace

CGS2718PA, CGS2718NA, CGS3124PA, CGS3124NA, SGS3124PA, SGS3124NA,CLD3018PTA, CLD3018NTA, CLD3924NTB, CLD3924PTB specifications

The models Desa CGS2718PA, CGS2718NA, CGS3124PA, CGS3124NA, SGS3124PA, SGS3124NA, CLD3018PTA, CLD3018NTA, CLD3924NTB, and CLD3924PTB are part of a versatile range of consumer appliances that combine modern technology with practical design. Each model brings its unique set of features aimed at enhancing user experience while maintaining high performance and efficiency.

Starting with the CGS series, the CGS2718PA and CGS2718NA are known for their compact sizes, making them ideal for smaller spaces without compromising functionality. They offer advanced digital controls, providing users with precise temperature settings and easy operation. Both models feature a sleek design, available in contemporary finishes that complement modern kitchen aesthetics.

The CGS3124PA and CGS3124NA expand on these features, offering greater capacity and additional functionalities such as enhanced cooking modes. These models incorporate the latest multi-cooking technology, allowing users to steam, bake, and roast with ease. Their energy-efficient systems help reduce power consumption while delivering great performance.

In the SGS series, both SGS3124PA and SGS3124NA prioritize efficiency and durability. Their robust construction is designed to withstand the rigors of daily use, while their intuitive controls simplify operation. These models are equipped with smart sensors that monitor cooking conditions and adjust settings automatically, ensuring optimal results every time.

Moving to the CLD series, the CLD3018PTA and CLD3018NTA are designed for versatility, featuring multiple cooking settings that cater to diverse culinary needs. These models excel in user-friendly interfaces, making meal preparation accessible to everyone, from novice cooks to experienced chefs.

The CLD3924NTB and CLD3924PTB stand out with their larger capacity and advanced technology that includes self-cleaning options, programmable timers, and compatibility with smart home systems. This adds another layer of convenience to the cooking process, allowing users to plan meals according to their schedules.

Overall, these models offer a comprehensive approach to modern cooking with an emphasis on efficiency, ease of use, and stylish design. They not only meet the demands of everyday cooking but also enhance the overall experience in the kitchen, making them a valuable addition to any home.