INSTALLATION
WARNING: Before installing in a solid fuel burning fireplace, the chimney flue and firebox must be cleaned of soot, creo- sote, ashes and loose paint by a qualified chimney cleaner. Creo- sote will ignite if highly heated. A dirty chimney flue may create and distribute soot within the house. Inspect chimney flue for damage. If damaged, repair flue before operating appliance.
NOTICE:Installation,service,and repair of this appliance must be performedbyaqualifiedinstaller, service agency, company or gas supplier experienced with this type of gas appliance. Only factory authorized components listed in these instructions may be used in accordance with the manufacturer’s instructions and all codes and requirements of the authority having jurisdiction. Any modifications to this kit, or use of unauthorized components or accessory items will void the manufacturer’swarranty,andmay result in a hazardous condition.
FLUE OPENING SPECIFICATIONS
Note: This vented appliance must be installed only in a
The charts in Figure 2 indicate technical information regarding the installation of your gas log set. Please make sure that all of the specifications shown are applicable before installation is attempted.
The fireplace must include a working flue and venting system with the minimum openings shown in the Figure 2.
|
|
| Burner | Btu Input |
| Minimum | |||||||||
|
|
| Descrip- | Natural |
|
| Vent | ||||||||
Model |
| tion |
|
| Gas |
| Opening | ||||||||
|
|
|
|
|
|
|
|
|
|
| |||||
SMS18 |
| 18" Ramp | 60,000 |
|
| 8" dia. | |||||||||
SMS24 |
| 24" Ramp | 80,000 |
|
| 8" dia. | |||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| MINIMUM FIREBOX SIZES | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
MODEL |
| FRONT |
| BACK |
| DEPTH | HEIGHT | ||||||||
|
|
| WIDTH |
| WIDTH* |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
SMS18 | 28" |
| 18" |
|
| 16" |
|
| 18" | ||||||
SMS24 | 32" |
| 24" |
|
| 16" |
|
| 18" | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
*At depth indicated |
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
| ||||||||||
|
| FUEL INLET PRESSURE |
| ||||||||||||
|
| SPECIFICATIONS (W.C.) |
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| Min. |
|
|
|
| Max. |
| ||||
| NG |
| 5.5" |
|
| 10.5" |
|
| |||||||
| LP |
| 11" |
|
| 13" |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| BURNER ORIFICE |
|
|
| |||||||||
| LOG |
|
| NATURAL |
|
|
| ||||||||
| SIZE |
|
|
|
|
|
|
|
|
|
| ||||
|
| IN. |
|
| NUM. |
| |||||||||
|
| 18" |
| .120 |
|
| 31 |
|
| ||||||
|
| 24" |
| .140 |
|
| 28 |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 2 - Technical Information Charts
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural gas, you must install ON/OFF Safety Valve/Pilot Kit (see Accessories, page 13). Call dealer where you bought log set.
If the fireplace does not have a gas supply shutoff valve, one must be installed.
VENTING SPECIFICATIONS FOR INSTALLATION
The fireplace chimney flue and vent must be draft- ing properly. To check the vent for proper drafting: Light a tightly rolled newspaper on one end and place it at the inside front edge of the fireplace. Observe the smoke and be sure the vent is properly drawing it up the chimney. If the smoke spills out into the room, extinguish the flame and remove any obstruction until proper venting is achieved.
The chimney flue must remain open a minimum of 3" at all times during the operation of this log set.