Bosch Appliances BC2600RA installation manual Gas Piping, Gas Pressure, Gas Meter

Page 9

Installation Instructions

7. Gas Piping

Follow the instructions from the gas supplier.

The appliance must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 3.5 kPa.

The appliance and its gas connections must be leak tested before placing the appliance in operation.

The inlet gas pressure must be within the range specified. This is for the purposes of input adjustment.

In order to choose the proper size for the gas line, consult local codes and / or the AS5601.

Gas Pressure

Size the gas line according to total MJ/h demand of the building and length from the meter or regulator so that the follow- ing supply pressures are available even at maximum demand refer AS5601:

Natural Gas Supply Pressure

Min. 1.13 kPa

Max. 3.00 kPa

LP Gas Supply Pressure

Min. 2.75 kPa

Max. 3.50 kPa

Gas Meter

Select a gas meter capable of supplying the entire MJ/h demand of all gas appli- ances in the building.

Measuring Gas Pressure

Gas Connection

1)Fit a union to the water heater gas inlet for easy connec- tion and removal. The thread diameter is 20 mm.

THIS DOES NOT INDICATE THE SIZE OF THE GAS SUPPLY.

2)Fit an AGA / NZGA approved isolating gas cock in the supply line adjacent to the water heater gas connection.

3)Ensure that the supply pipe and the gas pressure regula- tor (LPG or Natural Gas) has sufficient flow capacity for this and other appliances connected to the fitting line.

4)For LPG appliances ensure that gas cylinders are of suf- ficient size. The water heater alone will require 2 x 45 Kg capacity cylinders.

5)Before connecting the appliance to the gas service, purge any debris or air from the gas service.

6)Check all joints for leaks with an approved leak tester after connection.

In order to check the gas supply pressure to the unit, a tap is provided on the gas inlet. Remove the hex head philips screw from the tap, and connect a manometer using a silicon tube.

In order to check the gas manifold pressure on the gas valve inside the unit. The pressure can be checked by removing the hex head philips screw and connecting a manometer with a silicon tube.

Refer to AS 5601 Installation Code or NZS 5261 : 2003 installation code for pipe sizing and details. Ensure that the gas pipe size is correct. If undersized the appliance will not operate correctly

SERVICE CALLS ARE CHARGEABLE FOR UNITS WITH INCORRECT PIPE SIZES OR BLOCKED GAS OR WATER FILTERS.

9

Image 9
Contents Installation Manual Installation Manual Included Accessories Use Extreme Caution if Using With a Solar Pre-Heater Before InstallationCheck the Gas Check Water Supply QualityIndoor Choosing Installation SiteBefore installing, check for the following Installation ClearancesClearances for Flue Terminal front of heater Securing to the wall InstallationGas Pressure Gas PipingGas Meter Measuring Gas Pressure Gas ConnectionWater Piping Supply water piping Drain processingHot water piping Condensate Piping Earth Electrical WiringYPRM67XB Connecting Remote Controller Cord to Unit Handling after trial operation MaintenanceLighting Instructions 338 Dimensions