Bosch Appliances GWH 2700 ES NG, GWH 2700 ES LP, ESVVT manual Domestic hot water recirculation, Gwh

Page 26

Installation instructions

Connecting the pressure relief valve (PRV)

A listed pressure relief valve supplied with the heater must be installed at the time of installation. No valve is to be placed between the PRV and the heater. No reducing coupling or other restriction may be installed in the discharge line. The discharge line must be a min- imum of 4” above a drain and installed such that it allows complete drainage of both the PRV and the line. The discharge line must be placed where it will not cause any damage.

The location of the PRV must be readily accessible for servicing or replacement, and be mounted as close to the water heater as possible. See Fig. 31. To install the PRV, a suitable fitting connected to an extension on a “T” fitting can be sweated to the hot water line.

Support all piping.

3.11 Domestic hot water recirculation

Although recirculation directly through the tankless water heater is allowed, temperature stability is improved by recirculating through a mini-tank as shown in Fig. 32. By using the design in Fig. 32, there is no recirculation of hot water through the tankless water heater and therefore, does not affect the heat exchanger warranty. Direct recirculation through the tankless water heater is permissible, however, the heat exchanger warranty is reduced; contact Bosch Thermotechnology for further installation requirements. The following drawing is provided to outline one possible recirculation design using the water heater in conjunction with an Ariston mini tank water heater. This schematic is for illustration only and must not be used for actual installation without appropriate engineering and technical advice from a properly licensed professional in the locality where the installation is made.

5

 

GWH

 

 

2700

 

 

ES

 

2

4

 

 

1

 

 

 

 

3

Fig. 31 Plumbing Connections (with shutoff valves) and Pressure Relief Valve

1Water filter

6720608158-77.1AL

Ariston Minitank

Fig. 32 Recirculation application

1Full port isolation valve

2 Circulator (pump)

3 Check valve

4PRV

5Expansion tank

The use of a small electric mini-tank water heater (4-6 gallon size) should be used for this application and designed so the pump will circulate the water through the mini-tank and the building's hot water return loop only. Timed or thermostatically controlled operation of the pump is commonly done. Contact Bosch Thermotechnology if further information is needed.

26

6 720 608 542

Image 26
Contents Intended for variable flow applications What to do if you smell gasIndex For your safety Features Appliance detailsSpecifications Technical data GWH 2700 ES is not approved or designed for To remove combustion cover service onlyUnpacking the heater General rules to follow for safe operation VentingDimensions and Minimum installation clearances DimensionsIntroduction Installation instructionsTools required for installation VentingFittings or Piping Equivalent Feet Installation instructions Horizontal venting systems onlyVenting Specifications Minimum combustion air and exhaust pipe length Installation instructions Condensate drain requirementsTwin pipe termination clearances Maximum combustion air and exhaust pipe lengthCanadian installations1 Installations2 Canadian installations1 Horizontal twin pipe penetration Vertical venting installation twin pipe penetra- tion Vent connectionsInstallation instructions Condensate drain installation Venting Flex ProTech Heat FabIntake Total equivalent vent length calculationExhaust ExampleLevel Vent length1 Speed P2 Adjusting minimum power fan speed P2Adjusting maximum power fan speed P1 Installation instructions Combustion air requirements Twin pipe and Concentric pipeMounting installation Proper location for installing your heaterHeater placement and clearances Gas piping & connections GAS Line Sizing For Natural GAS Water connections Water qualityDomestic hot water recirculation GWHStatic Pressure Test Connecting manometerMeasuring gas pressure Operating Pressure TestPosition of the fuses in control unit Electrical power supplyElectrical connections Operation instructions LCD Display functionsTemperature selection For your safety read before operating your water heaterPower Operation Use of optional remote control Accessory part no. TSTAT2Reset button Program buttonAnnual maintenance Maintenance and serviceAnnual maintenance table Every year Winterizing for seasonal useMineral scale build-up Adjusting CO2 carbon dioxideDescaling using a pump Returning to Service Measuring CO2 combustion cover must be installedAdjusting CO2 Once Gas Pressure is adequateFinal Readings % 3.0 % 60 ppmComment Program Description Factory DefaultProgram values Control board diagnostics Diagnostic menuWater is too hot TroubleshootingTroubleshooting Water is not hot enoughNoisy burner/heater during operation Hot water temperature fluctuates at tapLow water flow/pressure Lack of adequate gas pressure. Inadequate gas Problem solving Error code diagnosticsProblem solving Display Cause Solution Venting may cause this failureOver-temperature detected by No flame ionization detected with Electrical diagram Electrical diagramSensor resistance charts Back Flow characteristics GWH 2700 ES Functional scheme Functional schemeInterior components Interior components diagram and parts listInterior components diagram and parts list Appliance overview Description Reference Components diagramGroup Interior components diagram and parts list Group 1211 6720608158-73.1AL Interior components diagram and parts list Group 708 300 Packing Protecting the environmentProtecting the environment ComponentsLimited Warranty Limited Warranty 6720608542