Installation instructions
Connecting the pressure relief valve (PRV)
A listed pressure relief valve supplied with the heater must be installed at the time of installation. No valve is to be placed between the PRV and the heater. No reducing coupling or other restriction may be installed in the discharge line. The discharge line must be a min- imum of 4” above a drain and installed such that it allows complete drainage of both the PRV and the line. The discharge line must be placed where it will not cause any damage.
The location of the PRV must be readily accessible for servicing or replacement, and be mounted as close to the water heater as possible. See Fig. 31. To install the PRV, a suitable fitting connected to an extension on a “T” fitting can be sweated to the hot water line.
Support all piping.
3.11 Domestic hot water recirculation
Although recirculation directly through the tankless water heater is allowed, temperature stability is improved by recirculating through a
5 |
| GWH |
|
| 2700 |
|
| ES |
| 2 | 4 |
|
| |
1 |
|
|
|
| 3 |
Fig. 31 Plumbing Connections (with shutoff valves) and Pressure Relief Valve
1Water filter
Ariston Minitank
Fig. 32 Recirculation application
1Full port isolation valve
2 Circulator (pump)
3 Check valve
4PRV
5Expansion tank
The use of a small electric
26 | 6 720 608 542 |