Bosch Appliances GWH 2700 ES NG, GWH 2700 ES LP, ESVVT manual No flame ionization detected with

Page 44

Problem solving

Display

Cause

Solution

 

No flame ionization detected with

1.

Verify that all manual gas shut off valves are open.

 

water flow.

2.

Check gas type, see Fig. 2, page 6.

3.Reset error code and open a water tap to cycle the heater in an effort to purge air on new installations. Cycling hot water tap on and off multiple times may be necessary. If heater still faults with EA error code, have a licensed gas technician properly purge air out of the gas line leading to the water heater.

4.Check three wire connections to ignition group on the lower front of the heat exchanger are secure.

5.Check gas pressure, see chapter 3.12, page 27.

6.Check venting specifications are met. Improper venting may cause premature failure of the flame sensor rod.

7.Check that the minimum power fan speed has been adjusted to the proper value. See page 18.

8.Observe inside the viewing window of the heat exchanger when a hot water tap is opened. Sparking should be followed by a steady blue flame. If flame is unstable or yellow with proper gas pressure, confirm CO2 readings per section 6.4.

Ionization failure during operation.

1.

Check gas type, see Fig. 2, page 6.

 

2.

Check three wire connections to ignition group on the lower

 

front of the heat exchanger are secure.

 

3.

Check venting specifications are met. Improper venting may

 

cause unstable burner flames and loss of flame ionization.

 

4. Check that the minimum power fan speed has been adjusted to

 

the proper value. See page 18.

 

5.

Check gas pressure, see section 3.12, page 27.

 

6.

Check and adjust CO2 readings, see section 6.4, page 33.

 

 

 

Ionization error at standby.

1.

Loose connection to the flame ionization rod. Verify that the

 

thinner wire leading from the control unit is securely connected to

 

the flame sensor located on the lower front of the heat exchanger.

 

See Fig. 64, page 49.

 

2.

Flame ionization rod or control unit may be damaged. Contact

 

Bosch Water Heating for further instruction.

 

 

Gas leakage error, gas valve circuit

1. Disconnect power supply cord and check wire connections on

not closing properly.

gas valve and the two connectors on the control board.

 

2. Flow water out of a hot water tap above the minimum activation

 

point of 0.65 GPM. Measure voltage at the gas valve wire plug

 

connection. The voltage should measure 24VDC between the left

 

pair of wires and 24VDC between the right pair of wires when the

 

unit is operating. If voltage is not proper, contact Bosch Water

 

Heating for further instruction.

 

3. Gas valve may be defective, contact Bosch Water Heating for

 

further instruction.

Table 20

* By installer or service technician only.

44

6 720 608 542

Image 44
Contents Intended for variable flow applications What to do if you smell gasIndex For your safety Features Appliance detailsSpecifications Technical data GWH 2700 ES is not approved or designed for To remove combustion cover service onlyUnpacking the heater General rules to follow for safe operation VentingDimensions and Minimum installation clearances DimensionsInstallation instructions Tools required for installationIntroduction VentingFittings or Piping Equivalent Feet Installation instructions Horizontal venting systems onlyVenting Specifications Installation instructions Condensate drain requirements Twin pipe termination clearancesMinimum combustion air and exhaust pipe length Maximum combustion air and exhaust pipe lengthCanadian installations1 Installations2 Canadian installations1 Horizontal twin pipe penetration Vertical venting installation twin pipe penetra- tion Vent connectionsInstallation instructions Condensate drain installation Venting Flex ProTech Heat FabTotal equivalent vent length calculation ExhaustIntake ExampleLevel Vent length1 Speed P2 Adjusting minimum power fan speed P2Adjusting maximum power fan speed P1 Installation instructions Combustion air requirements Twin pipe and Concentric pipeMounting installation Proper location for installing your heaterHeater placement and clearances Gas piping & connections GAS Line Sizing For Natural GAS Water connections Water qualityDomestic hot water recirculation GWHConnecting manometer Measuring gas pressureStatic Pressure Test Operating Pressure TestPosition of the fuses in control unit Electrical power supplyElectrical connections Operation instructions LCD Display functionsTemperature selection For your safety read before operating your water heaterPower Use of optional remote control Accessory part no. TSTAT2 Reset buttonOperation Program buttonMaintenance and service Annual maintenance table Every yearAnnual maintenance Winterizing for seasonal useMineral scale build-up Adjusting CO2 carbon dioxideDescaling using a pump Measuring CO2 combustion cover must be installed Adjusting CO2Returning to Service Once Gas Pressure is adequateFinal Readings % 3.0 % 60 ppmComment Program Description Factory DefaultProgram values Control board diagnostics Diagnostic menuTroubleshooting TroubleshootingWater is too hot Water is not hot enoughNoisy burner/heater during operation Hot water temperature fluctuates at tapLow water flow/pressure Lack of adequate gas pressure. Inadequate gas Problem solving Error code diagnosticsProblem solving Display Cause Solution Venting may cause this failureOver-temperature detected by No flame ionization detected with Electrical diagram Electrical diagramSensor resistance charts Back Flow characteristics GWH 2700 ES Functional scheme Functional schemeInterior components Interior components diagram and parts listInterior components diagram and parts list Appliance overview Description Reference Components diagramGroup Interior components diagram and parts list Group 1211 6720608158-73.1AL Interior components diagram and parts list Group 708 300 Protecting the environment Protecting the environmentPacking ComponentsLimited Warranty Limited Warranty 6720608542