Specifications
Power Supply | Dedicated 120 VAC, 60 Hz., 15 A |
Current Draw | Less than 5 Amps |
Gas Supply Connection INDUCED DRAFT MODELS: 1" NPT Minimum conncection to gas valve. Schedule 40 black iron pipe recommended for all models.
Approved Gas Type
Gas Pressure (Nat. & L.P.)
Venting System
Minimum Clearance for Servicing
Maximum Water Supply Pressure
Thermostat Sensor(s)
Control Board
Control Display
Natural or Propane. Gas supply must match the gas type listed on the water heater rating label.
Manifold Pressure: 4.5" w.c. natural gas, 10.0" w.c. L.P.
Gas Supply Pressure: At least 1" above manifold pressure with water heater operating, 14" w.c. maximum
PDV-S MODELS:
Power vented through either 3" or 4" diameter PVC, CPVC, or ABS pipe for 150,000 or 199,999 Btu/hr. models, 4" only for 250,000 Btu/hr. models. Refer to the installation instruction manual for further information on venting lengths and installation requirements.
PDV-T MODELS:
Power vented through
INDUCED DRAFT MODELS:
Connect 8” vent to blower vent collar for venting through a chimney or type B vent only. Vertical venting only.
30" Front Clearance, 16" Top, 2" Sides and Rear
150 PSI
Redundant thermister with 11,900 + or - 0.5% ohms resistance at 70 deg. F. Sensor inside well for lower sensor.
Honeywell Integrated Control Board for Temperature Control, Induced Draft Blower, and Ignition Control Functions. Operates on 24 volts AC current from transformer. Single sensor boards for
Honeywell LCD Control Display with Temperature Setpoint, Format, and Error Code Display in User Mode, Diagnostic Functions in Service Mode. Communicates with Control Board. 24 volts AC. Same control display used on all models.
Transformer
Pilot
Induced Draft Blower
120 VAC Primary, 24 VAC Secondary, 40 VA
Intermittent Pilot with Spark Electrode and Flame Sensor monitored by Control Board
5