Bradford-White Corp PDV80S250, D80T725, D65T625, PDV100S150, PDV100S250, PDV100T360 Specifications

Page 5

Specifications

Power Supply

Dedicated 120 VAC, 60 Hz., 15 A

Current Draw

Less than 5 Amps

PDV-S & PDV-T MODELS: 3/4" NPT Minimum connection to gas valve.

Gas Supply Connection INDUCED DRAFT MODELS: 1" NPT Minimum conncection to gas valve. Schedule 40 black iron pipe recommended for all models.

Approved Gas Type

Gas Pressure (Nat. & L.P.)

Venting System

Minimum Clearance for Servicing

Maximum Water Supply Pressure

Thermostat Sensor(s)

Control Board

Control Display

Natural or Propane. Gas supply must match the gas type listed on the water heater rating label.

Manifold Pressure: 4.5" w.c. natural gas, 10.0" w.c. L.P.

Gas Supply Pressure: At least 1" above manifold pressure with water heater operating, 14" w.c. maximum

PDV-S MODELS:

Power vented through either 3" or 4" diameter PVC, CPVC, or ABS pipe for 150,000 or 199,999 Btu/hr. models, 4" only for 250,000 Btu/hr. models. Refer to the installation instruction manual for further information on venting lengths and installation requirements.

PDV-T MODELS:

Power vented through Co-axial Venting (pipe inside a pipe) - Combustion air enters from the outside the building through an outer pipe (200mm diam.) and exhausts flue products through the inside pipe (130mm diam.). Refer to the installation instruction manual for further information on venting lengths and installation requirements.

INDUCED DRAFT MODELS:

Connect 8” vent to blower vent collar for venting through a chimney or type B vent only. Vertical venting only.

30" Front Clearance, 16" Top, 2" Sides and Rear

150 PSI

Redundant thermister with 11,900 + or - 0.5% ohms resistance at 70 deg. F. Sensor inside well for lower sensor. PDV-T model series and Induced Draft models also use an upper sensor (dual sensors for these models).

Honeywell Integrated Control Board for Temperature Control, Induced Draft Blower, and Ignition Control Functions. Operates on 24 volts AC current from transformer. Single sensor boards for PDV-S models and dual sensor boards for PDV-T models and Induced Draft models.

Honeywell LCD Control Display with Temperature Setpoint, Format, and Error Code Display in User Mode, Diagnostic Functions in Service Mode. Communicates with Control Board. 24 volts AC. Same control display used on all models.

Transformer

Pilot

Induced Draft Blower

120 VAC Primary, 24 VAC Secondary, 40 VA

Intermittent Pilot with Spark Electrode and Flame Sensor monitored by Control Board

PDV-S MODELS: 115 VAC, 60 Hz., 4.3 Amps.

PDV-T MODELS AND D80T725, D65T625: 115 VAC, 60 Hz., 3.6 Amps.

5

Image 5
Contents Service Manual Table of Contents Features of PDV-T Model Series Features of PDV-S Model SeriesFeatures of Induced Draft Models Features of Honeywell Integrated Controls SystemTools Required for Service Specifications Sequence of Operation Verify Primary and Secondary voltage at the control board TroubleshootingError code #63 on display. See Main Burner short Pressing Select button will change display to next mode Max Setpoint Display/Change Setpoint Display/Change Software Version Display only SET Display of Water Temperature ExitingSELECTServiceSETModeTo Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature SetpointSetpoint Flashes Idle Status Operational Select SET Error Code History Error Codes and Error History DisplayTo view previous error codes ExitingSELECTServiceSETMode Error Code Definitions Resetting Error Codes in Hard Lockout Condition Unplug or disconnect electrical power to the water heater Service Procedure PDV24-IService Procedure PDV24-I Lower Sensor Upper SensorService Procedure PDV23-II Service Procedure PDV24-II Service Procedure PDV24-II Condition Service Procedure PDV24-IIICondition Error code 57 Flame Rod Shorted To Ground Probe To control board Service Procedure PDV24-IVCorrect improper venting condition Manifold Pressure Port PDV S&T Models Service Procedure PDV24-VPDV S&T Models PDV S&T Models Main Burner Removal Induced Draft ModelsPilot Burner Inspection Pilot Burner RemovalRemove lower sensor Service Procedure PDV24-VIControl board replacement Service Procedure PDV24-VII Service Procedure PDV24-VIII PDV-S PDV S PDV-S PDV-T PDV T PDV-T Induced Draft Models Induced Draft Models Induced Draft Models CO2 BTU/HECO GFI