Bradford-White Corp IGI-180R, IGI-180C instruction manual Exceptions for Installations

Page 22

Vent terminals must terminate at least 3 feet (0.9 m) above any forced air inlet located within 10 feet

(3.1 m). This provision does not apply to:

1.The combustion air intake of a direct vent appliance or the circulating air inlet and flue gas discharge of listed outdoor appliances.

2.The exhaust vent terminal must be installed with at least 12 inches (30 cm) of clearance from any air opening into a building.

3.The bottom of the exhaust vent and combustion air intake terminals must be located at least 12 inches (30 cm) above grade and above the anticipated snow level.

4.Must be installed at least 3 feet (0.9 m) from any gas meter, gas valve or other gas regulating equipment.

5.Must be installed in a location where it will not be blocked by snow.

EXCEPTIONS FOR INSTALLATIONS

The vent terminal must not terminate:

1.Directly above a paved sidewalk or paved driveway which is located between two single-family dwellings and serves both dwellings;

2.Less than 7 feet (2.1 m) above a paved sidewalk or a paved driveway located on public property;

3.Above a gas meter/regulator assembly within 3 feet (0.9 m) horizontally of the vertical centerline of the regulator;

4.Within 6 feet (1.8m) of any gas service regulator vent outlet;

5.Less than 1 foot (30.5 cm) above grade level and the anticipated snow level;

6.Within 12 inches (30.5 cm) of a window or door, which can be opened in any building, any non- mechanical air supply inlet to any building, or the combustion air inlet of any other appliance;

7.Underneath a veranda, porch or deck, unless:

The veranda, porch or deck is fully open on a minimum of two sides beneath the floor and

The distance between the top of the vent termination and the underside of the veranda, porch or deck is greater than 1 foot (30.5 cm).

The vent system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the National Fuel Gas Code, ANSI Z223.1.73.4e and 7.8a, b as follows:

1.Do not terminate the exhaust vent terminal over public area where condensate or vapor can cause nuisance or hazard.

2.For direct vent, the venting system shall terminate at least 1 foot (0.3 m) below, 1 foot (0.3 m) horizontally from or 1 foot (0.3 m) above any door, window, or gravity air inlet into building.

3.The manufacturer also recommends the vent system terminations not be installed closer than 1 foot (0.3 m) from an inside corner of an L shaped structure.

4.The horizontal distance between two vent terminals on the same wall shall be 1 foot (0.3 m), while the vertical distance between two terminals on the same wall shall be 5 feet (1.52 m).

5.The distance between two facing vent terminals shall be 4 feet (1.22 m)

6.The vent termination shall not be mounted directly above or within 3 (0.9 m) feet horizontally from an oil tank vent or gas meter to avoid potential freeze-up from condensation.

7.The vent shall terminate a minimum of 12 inches (30.5 cm) above expected snowfall level to prevent blockage of vent termination.

Vent pipes serving power vented appliances are classified by building codes as “vent connectors”. Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF WATER HEATER and CLEARANCES, and with National Fuel Gas Code and local codes.

22

Image 22
Contents IGI-180R and IGI-180C Model Series Section I Important Information Read CarefullyPage Page Table of Contents Min Section II SpecificationsMax. Flow Rate @ Degree Temperature Rise IGI-180C-5X First Hour 462 306 228 186 156 132 SupplyEVERHOT→ IGI Model Series Dimensions Cm, Front Features Section III General InformationSection IV Installation Instructions Do not Operate the Appliance Until the Leakage is CorrectedUnpacking Water Heater LocationRemove Carton Mount Water Heater on the WallWater Quality Lime Condition Warning SignalSection V Water Connections DescriptionPage Recommended Piping for a Basic Installation Fig Recommended Piping for a Circulation System Fig Recommended Piping for Power Failure Freeze Protection Drain Solenoid Piping FigPage Pressure Relief Valve Section VI Venting VENT/AIR Intake Terminal Locations Direct Vent Terminal LocationExceptions for Installations Venting System Layout Venting System Installation Horizontal Direct Vent InstallationsHorizontal Direct Vent using standard vent kit components Page Vertical Vent Installations Dip Switch Settings Fig Never USE a Match or Open Flame for Testing Section VII GAS ConnectionsGAS Meter Size -NATURAL GAS only Initial Operation and Testing Installer onlyGAS Pressure Regulation Page Section Viii Electrical Connections Wiring Diagram Wiring Diagram Schematic Temperature Controls Residential ModelsPage Commercial Models Main Control for Commercial Models FigRemote Main Control Installation Optional Remote Control Wiring Connections Inside Water Heater Fig Initial Operation and Testing of Controls Installer onlySection IX Operating Instructions Sequence of OperationTo Turn OFF GAS to the Appliance Lighting Instructions For Your Safety Read Before OperatingManual Gas Valve Fig Turning OFF the Water Heater for AN Extended Period of Time Temperature Adjustment Main or Bath Control for Residential Models Fig Commercial Models See figureMain Control for Commercial Models Fig Approximate TIME/TEMPERATURE Relationships in Scalds ScaldingError Messages on Remote Temperature Control Display First AID for ScaldsSection X Maintenance Burner Flame Appearance Fig Lime Scale Flushing Diagram Fig Page Schematic Diagram of Internal Parts Section XI Parts List Exploded View Internal Components Exploded View Internal Components Exploded View Electrical Venting Components Number Description Quantity Number Description Quantity Description Quantity