5. Measure the gas pressures to see that these are within the specified limits below:

Supply Pressure:

Nat. Gas: Min.: 6”, Max.: 10.5” w.c.

 

L.P. Gas: Min.: 10”, Max.: 13.5” w.c.

Manifold Pressure:

Nat. Gas: 3.4” w.c. High Fire,

0.6” w.c. Low Fire

 

L.P. Gas: 5.1” w.c. High Fire,

0.9” w.c. Low Fire

6.Turn off the hot water faucets. Disconnect the electrical power to the water heater. Remove the pressure gauges and replace the plugs. Check for gas leaks around the plugs.

7.Replace the front control panel. Restore electrical power to the water heater.

NOTICE

If the gas supply pressure is below the specified value, check the gas piping to insure that it is the correct size for all the gas appliances on line. Check the supply pressure with all the gas appliances in operation. The manifold pressure will vary with the water flow rate. Several hot water faucets may need to be opened with the temperature control set on the highest setting in order to get maximum high fire manifold pressure. If the manifold pressure is below the specified value and there is sufficient water pressure and flow, be sure the inlet gas pressure is within the specified limits before attempting to adjust the manifold pressure.

21

Image 21
Contents IGE-199R and IGE-199C Model Series Read Carefully Section I Important InformationPage Do not Operate the Appliance Until the Leakage is Corrected Table of Contents IGE-199R-10X Section II SpecificationsEVERHOT→ IGE Model Series Dimensions Section III General Information FeaturesDo not Operate the Appliance Until the Leakage is Corrected Section IV Installation InstructionsWater Heater Location UnpackingReference Description Minimum Distance Inches cm Build Opening Clearances FigRemove Carton Mount Water Heater on the WallSection V Water Connections Lime Condition Warning SignalWater Quality Instructions for ConnectionsPage Recommended Piping for a Basic Installation Drain Solenoid Piping Fig Recommended Piping for Power Failure Freeze ProtectionRecommended Piping for a Circulation System Page Pressure Relief Valve Section VI GAS Connections Never USE a Match or Open Flame for TestingInitial Operation and Testing Installer only GAS Meter Size -NATURALGAS onlyGAS Pressure Regulation Page Section VII Electrical Connections Wiring Diagram Wiring Diagram Schematic Residential Models Remote Temperature ControlsPage Commercial Models Initial Operation and Testing of Controls Installer only Control Wiring Connections Inside Water HeaterSection Viii Operating Instructions To Fill the Water HeaterSequence of Operation Lighting Instructions For Your Safety Read Before Operating To Turn OFF GAS to the ApplianceManual Gas Valve Fig Residential Models see Figure Turning OFF the Water Heater for AN Extended Period of TimeCommercial Models see Figure Main or Bath Control For Residential Models FigMain Control for Commercial Models Fig First AID for Scalds Approximate TIME/TEMPERATURE Relationships in ScaldsError Messages on Remote Temperature Control Display Section IX Maintenance Burner Flame Appearance Fig Page Lime Scale Flushing Diagram Fig Schematic Diagram of Internal Parts Section X Parts List Exploded View Internal Components Exploded View Internal Components Exploded View Electrical Parts List Anti-Frost Heater Clip