American Water Heater (A)BCG3 85T500-8N, (A)BCG3 85T500-8P Outdoor Air Through Two Vertical Ducts

Page 17

Outdoor Air Through Two Vertical Ducts

The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only.

Do not refer to these illustrations for the purpose of vent installation. See Venting Installation on page 15 for complete venting installation instructions.

When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.

Air From Other Indoor Spaces

Figure 17

The confined space shall be provided with two permanent vertical ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The vertical ducts shall communicate directly with the outdoors. See Figure 17.

Each duct opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.

Figure 18

The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 18.

Each opening shall communicate directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space.

Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/hr (2200 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).

17

Image 17
Contents Commercial gas water heaters Table Of Contents Asme CRN Safe Installation, Use and ServiceFire and Explosion Hazard General Safety InformationHydrogen Gas Flammable PrecautionsGrounding Instructions Qualifications IntroductionAbbreviations Used Features and components 2 NPT Installation considerationsRough In Dimensions Model Right Left Back Ceiling Side Locating the Water HeaterClearances Insulation Blanket Installation On Combustible FlooringHard Water Circulation PumpsNatural Gas Installations Propane InstallationsHigh Altitude Installations Power Supply Installation RequirementsWater Temperature Controland Mixing Valves Gas Pressure RequirementsDishwashing Machines Temperature-Pressure Relief ValveClosed Water Systems Thermal Expansion Air Requirements Contaminated AirUnconfined Space VENTING InstallationConfined Space Vent AdapterFresh Air Openings For Confined Spaces Multiple Heater ManifoldOutdoor Air Through Two Openings Outdoor Air Through One OpeningAir From Other Indoor Spaces Outdoor Air Through Two Vertical DuctsMultiple Gas Fired Tank-Type Heaters Technical Data VentingValve Discharge Pipe Water heater installationWater Line Connections Code Restrictions Installation Diagrams Top Inlet/Outlet UsageHeater Wiring Purging Gas PipingGas Pressure Regulator GAS Supply Pipe Length FeetFilling AdjustmentsGeneral Lighting & Operation Label For Your Safety Read Before OperatingIgniter Assembly Check the Igniter AssemblyCheck Venting Main BurnerRemote Storage Tank Temperature Control MAINTENANCETemperature-Pressure Relief Valve Test Checking the InputAnode Rod Inspection Hot Water OdorDraining and Flushing To Drain the Water Heater Storage TankDeliming Solvents Tank Cleanout ProcedureDeliming Using Flo-Jug Method Chemical Hazard For your information AIR in HOT Water Faucets High Water Temperature Shut OFF SystemSequence of Operation Flow Chart Complaint Cause Remedy User Service Agent Operational checklistWater Piping DiagramsTemperature & Pressure Temperature & Pressure Relief Valve Circulating Pump Multi Flue 2 Units Multi Flue 2 Units with Vertical Storage Tank Multi Flue 2 Units with Vertical Storage Tank Return from Multi Flue 2 Units TWO Temperature Multi Flue 2 Units with Booster TWO Temperature MULTI-FLUE 3 Units MULTI-FLUE 3 Units with Vertical Storage Tank MULTI-FLUE 3 Units with Horizontal Storage Tank Multi Flue Flue 4 Units MULTI-FLUE 4 Units with Vertical Storage Tank MULTI-FLUE 4 Units with Horizontal Storage Tank Manifold Kits For Technical ASSISTANCE, Service or Warranty Information