American Water Heater (A)BCG3 85T500-8N Water heater installation, Water Line Connections

Page 19

water heater installation

Water Line Connections

This manual provides detailed installation diagrams (see pages 34-48 of this manual) for typical methods of application for the water heater(s).

Water (potable) Heating And Space Heating

1.All piping components connected to this unit for space heating applications shall be suitable for use with potable water.

2.Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.

3.This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance.

4.When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to installation diagrams on pages 34-48 of this manual for suggested piping arrangements.

Thermometers (not Supplied)

Thermometers should be obtained and field installed as shown in the installation diagrams.

Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply.

Water Piping Diagrams

This manual provides detailed water piping diagrams for typical methods of application for the water heaters, see Water Piping Diagrams beginning on page 34.

The water heater may be installed by itself, or with a separate storage tank, on both single and two-temperature systems. When used with a separate storage tank, the circulation may be either by gravity or by means of a circulating pump. When a circulating pump is used it is important to note that the flow rate should be slow so that there will be a minimum of turbulence inside the heater.

Adjust flow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle flow on the suction side of a pump.

T&P Valve Discharge Pipe

Explosion Hazard

Temperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code.

Properly sized temperature- pressure relief valve must be installed in opening provided.

Can result in overheating and excessive tank pressure.

Can cause serious injury or death.

This water heater is provided with a properly rated/sized and certified combination temperature - pressure (T&P) relief valve by the manufacturer. See Temperature-Pressure Relief Valve on pages 13-14 for information on replacement and other requirements.

CAUTION

Water Damage Hazard

Temperature-Pressure Relief Valve discharge pipe must terminate at adequate drain.

Install a discharge pipe between the T&P valve discharge opening and a suitable floor drain. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

T&P Valve Discharge Pipe Requirements:

Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall not be exposed to freezing temperatures.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both the Temperature-Pressure Relief Valve and the discharge pipe.

Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.

Shall not have any valve or other obstruction between the relief valve and the drain.

The type, size and location of the relief valves must be in accordance with local codes. The locations of the relief valves shown in the installation diagrams are typical. See pages 34-48. The heater has a factory installed high temperature limit switch and temperature and pressure relief valve.

Cold water lines to heater should be installed as shown in order to minimize gravity circulation of hot water to building cold water lines.

A listed temperature and pressure relief valve of adequate capacity is installed on the heater. The locations shown in the installation diagrams on pages 34-48 are typical.

The discharge opening of the temperature and pressure relief valve must be piped to an open drain and should not be subject to freezing temperatures.

Install in accordance with all local codes.

19

Image 19
Contents Commercial gas water heaters Table Of Contents Asme CRN Safe Installation, Use and ServiceFire and Explosion Hazard General Safety InformationGrounding Instructions PrecautionsHydrogen Gas Flammable Abbreviations Used IntroductionQualifications Features and components Rough In Dimensions Installation considerations2 NPT Clearances Locating the Water HeaterModel Right Left Back Ceiling Side Circulation Pumps Installation On Combustible FlooringInsulation Blanket Hard WaterHigh Altitude Installations Propane InstallationsNatural Gas Installations Gas Pressure Requirements Installation RequirementsPower Supply Water Temperature Controland Mixing ValvesThermal Expansion Temperature-Pressure Relief ValveDishwashing Machines Closed Water SystemsAir Requirements Contaminated AirVent Adapter VENTING InstallationUnconfined Space Confined SpaceOutdoor Air Through One Opening Multiple Heater ManifoldFresh Air Openings For Confined Spaces Outdoor Air Through Two OpeningsAir From Other Indoor Spaces Outdoor Air Through Two Vertical DuctsMultiple Gas Fired Tank-Type Heaters Technical Data VentingWater Line Connections Water heater installationValve Discharge Pipe Code Restrictions Installation Diagrams Top Inlet/Outlet UsageHeater Wiring GAS Supply Pipe Length Feet Gas PipingPurging Gas Pressure RegulatorGeneral AdjustmentsFilling Lighting & Operation Label For Your Safety Read Before OperatingMain Burner Check the Igniter AssemblyIgniter Assembly Check VentingChecking the Input MAINTENANCERemote Storage Tank Temperature Control Temperature-Pressure Relief Valve TestTo Drain the Water Heater Storage Tank Hot Water OdorAnode Rod Inspection Draining and FlushingDeliming Using Flo-Jug Method Tank Cleanout ProcedureDeliming Solvents Chemical Hazard For your information AIR in HOT Water Faucets High Water Temperature Shut OFF SystemSequence of Operation Flow Chart Complaint Cause Remedy User Service Agent Operational checklistWater Piping DiagramsTemperature & Pressure Temperature & Pressure Relief Valve Circulating Pump Multi Flue 2 Units Multi Flue 2 Units with Vertical Storage Tank Multi Flue 2 Units with Vertical Storage Tank Return from Multi Flue 2 Units TWO Temperature Multi Flue 2 Units with Booster TWO Temperature MULTI-FLUE 3 Units MULTI-FLUE 3 Units with Vertical Storage Tank MULTI-FLUE 3 Units with Horizontal Storage Tank Multi Flue Flue 4 Units MULTI-FLUE 4 Units with Vertical Storage Tank MULTI-FLUE 4 Units with Horizontal Storage Tank Manifold Kits For Technical ASSISTANCE, Service or Warranty Information

(A)BCG3 85T500-8N, (A)BCG3 85T500-8P specifications

American Water Heater has long been a trusted name in the industry, providing high-quality solutions for residential and commercial water heating needs. Among its impressive lineup of products, the (A)BCG3 85T500-8P and (A)BCG3 85T500-8N models stand out due to their outstanding efficiency, performance, and innovative technologies.

These water heaters are primarily classified as high-efficiency gas water heaters, designed to meet a variety of usage demands. With a robust design and advanced technological features, they cater to homes and businesses that require reliable and energy-efficient hot water solutions.

One of the most notable features of the (A)BCG3 85T500-8P and (A)BCG3 85T500-8N models is their remarkable thermal efficiency. They are engineered to optimize energy usage, which not only helps reduce utility bills but also minimizes environmental impacts. This energy efficiency is achieved through advanced insulation and heat exchange technologies that maintain water temperature with minimal energy expenditure.

Both models come equipped with a powerful gas burner that allows for rapid heating, making them ideal for high-demand scenarios. The innovative burner technology ensures even heat distribution, significantly reducing recovery time and ensuring that hot water is available whenever needed.

In terms of safety, American Water Heater has incorporated several features to protect users and the unit itself. These include safety shut-off valves and temperature control features that prevent overheating and provide peace of mind.

Durability is another hallmark of these models. Constructed with high-quality materials, they resist the wear and tear commonly associated with traditional water heaters. Furthermore, the design of the (A)BCG3 85T500-8P and (A)BCG3 85T500-8N emphasizes ease of maintenance, allowing for simpler servicing and reduced downtime.

Finally, both models are backed by American Water Heater's commitment to customer satisfaction, supported by comprehensive warranties and reliable customer service. This assurance adds value to their products, making them a preferred choice for consumers seeking efficient and dependable water heating solutions.

In conclusion, the (A)BCG3 85T500-8P and (A)BCG3 85T500-8N models exemplify American Water Heater’s dedication to innovation and efficiency, making them excellent options for anyone in need of advanced water heating technology.