is
3.6.5 Circulation pipe
3.7Water connections, Unvented
See (C) in the installation diagram (3.5 "Installation diagram").
If an immediate flow of hot water is required at
1.Fit a circulation pump (6) of the correct capacity for the length and resistance of the circulation system.
2.Fit a
3.Fit two stop valves for service purposes (4).
4.Connect the circulation pipe to the
Warning
The installation should be carried out by an authorised installation engineer, in compliance with general and local regulations (1.3 "Regulations").
3.7.1Cold water side
See (A) in the installation diagram (3.5 "Installation diagram").
1.Fit an approved stop valve (4) on the cold water side as required by applicable regulations (1.3 "Regulations").
2.The maximum working pressure of the appliance is 8 bar. Because the pressure in the water pipe at times can exceed 8 bar, you must fit an approved
3.Fit a
4.Fit an expansion valve (15) and connect the overflow side to an open wastewater pipe.
3.7.2Recirculation pipe
You can install a top to bottom circulation pump to prevent water stacking in the boiler.
1.Optional: depending on the
2.Fit a
3.Fit a stop valve (11).
3.7.3Hot water side
See (B) in the installation diagram (3.5 "Installation diagram").
Note
Insulating long hot water pipes will prevent unnecessary energy loss.
1.Optional: fit a temperature gauge (12) so you can check the temperature of the tap water.
2.Fit the T&P valve (3).
3.Fit a stop valve (11) in the hot water outlet pipe for servicing.
3.7.4Drain valve
1.Fit the standard drain valve (9) supplied with the appliance.
2.If applicable, fit a circulation pipe (3.6.5 "Circulation pipe").
If not, fit the blind threaded plug and gasket (C) supplied with the drain valve, as shown in the figure.
Instruction manual BFM | 25 |