A.O. Smith Water Heater Vent Pipe Size, Vent Connectors, Chimney Connection

Page 14

Align the legs of the draft hood with the slots provided. Insert the legs and secure the draft hood to the water heater's top with the four screws provided as shown in Figure 9. Do not alter the draft hood in any way. If you are replacing an existing water heater, be sure to use the draft hood supplied with this water heater.

Vent Pipe Size

It is important that you follow the guidelines in these instructions for sizing a vent pipe system. If a transition to a larger vent size is required, the vent transition connection must be made at the draft hood outlet.

Vent Connectors

1.Type B, Double wall, U.L. Listed Vent Pipe.

2.Single wall Vent Pipe.

Maintain the manufacturer's specified minimum clearance from combustible materials when using type B double wall vent pipe.

Vent connectors made of type B, double wall vent pipe material may pass through walls or partitions constructed of combustible material if the minimum listed clearance is maintained.

Maintain a six inch minimum clearance from all combustible materials when using single wall vent pipe. IMPORTANT: Single wall vent pipe cannot be used for water heaters located in attics and may not pass through attic spaces, crawl spaces or any confined or inaccessible location. A single wall metal vent connector cannot pass through any interior wall.

When installing a vent connector, please note the following (See Figures 10-12):

Install the vent connector avoiding unnecessary bends, which create resistance to the flow of vent gases.

Install without dips or sags with an upward slope of at least 1/4-inch per foot.

Joints must be fastened by sheet metal screws or other approved means. It must be supported to maintain clearances and prevent separation of joints and damage.

The length of the vent connector cannot exceed 75% of the vertical vent height.

The vent connector must be accessible for cleaning, inspection, and replacement.

Vent connectors cannot pass through any ceiling, floor, firewall, or fire partition.

It is recommended (but not mandatory) that a minimum 12 inches of vertical vent pipe be installed on the draft hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for obstructions, corrosion, and proper installation.

Chimney Connection

IMPORTANT: Before connecting a vent to a chimney, make sure the chimney passageway is clear and free of obstructions. The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces. Also consult local and state codes for proper chimney sizing and application or, in the absence of local and state codes, the "National Fuel Gas Code", ANSI Z223.1(NFPA 54)-current edition.

The connector must be installed above the extreme bottom of the chimney to prevent potentially blocking the flue gases.

The connector must be firmly attached and sealed to prevent it from falling out.

To aid in removing the connector, a thimble or slip joint may be used.

The connector must not extend beyond the inner edge of the chimney as it may restrict the space between it and the opposite wall of the chimney (Figure 10).

 

LISTED

LINED

 

CHIMNEY

 

!___

 

2 FT. MINIMUM ABOVE ANY OBJECT

3 FT. MINIMUM

WITHIN

10FT. HORIZONTALLY

SUPPORT

 

 

MAINTAIN

 

 

CLEARANCE*

 

 

t

 

DO NOT EXTEND

 

OF CHIMNEY

CONNECTOR

CHIMNEY TERMINATION VENT SYSTEM

FIGURE 10.

Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.

Vertical Exhaust Gas Vent

Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer's instructions and the terms of its listing.

It must be connected to the water heater's draft hood by a listed vent connector or by directly originating at the draft hood opening.

Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer's instructions.

Gas vents must be supported to prevent damage, joint separation, and maintain clearances to combustible materials (Figures 11 and 12).

IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.

An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent (Figure 12). Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation. CAUTION: DO NOT common vent this water heater with any power vented appliance.

Figures 10-12 are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the "National Fuel Gas Code", NFPA 54, ANSI Z223.1-current edition and the guidelines set forth by prevailing local codes.

14

Image 14
Contents Installer SmithWater Important Definitions Fire Hazard Improper installation and use may result in property damageFire or Explosion Harzard GET to Know Your Water Heater GAS Models Consumer Responsibilities Important Information About This Water HeaterConsumer Information Location Requirements Site LocationClearances and Accessibility Pmpey Damage HazardGas Requirements Gas Pressure TestingGas Pressure Gas PipingLP Gas Only Explosion HazardCarbon Monoxide Warning Unconfined SpaceConfined Space RoomLouvers and Grilles All Air from Inside the BuildingAll Air from Outdoors Draft Hood Installation PER OpenChimney Connection Vent ConnectorsVent Pipe Size Piping Installation MA,NTA,N\Propey Damage Hazard Closed System/Thermal ExpansionRelief Valve and Pipe Insulation Some Models Temperature and Pressure Relief Valve Explosion HarzardTemperature & Pressure Relief Valve Combination Space Heating/Potable Water SystemSolar Installation AIRGas Supply and Piping Vent Pipe SystemWater System Piping Lighting Instructions BeforeToturnoffgastoappliance ForyoursafetyreadbeforelightingChecking the Draft Burn HazardEmergency Shut Down Water Temperature RegulationBurner Flames White Rodgers ValvesCondensation Operational ConditionsProperty Damage Hazard Draining and Flushing Routine Preventive MaintenanceAnode Rod/Water Odor Manualrelief Replacement PartsRemoving the Burner from the Manifold/ Burner Assembly ThermalReplacing the Pilot/Pilot Tube Assembly Replacing the ThermocoupleCleaning the Combustion Chamber and Flame-arrestor Replacing the Manifold/Burner AssemblyExternal Inspection & Cleaning of the Base-Ring Filter Removing and Replacing the Gas Control Valve/Thermostat Testing the Igniter SystemPiezoelectric Igniter System FVlR System Operational Checklist Possible CausesProblem Thermostat set too highYES Repair Parts List Listed Parts Kits and Illustrations Page Limited Residential GAS Warranty Conditions and ExceptionsLimitation on Implied Warranties Claim ProcedureInstallation Information Disclaimers

Water Heater specifications

A.O. Smith is a renowned name in the water heating industry, celebrated for its commitment to innovation, quality, and efficiency. Their water heaters are designed to cater to a wide variety of needs, making them suitable for both residential and commercial applications. The main features of A.O. Smith water heaters are tailored to ensure optimal performance, convenience, and reliability.

One of the standout characteristics of A.O. Smith water heaters is their impressive energy efficiency. Many models are equipped with advanced insulation technologies that minimize heat loss, allowing users to save on energy bills while ensuring a consistent supply of hot water. The introduction of high-efficiency gas burners and electric heating elements enhances their energy utilization, which is reflected in their excellent Energy Factor ratings.

A.O. Smith also incorporates smart technology in its water heaters. Many models feature integrated Wi-Fi connectivity, allowing homeowners to monitor and control their water heating system remotely via a smartphone app. This capability enables users to adjust temperature settings, receive maintenance alerts, and track energy usage, providing a new level of convenience and control.

Durability is another hallmark of A.O. Smith water heaters. Constructed with high-quality materials, these units often feature a glass-lined tank that enhances corrosion resistance. Additionally, many models are designed with a robust anode rod that helps prevent rusting, extending the lifespan of the heater and ensuring dependable service for years to come.

Safety features are also a priority for A.O. Smith. Many water heaters come equipped with advanced safety mechanisms, such as automatic shut-off valves, temperature controls, and flame failure detection systems, ensuring safe operation and reducing the risk of accidents.

Different models are available to suit varying space requirements and preferences. A.O. Smith produces traditional tank water heaters as well as modern tankless options, which provide endless hot water on demand, making them ideal for homes needing high hot water consumption. Their versatility guarantees that customers can find the perfect solution tailored to their specific needs.

In conclusion, A.O. Smith water heaters represent a blend of innovation, efficiency, durability, and safety. With various models available that cater to different heating needs and preferences, A.O. Smith continues to remain a trusted choice for consumers seeking reliable hot water solutions.