Mitsubishi Electronics PAC-YG63MCA instruction manual Ch1

Page 12

(3) Turn on the power of this device.

Verify that the LED16 (CPU power on) and LED17 (M-NET power on) are lit.

(4) Set the time.

Set the current time from a system controller (G(B)-50A, TG-2000A) or a Maintenance Tool.

(5) Configure the settings of the system controller (G(B)-50A or TG-2000A).

Configure settings for the system controller (G(B)-50A or TG-2000A) such as the type of sensor to use and the measurement range.

The main items that should be set are shown below.

(a) When using Pt100 detection (only channel 1 can be used)

Ch

Setting

Setting with G(B)-50A or TG-2000A

 

 

 

 

 

 

 

Measurement category setting

Select temperature/humidity (Be sure to select

 

temperature.)

 

 

 

 

 

Ch1

Measurement range setting

Set the upper limit and lower limit values

(Set a range from -30°C [-22°F] to 60°C [140°F].)

 

 

 

 

 

 

Measurement correction

Input the measurement temperature correction value

 

(offset value)

 

 

 

 

 

(b) When using an analog input (4 to 20 mADC detection, 1 to 5 VDC detection, or 0 to 10VDC detection)

 

Ch

Setting

Setting with G(B)-50A or TG-2000A

 

 

 

 

 

 

 

 

 

 

Measurement category setting

Select the temperature/humidity

 

 

 

 

 

Ch1

Measurement range setting

Set the upper limit and lower limit values

 

 

 

 

 

 

Measurement correction

Input the measurement correction value (offset value)

 

 

 

 

 

 

Measurement category setting

Select the temperature/humidity

 

 

 

 

 

Ch2

Measurement range setting

Set the upper limit and lower limit values

 

 

 

 

 

 

Measurement correction

Input the measurement correction value (offset value)

 

 

 

 

(c) When using upper/lower limit alarm interlock output

 

 

 

 

 

 

Ch

Setting

Setting with G(B)-50A or TG-2000A

 

 

 

 

 

 

 

 

 

Ch1

Upper/lower limit alarm detection value and

Upper/lower limit alarm detection value and cancellation

 

cancellation value settings

value settings

 

 

 

Ch2

Upper/lower limit alarm detection value and

Upper/lower limit alarm detection value and cancellation

 

cancellation value settings

value settings

 

 

 

 

 

 

(6)Settings for the interlock function are performed from the Maintenance Tool. Perform settings such as interlock criteria for this device from Maintenance Tool. For details, refer to the operating manual for the Maintenance Tool.

11

Image 12
Contents AI controller Safety Precautions Include some slack in the power supply wiresParts List Specifications Device SpecificationsUsage External Dimensions Example of System ConfigurationInstallation Parts Purchased Separately Installation Instructions Wiring Instructions 7-1. Terminal Diagram Top of the control panel toTerminal block FireConnecting the Power and M-NET Transmission Lines NETConnecting the Sensors Connecting Alarm Setpoint Outputs Non-valtage Contacts Initial Settings Ch1 Dip Switch Functions Supported FunctionAlarm Setpoint Output and Error Displays Sensor and Communication Error DisplaysLED Display Designations System Operation Test Electromagnetic Compatibility Directive