Mitsubishi Electronics PAC-YG63MCA instruction manual Dip Switch Functions, Supported Function

Page 13

9Dip Switch Functions

SW

 

Supported

 

Function

 

OFF

ON

Remark

 

Channel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW01

1

 

 

Selection of the input to use

 

No

Yes

Specify whether to use the channel 1 input terminal.

 

 

 

 

 

 

4 to 20 mADC/

0 to 10 VDC

Set the type of analog input for channel 1 (1).

 

2

 

 

 

 

1 to 5 VDC

 

 

 

Selection of the analog input

detection

* This should also be set in accordance with the selection

 

 

 

 

detection

 

 

 

 

type (1)

 

 

of analog input type (2) (SW11-1 and 2).

 

 

 

 

 

 

Pt100

 

3

 

 

 

 

* The setting of SW01-2 is disabled when SW01-3 is ON.

 

 

 

 

 

detection

 

 

Channel 1

 

 

 

 

 

 

4

 

Unused

 

 

 

Set to OFF

 

5

 

 

Selection of upper/lower limit

No

Yes

Specify whether to use channel 1 upper/lower limit

 

 

 

alarm interlock output use

 

alarm interlock output.

 

 

 

 

 

 

 

 

6

 

 

Unused

 

 

 

Set to OFF

 

7

 

 

Unused

 

 

 

Set to OFF

 

8

 

 

Unused

 

 

 

Set to OFF

SW02

1

 

 

Selection of the input to use

 

No

Yes

Specify whether to use the channel 2 input terminal.

 

 

 

 

Selection of the analog input

4 to 20 mADC/

0 to 10 VDC

Set the type of analog input for channel 2 (1).

 

2

 

 

1 to 5 VDC

* This should also be set in accordance with the selection

 

 

 

type (1)

 

detection

 

 

 

 

 

detection

of analog input type (2) (SW12-1 and 2).

 

 

 

 

 

 

 

 

3

 

 

Unused

 

 

 

Set to OFF

 

4

Channel 2

 

Unused

 

 

 

Set to OFF

 

5

 

 

Selection of upper/lower limit

No

Yes

Specify whether to use channel 2 upper/lower limit

 

 

 

alarm interlock output use

 

alarm interlock output.

 

 

 

 

 

 

 

 

6

 

 

Unused

 

 

 

Set to OFF

 

7

 

 

Unused

 

 

 

Set to OFF

 

8

 

 

Unused

 

 

 

Set to OFF

SW03

1

Measurement

data backup interval

 

SW03-1

SW03-2

 

 

1-minute interval: (2 hours worth)

 

OFF

OFF

Set to back up measurement data to the fixed memory.

 

 

2-minute interval: (4 hours worth)

 

OFF

ON

 

2

5-minute interval: (10 hours worth)

 

ON

OFF

Excess past data will be erased.

 

10-minute interval: (20 hours worth)

 

ON

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Unused

 

 

 

 

Set to OFF

 

4

Unused

 

 

 

 

Set to OFF

 

5

Unused

 

 

 

 

Set to OFF

 

6

Unused

 

 

 

 

Set to OFF

 

7

Unused

 

 

 

 

Set to OFF

 

8

Unused

 

 

 

 

Set to OFF

SW06

 

 

 

 

 

(Address 10s)

An address from 01 to 50 can be set.

 

 

 

 

 

0 to 9 (decimal)

 

 

M-NET address

 

 

Set an address that is not the same as that of another

 

 

 

 

(Address 1s)

SW07

 

 

 

 

 

unit.

 

 

 

 

 

0 to 9 (decimal)

 

 

 

 

 

 

 

SW08

1

Unused

 

 

 

 

Set to OFF

 

2

Unused

 

 

 

 

Set to OFF

 

3

Unused

 

 

 

 

Set to OFF

 

4

Unused

 

 

 

 

Set to OFF

 

5

Unused

 

 

 

 

Set to OFF

 

6

Unused

 

 

 

 

Set to OFF

SW09

1

Unused

 

 

 

 

Set to OFF

 

2

Unused

 

 

 

 

Set to OFF

SW11

1

 

 

Selection of analog input type (2)

SW11-1

SW11-2

 

 

 

 

0 to 10 VDC detection

:

OFF

OFF

Set the type of analog input for channel 1 (2)

 

 

 

 

 

 

Channel 1

 

1 to 5 VDC detection

:

OFF

ON

 

 

 

*1: This setting is not necessary when SW01-3 is ON.

 

2

 

 

Setting not possible

:

ON

OFF

 

 

 

 

 

 

 

 

4 to 20 mADC detection:

ON

ON

 

SW12

1

 

 

Selection of analog input type (2)

SW12-1

SW12-2

 

 

 

 

0 to 10 VDC detection

:

OFF

OFF

 

 

 

Channel 2

 

 

 

 

 

1 to 5 VDC detection

:

OFF

ON

Set the type of analog input for channel 2 (2)

 

 

 

 

2

 

 

Setting not possible

:

ON

OFF

 

 

 

 

 

4 to 20 mADC detection:

ON

ON

 

Set the dip switches for function selection according to the system to be used.

At factory default, the SW01, SW02, SW03, SW08, and SW09 dipswitches are all set to OFF; the SW11 and SW12 dipswitches are both set to ON, and the M-NET address is set to 01.

Be sure to turn off the power before changing switch settings.

12

Image 13
Contents AI controller Include some slack in the power supply wires Safety PrecautionsSpecifications Device Specifications Parts ListUsage Example of System Configuration External DimensionsInstallation Parts Purchased Separately Installation Instructions Top of the control panel to Wiring Instructions 7-1. Terminal DiagramTerminal block FireNET Connecting the Power and M-NET Transmission LinesConnecting the Sensors Connecting Alarm Setpoint Outputs Non-valtage Contacts Initial Settings Ch1 Supported Function Dip Switch FunctionsSensor and Communication Error Displays Alarm Setpoint Output and Error DisplaysLED Display Designations System Operation Test Electromagnetic Compatibility Directive