Mitsubishi Electronics PAC-YG63MCA instruction manual Connecting the Sensors

Page 9

7-3. Connecting the Sensors

For channel 1, select one of the following four types: Pt100 detection, 4 to 20 mADC, 1 to 5 VDC, or 0 to 10 VDC analog input.

For channel 2, select one of the following three types: 4 to 20 mADC, 1 to 5 VDC, or 0 to 10 VDC analog input.

The wire length depends on the specifications of the sensor. However, since the use of long wires makes the device susceptible to noise, using wires shorter than 12 m (39.4 ft) is recommended. Use a shielded line for the sensor line and connect to the FG terminal on this unit or the FG terminal on the control panel.

(1)Channel 1 Pt100 Input

To use these, various settings need to be configured. Refer to "8. Initial Settings".

B / A / B

 

CN10

Device side

 

 

 

 

Field

B

A

B

Connections

 

 

 

 

 

 

 

Pt100 (3-wire system)

Caution:

Use a 3-wire system for Pt100.

A/B polarity is important for Pt100.

Be sure to match the polarity when using Pt100.

Do not install the sensor input line parallel to or near the M-NET transmission line or power line.

Also avoid loop wiring.

Furthermore, confirm the precautions for the sensor.

Strip 12±1 mm (15/32 ±1/32 in) of the wire coating and insert firmly into the terminal.

Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.

Perform wiring so that the terminal block is not strained.

If strained, use a wire guide or junction terminal to alleviate the stress on the terminal block.

(2) Channel 1 (Channel 2) Analog Input (4 to 20 mADC, 1 to 5 VDC, 0 to 10 VDC)

To use these, various settings need to be configured. Refer to "8. Initial Settings".

(a)When 1 to 5 VDC, 0 to 10 VDC, or 4 to 20 mADC (type for which power is supplied to the sensor) is connected

(b)When 4 to 20 mADC (type for which power is supplied to the signal line) is connected

CN05

(CN08)

Device side

CN05

(CN08)

Field

Connections

Device side

Field

Connections

Power supply

Sensor

Power supply

Sensor

Caution:

Select a power supply that is suitable for the sensor to be used.

Do not install the sensor input line parallel to or near the M-NET transmission line or power line. Also avoid loop wiring. Furthermore, confirm the precautions for the sensor.

Strip 12±1 mm (15/32 ±1/32 in) of the wire coating and insert firmly into the terminal.

Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.

Perform wiring so that the terminal block is not strained.

If strained, use a wire guide or junction terminal to alleviate the stress on the terminal block.

8

Image 9
Contents AI controller Include some slack in the power supply wires Safety PrecautionsParts List Specifications Device SpecificationsUsage Example of System Configuration External DimensionsInstallation Parts Purchased Separately Installation Instructions Top of the control panel to Wiring Instructions 7-1. Terminal DiagramTerminal block FireNET Connecting the Power and M-NET Transmission LinesConnecting the Sensors Connecting Alarm Setpoint Outputs Non-valtage Contacts Initial Settings Ch1 Supported Function Dip Switch FunctionsAlarm Setpoint Output and Error Displays Sensor and Communication Error DisplaysLED Display Designations System Operation Test Electromagnetic Compatibility Directive