Mitsubishi Electronics PAC-YG63MCA instruction manual Installation Instructions

Page 6

6-2. Installation Instructions

The AI controller PAC-YG63MCA does not have a waterproof structure.

Be sure to install the AI controller inside a control panel that is located indoors.

Prepare a control panel capable of storing this device such as the one shown in the figure. (Install the device in a control panel strong enough to withstand a weight of 0.6 kg [13/8 lb].)

This device can be installed horizontally, or as shown below, vertically. The following diagram also provides a rough estimate of how much space is required around the installation.

 

100

 

(315/16)

100

100

(315/16)

(315/16)

 

100

 

(315/16)

Size of the device: 200 (W) × 120 (H) × 45 (D) mm/ 77/8 (W) × 43/4 (H) × 125/32 (D) in

Unit: mm (in)

Note: The space shown above does not include space for peripherals. Additionally, the amount of space necessary varies according to the functions that are used and the wiring method. Secure enough space appropriate for the type of installation.

(1)Fix the top of this device to the control panel at two points by loosely tightening the screws (M4) that were procured locally. Fix the bottom in place with two screws and then tighten all four of the screws.

Screw pitch

150 (529/32)

110 (411/32)

Unit: mm (in)

(2)To remove the cover, as shown in the figure, remove the two screws for fixing the cover in place and then remove the cover by unhooking the upper hook section from the lower case. To attach the cover, hook the upper hook section on the lower case and then fix the cover in place with the two screws that were removed.

Hooks

Screws for fixing the cover

Note: Two hooks are located on the upper section of the cover.

5

Image 6
Contents AI controller Safety Precautions Include some slack in the power supply wiresParts List Specifications Device SpecificationsUsage External Dimensions Example of System ConfigurationInstallation Parts Purchased Separately Installation Instructions Terminal block Wiring Instructions 7-1. Terminal DiagramTop of the control panel to FireConnecting the Power and M-NET Transmission Lines NETConnecting the Sensors Connecting Alarm Setpoint Outputs Non-valtage Contacts Initial Settings Ch1 Dip Switch Functions Supported FunctionAlarm Setpoint Output and Error Displays Sensor and Communication Error DisplaysLED Display Designations System Operation Test Electromagnetic Compatibility Directive