Mitsubishi Electronics PAC-YG63MCA Usage, Parts List, Specifications Device Specifications

Page 3

2Usage

The AI controller measures temperature and humidity; it also has an alarm capability if the measurement data exceeds defined setpoints. Historical measurement data can be displayed via only the G(B)-50A Web browser and TG-2000A. Temperature and humidity cannot be displayed on the G-50A LCD.

Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit.

The AI controller also features a function that interlocks M-NET devices for indoor units, etc. set in advance and performs settings such as temperature control and operation/stoppage using measurement data values.

Caution: Usage Restrictions

Mitsubishi Electric does not take financial responsibility for damages caused by issues beyond our control or special circumstances (predicable or unpredictable); and secondary or accidental damages, and damages to other objects. We also do not take financial responsibility for opportunities lost as a result of device failure, or electrical power failure at the end- user site.

Mitsubishi Electric does not take financial responsibility caused by end-users' requests including, but not limited to, device testing, startup, readjustment and replacement.

Do not use this device in disaster prevention security or "critical to life" applications.

3Parts List

• The following parts should be included in your shipment:

Number

Part Name

Quantity

 

 

 

1

AI controller

1

2

Installation/instruction manual (this document)

1

*In addition to the parts listed above, see your local Mitsubishi Electric dealer to purchase the other parts necessary to operate this device (Refer to section 6-1). Furthermore, depending on the application, other Mitsubishi Electric parts may be required.

For details, refer to "6. Installation".

4Specifications

4-1. Device Specifications

Item

Power

Supply

Interface

Interlock

Function

Environment Conditions

Dimensions

Weight

Time Backup

During Power

Failure

Installation Environment

Description

24 VDC±10%: 5 W

 

 

 

 

 

Screw terminal

 

 

 

 

 

block (M3) (*5)

 

 

 

 

 

 

 

 

 

M-NET communication

17 to 30 VDC (*1)

 

 

Screw terminal

 

 

block (M3) (*5)

 

 

 

 

 

 

 

 

 

 

Ch

 

Sensor

Measurement

 

Measurement

 

Measurement error

External

 

 

target

 

range

 

connection method

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pt100

 

 

-30 to 60°C

 

±0.3%FS ±0.1°C (0.18°F)

Screwless terminal

 

 

 

Temperature

 

 

(*3)

 

 

(3-wire system)

 

[-22 to 140°F]

 

block (3 poles)

 

 

 

 

 

[at 25°C (77°F)]

 

Ch1

 

 

 

 

 

 

 

Input

Analog

4 to 20 mADC

 

 

 

 

±0.5%FS ±0.1°C (0.18°F)

 

 

 

Temperature/

 

(Set by system

 

(*3)

Screwless terminal

 

 

 

1 to 5 VDC

 

 

 

 

 

humidity

 

controller)

 

±0.5%FS ±0.1%RH

block (2 poles)

 

 

 

0 to 10 VDC

 

 

 

 

[at 25°C (77°F)]

 

 

 

Analog

4 to 20 mADC

 

 

 

 

±0.5%FS ±0.1°C (0.18°F)

 

 

 

 

Temperature/

 

(Set by system

 

(*3)

Screwless terminal

 

Ch2

 

1 to 5 VDC

 

 

 

 

humidity

 

controller)

 

±0.5%FS ±0.1%RH

block (2 poles)

(*2)

 

 

0 to 10 VDC

 

 

 

 

[at 25°C (77°F)]

 

Output

Upper/lower limit

 

Applied load

 

 

 

 

MIN: 5 VDC, 2 mW

block (M3.5) (*5)

(non-voltage contact)

 

 

alarm interlock output

 

MAX: 24 VDC, 5 W

Screw terminal

 

 

 

 

 

 

 

 

 

 

 

 

* AC loads cannot be connected.

 

Interlock M-NET devices according to measurement data values. (*4)

 

Temperature

 

Operating temperature range

 

0 to 40°C [32°F to 104°F]

 

 

 

 

 

Storage temperature range

 

-20 to 60°C [-4°F to 140°F]

 

 

 

 

 

 

 

Humidity

 

 

30 to 90%RH (no condensation)

 

 

 

200 (W) × 120 (H) × 45 (D) mm / 77/8 (W) × 43/4 (H) × 125/32 (D) in

0.6 kg / 13/8 lb

In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week. (The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)

Inside a control panel (indoors)

* Use this product in a hotel, a business office environment or similar environment.

*1: Supply electric power from a power supply unit for the transmission line or an outdoor unit. Furthermore, the power consumption factor of the M- NET circuitry of this unit is "1/4" (equivalent to one ME Remote Controller).

*2: Configure the dip switch settings for the analog input method to use while referring to "9. Dip Switch Functions".

*3: The measurement error for the system includes the measurement error for this unit, sensor, and wiring. a%FS (full scale) = a% × ([measurement range's upper limit value] - [lower limit value])

*4: Settings for the interlock function are performed from the Maintenance Tool. For details, refer to the operation manual for the Maintenance Tool.

*5: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread). The number indicates the screw diameter (mm).

2

Image 3
Contents AI controller Include some slack in the power supply wires Safety PrecautionsParts List Specifications Device SpecificationsUsage Example of System Configuration External DimensionsInstallation Parts Purchased Separately Installation Instructions Fire Wiring Instructions 7-1. Terminal DiagramTop of the control panel to Terminal blockNET Connecting the Power and M-NET Transmission LinesConnecting the Sensors Connecting Alarm Setpoint Outputs Non-valtage Contacts Initial Settings Ch1 Supported Function Dip Switch FunctionsAlarm Setpoint Output and Error Displays Sensor and Communication Error DisplaysLED Display Designations System Operation Test Electromagnetic Compatibility Directive