Mitsubishi Electronics PAC-YG63MCA instruction manual Installation Parts Purchased Separately

Page 5

6Installation

6-1. Parts Purchased Separately

Prepare the following parts to install this device.

Required Part

Specification

 

 

 

 

Unit fixing screws

M4 screw × 4 (* M4: ISO metric screw thread)

 

 

 

Commercially available power source: 24 VDC±10% 0.2 A (Minimum loading), SELV circuit, power line with

 

grounding terminal

 

Ripple noise: Lower than 200 mVp-p

Power supply for this

Compatible specification

device

Authorized or CE marked products.

 

Subject to regulations: - IEC60950 (or EN60950)

 

- CISPR22/24 (or EN55022/24)

 

- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)

 

 

Power supply for

A separate power supply for sensors may be required.

In the case of 24 VDC voltage, the capacity of the power supply for this unit can be increased so that the

sensors

power supply can be shared.

 

 

 

Power line

Use a sheathed vinyl cord or cable.

At least 0.75 mm² (AWG18)

 

 

 

 

Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or

 

equivalent.

M-NET transmission

• CPEV Φ1.2 mm to Φ1.6 mm • CVVS 1.25 mm² to 2 mm² (AWG 16 to 14)

* CPEV: PE insulated PVC jacketed shielded communication cable

line

* CVVS: PVC insulated PVC jacketed shielded control cable

 

PE: Polyethylene PVC: Polyvinyl chloride

 

Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately

 

purchased power supply unit for the transmission line.

 

 

 

Shows the size of the electric wire (copper wire) that is adapted to the terminal block of this device. Refer

 

to the usage and cautionary items of the sensor when performing settings. However, use a line with shielded

Signal lines

line.

(Sensor input lines)

Electric wire size ···· (1) Solid wire: Φ0.65 mm (AWG21) - Φ1.2 mm (AWG16)

 

(2) Stranded wire: 0.75 mm² (AWG18) - 1.25 mm² (AWG16)

 

Single strand: At least Φ0.18 mm

[Parts to be Purchased Separately]

Name

Model

Application

 

Remark

 

 

 

 

 

 

 

 

 

 

Power supply unit

PAC-SC50KUA

Power supply to the M-NET transmission line

This is not required when power is to be

supplied from an outdoor unit.

[Commercially available parts]

 

 

 

 

 

 

 

 

Part

 

Use

 

Remark

 

 

 

 

 

 

External 24 VDC

Supplies power to the AI controller.

Refer to "Power supply for this device" and "Power

power source

 

 

supply for sensors" in "Required Part" above for the

 

 

 

capacity of the power supply.

 

 

 

Sensor

Measures temperature and humidity.

Temperature sensor (PAC-SE40TSA) cannot be

 

 

 

connected.

 

 

 

 

 

4

Image 5
Contents AI controller Include some slack in the power supply wires Safety PrecautionsUsage Parts ListSpecifications Device Specifications Example of System Configuration External DimensionsInstallation Parts Purchased Separately Installation Instructions Top of the control panel to Wiring Instructions 7-1. Terminal DiagramTerminal block FireNET Connecting the Power and M-NET Transmission LinesConnecting the Sensors Connecting Alarm Setpoint Outputs Non-valtage Contacts Initial Settings Ch1 Supported Function Dip Switch FunctionsLED Display Designations Alarm Setpoint Output and Error DisplaysSensor and Communication Error Displays System Operation Test Electromagnetic Compatibility Directive